SIGNAL LIGHT STATUS
YELLOW | GREEN |
|
|
|
|
OFF | OFF | Off |
|
|
|
OFF | ON | Normal operation |
ON | ON | Replace cylinder or normal |
|
| startup operation |
ON | OFF | Operation fault |
|
|
|
The prerequisites for getting power and water into the steam cylinder are as follows:
-on/off/drain switch must be switched on
-control circuit
-modulation humidistat, if present, must be calling
-control circuit
-control circuit
-cabinet mounted humidistat, if present, must be calling
-door interlock switch must be made (interlock switch can be pulled out to operate unit)
Most water does not contain enough conductivity for full boil on initial
NHMC OPERATION
START-UP SELF TEST
Observe the LCD display when the on/off/drain switch is first pushed on. The microcomputer pc board will check the system components, display in words what it is doing and provide a message if any faults are found. The
LCD | EXPLANATION/COMMENTS |
| (WHAT YOU READ) |
|
|
CONDAIRMATIC MC | Note the V number. It tells you |
| the EPROM version. |
|
|
NORTEC V2... |
|
|
|
CONDAIRMATIC MC | Note the model type. Ensure |
| NHMC (model type) compatibility |
| with spec label (name plate). |
| Can be reconfigured if |
| necessary. |
|
|
SYSTEM TEST | Test begins. |
|
|
LAMP GREEN | Observe green signal light on |
|
|
LAMP YELLOW | Observe yellow signal light on |
|
|
CONTACT RELAY 1 | Provides 24 VAC to |
| external optional yellow lamp at |
| control strip to simulate a fault. |
|
|
DRAIN VALVE | Observe 24 volt solenoid |
| activated on drain valve. |
|
|
INLET VALVE | Observe 24 volt solenoid |
| activated on fill valve. |
|
|
CONTACTOR | Observe 24 volt coil activated |
| on contactor OR fan activated on |
| blower pack if present. |
|
|
CONTACT RELAY 2 | Provides 24 VAC to |
| external optional red lamp at |
| control strip to simulate cylinder |
| spent. |
|
|
CONTACT RELAY 3 | Provides 24 VAC to |
| external optional green lamp at |
| control strip. |
|
|
INTERNAL TEST | Completion of self test. |
|
|
LAMP | Observe green and yellow |
lamps pulse on together as sign | |
INTERNAL TEST | that all passed. |
|
|
STEAM OUTPUT | Begins normal operation and |
INTERNAL TEST | displays lbs/hr. |
|
|
NOTE: If cylinder water reaches the full cylinder sensor, the LCD will read “MAXIMAL LEVEL”.
- 8 -