Vermont Casting STR36 Planning Information, Mounting the Fireplace, Planning the Chimney Run

Page 7
Planning Information

STR/CVR Series Woodburning Fireplaces

Planning Information

Preplanning an installation is very important to ensure safety and to save time and money. An installer must predetermine where a fireplace will be set and how the chimney system will be run.

NOTE: STR33/36 and CVR36 models use CFM Cor- poration SK8 (2-wall) chimney systems. STR/CVR42 Fireplaces use only model 11CF chimney system.

Mounting the Fireplace

A fireplace may only be mounted on the following sur- faces:

1.A flat combustible surface.

2.A raised wooden platform.

3.A concrete block or other solid object placed beneath each of the four (4) corners of the fireplace.

The fireplace must be spaced 1/2" (13mm) from a com- bustible back wall and 1/2" (13mm) from a combustible

side wall or support. (Page 14, Fig. 20)

Planning the Chimney Run

Determine how the chimney will be run, length of run and chimney components required to complete the job. (Fig. 6) Never install a chimney below minimum heights.

L

 

T

 

MODEL SK &

TOTAL

INSTALLED

 

 

 

MODEL 11 CF

LENGTH

LENGTH

 

 

 

2 WALL CHIMNEY

(LT)

(L1)

 

 

 

 

 

 

L

 

1

 

SK81 / 11CF1

�����"

�����"

 

 

 

 

 

SK818 / 11CF18

�����"

�����"

 

 

 

 

 

 

L

 

 

 

SK83 / 11CF3

�����"

�����"

 

 

 

 

 

1

 

SK84 / 11CF4

�����"

�����"

 

 

 

 

 

 

 

 

FP705

Fig. 6 Installed lengths of chimney sections.

In planning a chimney system, it is important to know:

1.The height of a chimney is measured from the hearth to the exit point on the termination.

2.A chimney cannot be offset more than 30° from a vertical plane.

3.A chimney may run straight up or it may be neces- sary to offset it to avoid obstructions.

4.The maximum length of an angled run (total chimney system) is 20' (6m).

5.No more than 2 offsets (4 total 30˚ elbows in U.S./or 2 total 45° elbows in Canada) per fireplace may be used.

6.A guy wire stabilizer is required for chimneys extend- ing more than 6' (1.8m) above a roof line.

The Ten Foot Rule

Major U.S. building codes specify a minimum chimney height above the roof top. The “Ten Foot Rule” is a fire safety rule and not a draft rule. To ensure proper draft, it is recommended that you always meet or exceed the “Ten Foot Rule,” especially when installing a termination on a high pitch roof. (Fig. 7)

The key points of the "Ten Foot Rule" are:

1.If the horizontal distance from the chimney to the peak of the roof is 10' (3m) or less, the top of the chimney must be at least 2' (610mm) above the peak of the roof, but never less than 3' (914mm) in height above the highest point where it passes through the roof.

2.If a horizontal distance from the chimney to the peak of the roof is more than 10' (3m), a chimney height reference point is established on the surface of the roof a distance of 10' (3m) from the chimney in a horizontal plane. The top of the chimney must be at least 2' (610mm) above the reference point, but never less than 3' (914mm) in height above the high- est point where it passes through the roof.

0 To 10'

 

2' Min. 3'

0 To 10'

Min.

 

 

2' Min. 3'

 

Min.

Reference

Point

AC246

Fig. 7 Ten Foot Rule illustration.

7412961

7

Image 7
Contents STR/CVR Series STR33 STR36 STR42 CVR36 CVR42DO NOT DISCARD THIS MANUAL: Retain for future use Homeowners Installation and Operating ManualSTR/CVR Series Woodburning Fireplaces Safety InformationTable of Contents Precautions7412961 STR Series Woodburning FireplaceCVR Series Woodburning Fireplace STR/CVR Series Woodburning FireplacesCVR Fireplace STR/CVR Series Woodburning FireplaceSTR/CVR Series Woodburning Fireplaces STR FireplaceFig. 4 Fireplace and chase parts identification Chase InstallationSTR/CVR Series Woodburning Fireplaces 7412961STR/CVR Series Woodburning Fireplaces Chimney Requirements - Offset Installations30˚ Elbow Offsets Illustration KeyThe Ten Foot Rule Planning InformationMounting the Fireplace Planning the Chimney RunInsulating Fireplace Enclosure for Cold Climates InstallationChase Installation Chimney SupportsChimney Set-up Straight-UpChimney InstallationOffset Installation FramingSTR/CVR Series Woodburning Fireplaces Ceiling Chimney Hole Possible ObstructionsCutting the Hole Framing the Ceiling Hole7412961 Positioning, Safety Strips Securing the FireplaceOutside Air Kit STR/CVR Series Woodburning Fireplacesin the Ceiling Hole Installing the Chimney SystemInstalling the Firestop Spacer Proper Firestop Spacer InstallationPenetrating the Roof Continue Installing Pipe to Complete RunCanadian Requirements for Insulation Shield Additional CeilingsAir Space Clearances Install Remainder of Chimney SectionsInstalling Top Housing or Termination Installing Chimney In a ChaseMantel Clearance STR/CVR Series Woodburning Fireplaces7412961 Mantel ClearanceB D C Side Wall ProtectionSTR/CVR Series Woodburning Fireplaces B C CSTR/CVR Series Woodburning Fireplaces Minimum Hearth Extension DimensionsHearth Installation Minimum Wall Clearances7412961 COMMON MATERIALS AND FACTORSSTR/CVR Series Woodburning Fireplaces Example for Common BrickSTR/CVR Series Woodburning Fireplaces Installing Line for Gas Logs7412961 CVR36 CVR36/42 SERIESSTR/CVR Series Woodburning Fireplaces DescriptionSTR/CVR Series Woodburning Fireplaces STR33/36/42 SERIES7412961 STR/CVR Series Woodburning Fireplaces AccessoriesSTR/CVR Series Woodburning Fireplaces Chimney ComponentsFirestop U.S. Chimney Components, contdCanada STR/CVR Series Woodburning Fireplaces7412961 STR/CVR Series Woodburning Fireplaces7412961 STR/CVR Series Woodburning FireplacesC. Fan Motor LIMITED WARRANTY & 30 YEAR PROTECTION PLAN7412961 B.Firegrate, Glass Doors, Outside Air SystemCFM Corporation