Breckwell P2000FS, P2000I owner manual Freestanding Installation, Equivalent Vent Length EVL

Page 7

INSTALLATION

7

Equivalent Vent Length (EVL)

The longer the run of pipe in your installation (both with insert and freestanding), the more restriction there is in the system. Therefore, larger diameter pipe should be used.

Use 4” pipe if you have more than 15 feet of Equivalent Vent Length.

Horizontal runs shall not exceed 10 feet of EVL.

Recommended vertical runs to be a minimum of 8 feet.

To calculate EVL, use the following conversions:

90º elbow or “T”

= 5 equivalent feet

45º elbow

= 3 equivalent feet

Horizontal Pipe Run

= 1 equivalent foot per actual foot

Vertical Pipe Run

= 0.5 equivalent foot per actual foot

NOTE: At altitudes above 3,000 feet, we suggest the use of 4” diameter vent at an EVL of 7 feet or more.

FREESTANDING INSTALLATION

A. HORIZONTALLY THROUGH WALL

(refer to Figure 8)

NOTE: See “VENTING” and follow L-Vent chimney manufacturer’s instructions.

1.Position stove, adhering to clearances shown in Figures 1 & 2.

2.Locate position of hole in wall; directly behind stove exhaust vent (refer to figure 5).

3.Always maintain 3” clearance from combustible materials.

4.Install L-Vent wall thimble per L-Vent manufacturer’s instructions.

5.Attach enough piping to penetrate and extend at least 6” beyond exterior walls. An 8-foot vertical pipe run is suggested where possible to reduce the possibility of smoke spillage in the event of a loss of negative pressure.

6.Attach cap and seal outside wall thimbles with non-hardening waterproof mastic.

Termination should not be located so that hot exhaust gases can ignite trees, shrubs, or grasses or be a hazard to children. Exhaust gases can reach temperatures of 500ºF and cause serious burns if touched.

FIGURE 8

Locate terminations: a) not less than 3 feet above any forced air inlet located within 10 feet; b) not less than 4 feet below or horizontally from, or one foot above, any door, window or gravity air inlet into any building; c) not less than two feet from an adjacent building and not less than 7 feet above grade when located adjacent to a public walkway. Mobile home installations must use a spark arrester.

Image 7
Contents Luxury Series P2000 Important Information IntroductionSafety Precautions Table of Contents Installation Rear View P2000FS Rear View P2000I When Outside AIR is not UsedCombustion AIR Supply VentingEquivalent Vent Length EVL Freestanding InstallationHorizontally Through Wall Vertically Into Existing Chimney System Vertically with NEW Chimney System Refer to FigureVertically Into Existing Masonry Fireplace Installation Through Side of Masonry ChimneyAssembling the Flashing SET Insert InstallationsWhen Vent Pipe Extends to Chimney TOP Refer to Figure AS a BUILT-IN Fireplace Chase dimensions shown are minimums and must be maintainedSpecial Mobile Home Requirements Electrical InstallationOperation Hotrod Automatic Firestarter Proper FuelPRE-START-UP Check Building a FireRE-STARTING a Warm Stove Breckwell Maintenance ToolShutdown Procedure Safety FeaturesMillivolt Thermostat is Required Thermostat InstallationThermostat Installation Optional ThermostatPlease Read this ASH Disposal Insert MaintenanceASH Removal ASH Disposal Freestanding ModelsVacuum USE CleaningBlowers Daily Weekly Annually or per Ton Chimney CleaningRecommended Maintenance Schedule Removal and Replacement of Broken Door GlassP2000I Stove Shuts OFF and the # 2 Light Flashes Troubleshooting GuidePossible Causes Stove Shuts OFF and the # 3 Light Flashes Convection Blower Shuts OFF and Comes Back on Stove Feeds PELLETS, but will not IgnitePossible Causes Possible Remedies Smoke Smell Coming Back Into the HomeTroubleshooting Guide Troubleshooting Guide P2000 High Limit Switch Keeps TrippingSmoke Smell or Soot BUILD-UP Digital Circuit Board Timing RatesElectrical Diagram Burnpot Replacement PartsLifetime Limited Warranty
Related manuals
Manual 31 pages 35.78 Kb Manual 30 pages 40.93 Kb