CFM Corporation A132, A125 manual Troubleshooting the Gas Control System

Page 15

Gas Fireplace Insert

Troubleshooting the Gas Control System

SIT NOVA 820 Millivolt Valve

NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.

WARNING: Before doing any gas control service work, remove glass front.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

 

 

 

 

1. Spark ignitor will not light

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off

 

 

electrode at pilot.

pilot and push the red button again. If pilot will not

 

 

 

light - check gap at electrode and pilot-should be

 

 

 

1/8" to have a strong spark.

 

 

 

 

 

 

B. Defective ignitor (Push Button)

Push Piezo Ignitor Button. Check for spark at

 

 

 

electrode and pilot. If no spark to pilot, and elec

 

 

 

trode wire is properly connected, replace ignitor.

 

 

 

2. Pilot will not stay lit after

A. Defective pilot generator

Check pilot flame. Must impinge on thermo

carefully following lighting

(thermocouple), remote wall

couple/thermopile. Note: this pilot burner assem

instructions.

switch.

bly utilizes both-a thermocouple and a thermopile.

 

 

 

The thermocouple operates the main valve

 

 

 

operation (On and Off). Clean and or adjust pilot for

 

 

 

maximum flame impingement on thermopile and

 

 

 

thermocouple.

 

 

 

 

 

 

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot;

 

 

 

milivolt meter should read greater than 10 mV. If

 

 

 

the reading is okay and the pilot does not stay on,

 

 

 

replace the gas valve. Note: An interrupter block

 

 

 

(not supplied) must be used to conduct this test.

 

 

 

3. Pilot burning, no gas to

A. Wall switch or wires defective

Check wall switch and wires for proper connec

main burner

 

tions. Jumper wire accross terminals at wall

 

 

 

switch, if burner comes on, replace defective wall

 

 

 

switch. If okay, jumper wires across wall switch

 

 

 

wires at valve, if burner comes on, wires are faulty

 

 

 

or connections are bad.

 

 

 

 

 

 

B. Thermopile may not be

1. Be sure wire connections from thermopile at

 

 

generating sufficient

gas valve terminals are tight and thermopile is

 

 

millivoltage.

fully inserted into pilot bracket.

 

 

 

2. One of the wall switch wires may be grounded.

 

 

 

Remove wall switch wires from valve terminals if

 

 

 

pilot now stays lit, trace wall switch wiring for

 

 

 

ground. May be grounded to fireplace or gas

 

 

 

supply.

 

 

 

3. Check thermopile with millivolt meter. Take

 

 

 

reading at thermopile terminals of gas valve.

 

 

 

Should read 250-300 millivolts (minimum 150)

 

 

 

while holding valve knob depressed in pilot

 

 

 

position and wall switch “Off”. Replace faulty

 

 

 

thermopile if reading is below specified minimum.

 

 

 

 

 

 

C. Plugged burner orifice.

Check burner orifices for debris and remove.

 

 

 

 

 

 

D. Defective automatic valve

Turn valve knob to “On”, place wall switch to “On”

 

 

operator.

millivolt meter should read greater than 100 mV. If

 

 

 

the reading is okay and the burner does not come

 

 

 

on, replace the gas valve.

 

 

 

4. Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

 

 

pilot safety to drop out.

 

 

 

 

 

 

 

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the

 

 

terminal.

flue gases)

 

 

 

 

10002964

15

Image 15
Contents Gas Fireplace Insert Table of Contents Insert Applications Installation & Operating InstructionsA125 A132 Locating Your Gas Fireplace Insert With Zero Clearance Kit Framing & FinishingMantels Gas Specifications Gas Line InstallationCombustion Air Zero Clearance ApplicationsInstallation of Remote Switch For RN/RP Gas Valves Adjustment of Leveling Bar If RequiredGas Supply Pressures Venting Instructions Venting and InstallationDraft Relief Opening Common Flue InstallationsLiner Installation Vent Safety SystemFan Removal Instructions Fan Kit InstallationGeneral Glass Information Glass CleaningInstallation of Logs and Ember Material Operating InstructionsFlame Adjustment RN/RP Models Large Lava Rock PlacementFirst Firing Flame CharacteristicsTo Turn Off Gas To Heater Lighting and Operating InstructionsSymptom Possible Causes Corrective Action Troubleshooting the Gas Control SystemHoneywell Millivolt Valve Burner and Burner Compartment MaintenanceCleaning the Standing Pilot Control System Brass CleaningDescription A125 A132 A125, A132 Gas InsertJT2TB0 KT2TB0 Optional Accessories RHE25SSP & HE25LP Replacement Parts A2 HE25FP TrimFor use with A125 HE25FP Replacement Parts Do not remove existing glass with frameOnly for RN/RP Valve units HE25BTKP HE25BTKP Replacement PartsRhesxl Trims Frame AssemblyA4 Riser Kits Trim Options for A132Frame Mounting General Information Rhessd and Rhesld trim assemblyThese products RHESS, RHESL, RHESSD, RHESLD, Rhesxl Trim Replacement PartsImportant Only trim panel assemblies ap Proved by CFM Corporation can be used onB6 Arch Door Kit Gas Fireplace Insert Gas Fireplace Insert Gas Fireplace Insert Limited Lifetime Warranty CFM Corporation

A132, A125 specifications

CFM Corporation, a renowned leader in the aviation industry, has made significant strides with its advanced jet engines, particularly the CFM56 series, which includes models like the A132 and A125. These engines are propelling the next generation of commercial aviation with their focus on fuel efficiency, reliability, and reduced emissions.

The CFM A132 and A125 engines are specifically designed for narrow-body aircraft, making them ideal for short to medium-haul flights. One of the standout features of the A132 is its exceptional thrust performance, providing operators with a thrust range that ensures versatility in various flight conditions. The A125, while slightly lower in thrust output, boasts impressive fuel efficiency, contributing to lower operational costs for airlines.

Both models utilize advanced materials and manufacturing techniques that enhance durability and performance. CFM incorporates innovative ceramic matrix composites (CMCs) and advanced alloys in their designs. These materials offer increased resistance to high temperatures and reduce overall weight, resulting in improved engine performance and longevity.

A key technology present in both A132 and A125 engines is the 3D-printed components, which enable intricate designs that were previously impossible or too costly to produce. This innovative manufacturing method not only simplifies production but also reduces waste and enhances the engines' overall performance.

Noise reduction technologies are also a priority, as the aviation industry increasingly focuses on minimizing its environmental impact. Both models feature advanced acoustic liners and the latest in fan blade design, significantly decreasing noise levels during operation. This is particularly beneficial for airlines operating flights in and out of urban areas where noise restrictions may apply.

Moreover, CFM's engines are renowned for their reliability, with maintenance intervals designed to extend engine life and reduce downtime. The A132 and A125 benefit from CFM's extensive experience and proactive approach to service, ensuring operators have access to support throughout the engine's lifecycle.

In summary, CFM Corporation's A132 and A125 engines represent a blend of advanced engineering, innovative technologies, and customer-centric design. With their powerful performance, fuel efficiency, and commitment to environmental sustainability, these engines are set to continue shaping the future of aviation. Airlines that invest in these models gain not only superior operational capabilities but also the promise of reliability and cost-effectiveness in an increasingly competitive market.