Breckwell P2000FS, P2000I Combustion AIR Supply, When Outside AIR is not Used, Venting

Page 6

6

INSTALLATION

COMBUSTION AIR SUPPLY

For a mobile home installation the stove must be connected to an outside source of combustion air. A 2” inside diameter metallic pipe, either flexible or rigid, may be attached to the inlet at the stove’s rear (refer to figures 5 & 6). A rodent guard (minimum ¼” wire mesh)/wind hood must be used at the terminus (refer to figure 7). All connections must be secured and airtight by either using the appropriately sized hose clamp and/or UL-181-AP foil tape.

For mobile home installations only: 2” inside diameter pipe may be used for the first 5 feet of combustion air supply run. From 5 to 10 feet use 2 ¾” inside diameter pipe. No combustion air supply may exceed 10 feet.

Sources of Outside Combustion Air

a.In fireplaces

Chimney top.

Ash clean out door.

b.For freestanding installations

A hole in floor near stove rear terminating only in a ventilated crawl space.

A hole in the wall behind the stove.

WHEN OUTSIDE AIR IS NOT USED

If outside air is not used, it is important that combustion air is easily available to the air inlet. A closeable outside air register can be used in tightly insulated homes. In insert installations, flashing vents should not be restricted. The flashing should not necessarily seal the fireplace face.

VENTING

The Breckwell P2000 is certified for use with listed TYPE L-Vent, 3” or 4” diameter in size. The stove was tested with Simpson Duravent brand. Class “A” chimney is not required. Refer to the instructions provided by the vent manufacturer, especially when passing through a wall, ceiling or roof.

This is a pressurized exhaust system. We suggest sealing all vent connector joints with 500°F (260°C) RTV silicone sealant to ensure consistent performance and to avoid smoke spillage. We also suggest that all horizontal connector joints be sealed with UL-181- AP foil tape.

FOLLOW L-VENT CHIMNEY MANUFACTURER’S INSTALLATION INSTRUCTIONS.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.

REAR VIEW P2000FS

FIGURE 5

REAR VIEW P2000I

FIGURE 6

FIGURE 7

Image 6
Contents Luxury Series P2000 Introduction Important InformationSafety Precautions Table of Contents Installation Venting When Outside AIR is not UsedCombustion AIR Supply Rear View P2000FS Rear View P2000IFreestanding Installation Equivalent Vent Length EVLHorizontally Through Wall Vertically with NEW Chimney System Refer to Figure Vertically Into Existing Chimney SystemInstallation Through Side of Masonry Chimney Vertically Into Existing Masonry FireplaceInsert Installations Assembling the Flashing SETWhen Vent Pipe Extends to Chimney TOP Refer to Figure Chase dimensions shown are minimums and must be maintained AS a BUILT-IN FireplaceElectrical Installation Special Mobile Home RequirementsOperation Building a Fire Proper FuelPRE-START-UP Check Hotrod Automatic FirestarterSafety Features Breckwell Maintenance ToolShutdown Procedure RE-STARTING a Warm StoveOptional Thermostat Thermostat InstallationThermostat Installation Millivolt Thermostat is RequiredPlease Read this ASH Disposal Freestanding Models MaintenanceASH Removal ASH Disposal InsertCleaning Vacuum USEBlowers Removal and Replacement of Broken Door Glass Chimney CleaningRecommended Maintenance Schedule Daily Weekly Annually or per TonP2000I Troubleshooting Guide Stove Shuts OFF and the # 2 Light FlashesPossible Causes Stove Shuts OFF and the # 3 Light Flashes Smoke Smell Coming Back Into the Home Stove Feeds PELLETS, but will not IgnitePossible Causes Possible Remedies Convection Blower Shuts OFF and Comes Back onTroubleshooting Guide Troubleshooting Guide Digital Circuit Board Timing Rates High Limit Switch Keeps TrippingSmoke Smell or Soot BUILD-UP P2000Electrical Diagram Replacement Parts BurnpotLifetime Limited Warranty
Related manuals
Manual 31 pages 35.78 Kb Manual 30 pages 40.93 Kb