Vermont Casting NV360, NV580 manual Framing and Finishing, Gas Specifications, Air Shutter Setting

Page 6

NV360/580 Series

Framing and Finishing

Check appliance to make sure it is levelled and properly positioned.

1.Choose unit location.

2.Nailing flanges are supplied with the fireplace (found on the fireplace hearth). To level the box and secure it firmly in place, remove the nailing flanges from the hearth and install at the sides of the firebox as shown in Figure 3.

3.Screw through the slotted holes in the drywall strip and into pre-drilled holes in fireplace side. Measure from face of fireplace to the face of the drywall strip to confirm the final depth.

 

C

Adjustable Drywall Strip

 

 

 

A

(Nailing Flanges)

 

B

Screw

Drywall

 

 

Position

Depths

 

 

A

1/2" / 13 mm

 

 

B

5/8" / 16 mm

 

 

C

3/4" / 19 mm

 

 

Adjustable

 

 

1/2", 5/8" & 3/4"

 

 

Spacing

 

 

 

FP1023

Fig. 3

Nailing flanges.

 

 

Finishing

Noncombustible materials such as brick and tile can be extended over the face of the unit (Do not cover the glass door or grille). If a trim kit is to be installed, brick and tile will have to be installed flush with the side of this appliance.

Gas Specifications

 

 

 

Max.

Min.

Model

Fuel

Gas Control

Input

Input

NV360RN

Natural

Millivolt Hi/Lo

33,500

23,500

NV360RP

Propane

Millivolt Hi/Lo

33,500

23,700

NV580RN

Natural

Millivolt Hi/Lo

45,000

31,500

NV580RP

Propane

Millivolt Hi/Lo

45,000

31,900

6

Air Shutter Setting

Model

Front

Rear

NV360RN

closed

closed

NV360RP

open

open

NV580RN

closed

closed

NV580RP

open

open

Gas Inlet & Manifold Pressures

 

Natural

LP

 

 

 

Minimum Inlet Pressure

5.5" w.c.

11" w.c.

Maximum Inlet Pressure

14.0" w.c.

14.0" w.c.

Manifold Pressure

3.5" w.c.

11" w.c.

 

 

 

NV360 / NV580

Certified to

ANSI Z21.50b-2002 / CSA 2.22b-2002

Vented Gas Fireplace

Units: H31A00, H31B00, I31A00, I31B00

High Elevations

Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370m) above sea level.

For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.

In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).

Gas Line Installation

When purging gas line the front glass must be removed.

The gas pipeline can be brought in through the right side of the appliance. Knockouts are provided at conve- nient locations to allow for the gas pipe installation and testing of any gas connection.

The gas line connection can be made with properly tinned 3/8” copper tubing, 1/2” rigid pipe or an approved flex connector. Since some municipalities have addi- tional local codes, it is always best to consult your local authority and the CSA-B149.1installation codes.

For USA installations consult the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.

Always check for gas leaks with a mild soap and water solution applied with a brush no larger than 1” (25 mm). Never apply soap and water solution with a spray bottle. Do not use an open flame for leak

testing.

20003565

Image 6
Contents Model NV360 NV580 What to do if you smell gasTable of Contents Installation & Operating Instructions Please Read the Following CarefullyFraming Dimensions NV360 NV580Hearth Extension Clearance to CombustiblesMantels AppliancesFraming and Finishing Air Shutter SettingGas Line Installation FinishingRemote ON/OFF Switch Installation Alternate Switch LocationEB-1 Electrical Box Install the Venting System Flashing and Termination Ceiling InstallationVenting Runs Operating Instructions Flame Characteristics Ember Material PlacementFlame Adjustment Lava RockDV580 Inspecting the Venting SystemTest Chimney Draw DV360Vent Safety Switch First FiringElectrical Connection Vent Safety Switch wiring, EN/EP units Lighting And Operating Instructions To Turn Off Gas to HeaterTroubleshooting Honeywell VS8420 Standing PilotThermocouple Nova SIT820 Valve Fuel Conversion InstructionsHoneywell Valve Burner and Pilot Orifice ConversionReplacement of Ceramic Hearth Panels Remove air shutter from burner panLogs May Be HOT MaintenanceCleaning the Standing Pilot Control System Burner and Burner CompartmentNV360/580 Description NV360 NV580NV360/580 Fuel Conversion Kits FK24 Fan Assembly AccessoriesFK12 Fan Assembly Hard Direct Wire Hook UpDecorative Frame Trims Remote ControlsCeramic Refractory Lining Vent AdapterNV360/580 Series Limited Lifetime Warranty CFM Corporation