Nortec 132-3091 manual NH Electric Steam Humidifier

Models: 132-3091

1 40
Download 40 pages 44.79 Kb
Page 29
Image 29
NH Electric Steam Humidifier

NH Electric Steam Humidifier

Humidifier Mandatory Pre Start-up Checklist (p. 1 of 1)

Unit Serial #: _ _ _ _ _ _ _ _

# of humidifiers: _____

Tag:_____________

Unit type:

 

 

Voltage: _____V/___ph

Steam output: ____lbs/hr

Customer/Job:_______________

Address: __________________________________

Inspected by: ________________

Date of inspection:____/____/____

_____________________________________________________________________________________________

WATER QUALITY:

 

 

 

 

 

Well water ￿

City water ￿

Softened wate ￿

RO / DI water ￿

Conductivity: _______mhmos

 

Hardness: _____ gr.

 

HUMIDIFIER MOUNTING:

 

 

 

 

Clearances around the unit

Acceptable

Obstruction

- Front (door opens freely?)

 

3ft min

____________________

- Top (steam lines)

 

2ft min

____________________

- Bottom (fill, drain, controls)

2ft min

____________________

- Right (main pwr)

 

2ft min

____________________

STEAM LINES:

 

 

CONDENSATE LINES:

- Slope up 2” per 12” ￿

 

- Slopped back to drain ￿

 

- Slope down ½” per 12” ￿

- Trapped 2” more than static duct pressure ￿

- Traps ￿

 

 

- Size _______

 

 

- Insulated ￿

 

 

- Stainless steel ￿ or plastic ￿

- Length/Size _____/_______

 

- ________% Vertical _______% Horizontal

- 90 deg. elbows￿ qty: ____

- 45 deg. Elbows￿

qty: ____

- Can condensate be trapped anywhere in the steam line? Yes ￿ no ￿

WATER LINES:

 

 

 

 

 

- ½” at max 4ft from the unit ￿

- 3/8” connection at fill ￿

 

 

- water pressure: 30-80psig ￿

- PVC ￿

 

- Stainless steel ￿

DRAIN LINES:

 

 

 

 

 

- Air gap located within 3ft of the unit ￿

- Slopped to drain ￿

- Size:________

CYLINDER:

- Cylinder properly installed and sitting upright

WIRING:

- No loose wires around the unit or on the PC board? yes ￿ no ￿

CONTROLS: Installed Location / Wiring /Setting

 

Installed Location / Wiring /Setting

- High limit:

￿___________________

- Air proving: ￿___________________

- Mod controller: ￿___________________

- Other:

￿___________________

POWER:

-Voltage, amperage rating and fuse correspond to Spec Label ￿

-Disconnect switch located close to humidifier ￿

-26 -

Page 29
Image 29
Nortec 132-3091 manual NH Electric Steam Humidifier