FMI VFP30R, VFP24R, VFP18R Checking GAS Connections, Pressure Testing Heater Gas Connections

Page 12

FIREPLACE MANUFACTURERS INC.

UNVENTED PROPANE/LP GAS LOG HEATER

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines under Con- necting to Gas Supply, page 11.

Test Pressures Equ al To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 15).

2.Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve.

3.Check all joints from propane/LP sup- ply tank to equipment shutoff valve (see Figure 16). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Open

Equipment

Shutoff

Valve

O

ClosedPOSI

Figure 15 - Equipment Shutoff Valve

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Fig- ure 15).

2.Open propane/LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to gas control (see Figure 15). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 14 through 16). Check all other internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 15).

Pressure Testing gas Supply Piping system

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect appliance with its appliance

 

main gas valve (control valve) and equip-

 

ment shutoff valve from gas supply pip-

 

ing system. Pressures in excess of 1/2

 

psig will damage heater regulator.

2.

Cap off open end of gas pipe where

 

equipment shutoff valve was con-

 

nected.

3.

Pressurize supply piping system by ei-

Propane/LP

Supply

Tank

Equipment

Shutoff Valve

Control Valve

Location

 

ther using compressed air or opening

 

propane/LP supply tank valve.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment

 

shutoff valve to gas supply. Check re-

 

connected fittings for leaks.

Figure 16 - Checking Gas Joints

12

105073

Image 12
Contents Unvented VENT-FREE PROPANE/LP GAS LOG Heater What to do if YOU Smell GASSafety Information Product Features Unpacking Local CodesProduct Identification Optional Remote Control Accessories AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Installation Check GAS TypeIf Using Mantel Minimum Noncombustible Material ClearancesDetermining Minimum Mantel Clearance When Using a Hood Mantel ClearancesFloor Clearances Determining Minimum Mantel ClearanceInstalling Damper Clamp Accessory for Vented Operation Installing Heater Base AssemblyInstallation Items Needed Connecting to GAS Supply Minimum inlet pressure for purpose of input adjustmentPressure Testing Heater Gas Connections Pressure Testing gas Supply Piping systemChecking GAS Connections Installing Logs Installing Front Log #1For Your Safety Read Before Lighting Operating HeaterLighting Instructions Manual Lighting Procedure To Turn OFF GAS to ApplianceOptional Remote Operation Inspecting Burners Pilot Flame PatternFront Burner Flame Pattern Cleaning and Maintenance Cleaning Burners Injector Holder and Pilot AIR Inlet HoleLogs Troubleshooting Observed Problem Possible Cause RemedySee Wiring Diagram, Gas leak. See Warning statement Specifications Wiring DiagramReplacement Parts Service HintsIllustrated Parts Breakdown VFP18R VFP24R VFP30RParts List KEY Part Numbers VFP18R VFP24R VFP30R Description QTYAccessories 105073 Warranty Information