Enviro C-11275 owner manual Trouble Shooting, Problem Possible Cause Solution

Page 35

Trouble Shooting

Problem

Possible Cause

Solution

 

 

 

The main burner does not

The gas valve may not be on.

• Check that the gas control knob is in the “ON” position.

ignite when called for.

 

 

Thermostat is not calling for

• Adjust the thermostat several degrees above ambient

 

 

heat.

temperature.

 

 

 

 

Problem with gas valve.

• Use a DC voltmeter to measure the voltage across the

 

 

TPTH and TP terminals. Main operator voltage: Open

 

 

circuit ≥ 325mV Closed circuit ≥ 100mV

 

 

• If voltage is not present, check the control circuit for

 

 

proper operation.

 

 

• If proper control system voltage is present, replace the

 

 

gas control.

 

 

 

Spark will not light the pilot

Defective piezo ignitor.

• Check connections to ignitor.

after repeatedly pressing the

 

• If ignitor connections are good but no spark, replace

spark ignitor.

 

ignitor.

 

 

 

 

Broken spark electrode.

• Check for broken ceramic insulation, replace electrode if

 

 

broken.

 

 

 

 

Misaligned spark electrode.

• If spark is not arcing from electrode to pilot, loosen the

 

 

screws on the pilot base adjust and tighten.

 

 

 

Pilot will not remain lit.

Problem with thermocouple

• Check for proper connection of the thermocouple to the

 

circuit.

rear of the valve. If loose, fully tighten.

 

 

• Check pilot for full flame impingement around

 

 

thermocouple. If flame is too small, check gas pressure,

 

 

adjust pilot rate screw, check pilot head for damage.

 

 

• Check thermocouple voltage at valve. It must be greater

 

 

than 5 mV. If low, replace thermocouple.

 

 

 

 

Air in gas line (pilot dies while

• Bleed line.

 

knob is depressed).

• Check gas line pressure.

 

 

• Contact dealer.

 

 

 

Burners will not remain lit.

Problem with thermopile

• Check gas line pressure .

 

circuit.

• Check for flame impingement on thermopile. If low, see

 

 

“Pilot will not remain lit”.

 

 

• Check thermopile for minimum of 300 mV when burner is

 

 

switched on.

 

 

• Check wiring to thermostat for breaks.

 

 

 

Flame lifting

Leak in vent pipe

• Check for leaks in vent connections.

 

 

 

 

Improper vent configuration

• Check vent configuration with manual.

 

 

 

 

Terminal may be recirculating

• Check to see if terminal is on correctly.

 

flue gases

• May need to install high wind termination cap.

 

 

• Contact dealer.

 

 

 

Glass fogs up

Normal Condition: after the appliance warms up the glass will clear.

 

**Due to additives in gas, glass may get hazy during operation** Clean as needed.

 

 

 

Blue Flames

Normal during start up: flames will yellow as the fireplace heats up.

 

 

 

Flames are burning “dirty” or

Flame impingement

• Check log positioning.

sooting

 

• Increase primary air by opening the venturi shutter and/

 

 

or by opening the vent restrictor.

 

 

See also “Burners will not remain lit.”

 

 

 

Remote control doesn’t work

Problem with the remote

• One or more of the batteries are dead. See remote

 

 

control instructions.

 

 

 

 

Problem with fireplace

• The on/off switch is turned to OFF.

 

 

• The gas control valve is turned to PILOT or OFF.

 

 

• The pilot has gone out.

 

 

 

35

Image 35
Contents 50-927 General Safety PrecautionsTable of Contents This Enviro DV36 Fireplace Codes And ApprovalsInstallation Options SpecificationsOperating Instructions For Your Safety Read BeforeBlue, the fireplace is getting too much Component Sound & Reason To Turn GAS Fireplace OFFMaintenance And Service Bottom latches for glass Never Operate Fireplace with the glass RemovedCompletely cooled down Kit Parts ListRemoving valve Screw Conversion Kit InstallationRing on valve screw Qualified Installers only Initial InstallationDo not interfere with the structural integrity of the walls Mantel Clearances Vent Termination Restrictions KIT Components Manufacturer Trade Name Nominal Sizes Installation of Fireplace Horizontal Vent Kit4DSC Two 2 piece wall Vent restrictor is located in the center Being Attached to Wood Vertical Vent Termination AssembleRoof Pitch Minimum Height H Feet Meters Use of Wall Straps Installation of Electrical Wiring for the Optional FAN KIT Max Supply Pressure Natural Gas Propane Main OrificeManifold Pressure Min. Manifold PressureEmpty firebox with grate and locator pins Secondary InstallationThird Stage Log Set Installation Complete log set-up with embers Never operate the fireplace with the glass door removedBack Panel In Place Turn off the gas control knob and allow the unit to coolKit Contents Hook Fan Tabs Over Grommets at Unit Back Installation of KitProblem Possible Cause Solution Trouble ShootingReference Part Description Part Number Parts ListParts List Options DiagramParts To the Dealer WarrantyWarranty Warranty Installation Data Sheet

C-11275 specifications

Enviro C-11275 is an innovative solution designed specifically for enhancing environmental management and sustainability efforts across various sectors. As industries begin to recognize the importance of minimizing ecological footprints, the demand for advanced technologies and products like Enviro C-11275 has surged. This product is engineered to address pressing environmental challenges, offering a blend of efficiency, reliability, and versatility.

One of the main features of Enviro C-11275 is its eco-friendly formulation, which significantly reduces harmful emissions compared to traditional alternatives. This characteristic aligns with global sustainability goals and regulatory requirements, making it an ideal choice for companies striving to meet their corporate social responsibilities. Moreover, the product is designed to be biodegradable, ensuring that it does not linger in the environment, thereby contributing to soil and water health.

Enviro C-11275 incorporates advanced nanotechnology that enhances its performance. The application of nanoscale additives allows for improved reactivity and a higher efficacy in contaminant removal. This technology ensures that even in small doses, Enviro C-11275 can achieve substantial results in remediation projects, making it cost-effective and efficient.

Furthermore, Enviro C-11275 features a user-friendly application system. Whether applied via spraying, injection, or mixing, the flexibility of its use allows for a wide range of practical applications, from agricultural to industrial cleaning. This adaptability makes it suitable for diverse fields, including manufacturing, waste management, and even residential maintenance.

One of the standout characteristics of Enviro C-11275 is its safety profile. Composed of non-toxic ingredients, it poses minimal risk to human health and the environment, setting it apart from other chemical solutions that often carry hazardous warnings. This safety aspect is paramount, particularly in industries where workers are regularly exposed to potentially harmful substances.

In addition, Enviro C-11275 is backed by extensive research and development. The formulation is the result of rigorous testing and validation, ensuring that it not only performs well but also meets stringent environmental standards. This commitment to excellence provides users with confidence in its efficacy and reliability.

Overall, Enviro C-11275 emerges as a leading contender for businesses focused on environmental stewardship. With its eco-friendly formulation, advanced nanoscale technology, versatile application methods, and strong safety profile, it stands as a testament to the ongoing evolution of sustainable products aimed at protecting our planet for future generations.