NHMC OPERATION

SIGNAL LIGHT STATUS

YELLOW

GREEN

 

 

 

 

OFF

OFF

Off

 

 

 

OFF

ON

Normal operation

ON

ON

Replace cylinder or normal

 

 

startup operation

ON

OFF

Operation fault

 

 

 

The prerequisites for getting power and water into the steam cylinder are as follows:

-on/off/drain switch must be switched on

-control circuit 8-10 must be made

-modulation humidistat, if present, must be calling

-control circuit 82-83 must be made

-control circuit 84-85 must be made

-cabinet mounted humidistat, if present, must be calling

-door interlock switch must be made (interlock switch can be pulled out to operate unit)

Most water does not contain enough conductivity for full boil on initial start-up. Units will need to concentrate the water over a time period (hours to days). During this process both lights are on.

NHMC OPERATION

START-UP SELF TEST

Observe the LCD display when the on/off/drain switch is first pushed on. The microcomputer pc board will check the system components, display in words what it is doing and provide a message if any faults are found. The start-up self-test sequence will be displayed as follows:

LCD

EXPLANATION/COMMENTS

 

(WHAT YOU READ)

 

 

CONDAIRMATIC MC

Note the V number. It tells you

 

the EPROM version.

 

 

NORTEC V2...

 

 

 

CONDAIRMATIC MC

Note the model type. Ensure

 

NHMC (model type) compatibility

 

with spec label (name plate).

 

Can be reconfigured if

 

necessary.

 

 

SYSTEM TEST

Test begins.

 

 

LAMP GREEN

Observe green signal light on

 

 

LAMP YELLOW

Observe yellow signal light on

 

 

CONTACT RELAY 1

Provides 24 VAC to 61-20 and

 

external optional yellow lamp at

 

control strip to simulate a fault.

 

 

DRAIN VALVE

Observe 24 volt solenoid

 

activated on drain valve.

 

 

INLET VALVE

Observe 24 volt solenoid

 

activated on fill valve.

 

 

CONTACTOR

Observe 24 volt coil activated

 

on contactor OR fan activated on

 

blower pack if present.

 

 

CONTACT RELAY 2

Provides 24 VAC to 63-36 and

 

external optional red lamp at

 

control strip to simulate cylinder

 

spent.

 

 

CONTACT RELAY 3

Provides 24 VAC to 62-40 and

 

external optional green lamp at

 

control strip.

 

 

INTERNAL TEST

Completion of self test.

 

 

LAMP

Observe green and yellow

GREEN-YELLOW

lamps pulse on together as sign

INTERNAL TEST

that all passed.

 

 

STEAM OUTPUT

Begins normal operation and

INTERNAL TEST

displays lbs/hr.

 

 

NOTE: If cylinder water reaches the full cylinder sensor, the LCD will read “MAXIMAL LEVEL”.