Figure #13
System Messages and Responses (EPROM : 2.XXN)
NHMC
|
| UNIT STATUS LAMPS | REMOTE INDICATION (24 VAC TO:) | |||
SYSTEM MESSAGE | UNIT |
|
|
|
|
|
DISPLAYED ON LCD | CONTACTOR | YELLOW | GREEN | “YELLOW” | “GREEN” | “RED” |
Maximal Level | ON | ON | ON | OFF | ON | OFF |
|
|
|
|
|
|
|
Excess Current / Error 1 | OFF | ON | OFF | ON | OFF | OFF |
|
|
|
|
|
|
|
No Current / Error 2* | OFF | ON | OFF | ON | OFF | OFF |
|
|
|
|
|
|
|
Max. Filling Time / Error 3 | OFF | ON | OFF | ON | OFF | OFF |
|
|
|
|
|
|
|
Cylinder Spent / Error 4 | ON | ON | ON | OFF | ON | ON |
|
|
|
|
|
|
|
No Current / Error 5 | OFF | ON | OFF | ON | OFF | OFF |
|
|
|
|
|
|
|
Output Too Low / Error 6 | OFF | ON | OFF | ON | OFF | OFF |
|
|
|
|
|
|
|
Electronic / Error 7 | OFF | ON | OFF | ON | OFF | OFF |
|
|
|
|
|
|
|
Phase Interrupt / Error 8 | ON | ON | OFF | OFF | OFF | OFF |
|
|
|
|
|
|
|
Cyl. Lifespan End / Error 9 | OFF | ON | OFF | ON | OFF | ON |
|
|
|
|
|
|
|
* When No Current/Error 2 is displayed, display will change to show Maximal Level and will alternate back and forth.
NHP
|
| UNIT STATUS LAMPS |
| REMOTE INDICATION | |
|
|
|
|
| (24 VAC TO:) |
SYSTEM FAULTS* | UNIT CONTACTOR | YELLOW | GREEN |
| “YELLOW” |
Maximal Level |
| See NHMC Chart above for details |
| ||
|
|
|
|
|
|
Excess Current | OFF | ON | OFF |
| ON |
|
|
|
|
|
|
No Current | OFF | ON | OFF |
| OFF |
|
|
|
|
|
|
Max. Filling Time | OFF | ON | OFF |
| ON |
|
|
|
|
|
|
Cylinder Spent | ON | FLASHING | ON |
| OFF |
|
|
|
|
|
|
No Current | OFF | ON | OFF |
| OFF |
|
|
|
|
|
|
Output Too Low | OFF | ON | OFF |
| OFF |
|
|
|
|
|
|
Electronic | N/A | N/A | N/A |
| N/A |
|
|
|
|
|
|
Phase Interrupt | N/A | N/A | N/A |
| N/A |
|
|
|
|
|
|
Cyl. Lifespan End | OFF | FLASHING | OFF |
| ON |
|
|
|
|
|
|
*NOTE: NHP does not display actual message or error.
-Remote indication
-Remote indication
-Remote indication
-12 -