Lucent Technologies EST-48 Optional Equipment Considerations, Cold Climate Insulation

Page 15

OPTIONAL EQUIPMENT

CONSIDERATIONS

Gas Line Connection

The EST-48 has been listed to accept a ¹⁄₂" gas line for an approved gas appliance. Always have the appliance installed in accordance with all local building codes.

CAUTION: ALL GAS CONNECTIONS SHOULD ONLY BE PERFORMED BY A QUALIFIED, LI- CENSED TRADESMAN. THE MAIN GAS SUP- PLY MUST BE OFF WHEN PLUMBING THE GAS LINE TO THE FIREPLACE OR WHEN PER- FORMING SERVICE WORK.

Install a ¹⁄₂" gas supply line through fireplace wall for connection to a decorative gas appli- ance inside the firebox. Outside, the gas supply line connects to a gas shut-off valve recessed flush into the wall or floor. The valve should be controlled by a removable valve key for safety.

Always plumb gas line installation per local codes. Check all connections with soap suds; leaks will bubble. Never test any gas line con- nection with a match or open flame.

This provision is intended for connection to a decorative gas appliance incorporating an au- tomatic shut-off device and complying with the Standard for Decorative Gas Appliances for installation in vented fireplaces, ANSI Z21.60 (1991) or American Gas Association draft re- quirements for Gas-Fired Log Lighters for Wood Burning Fireplaces, Draft No. 4 dated August, 1993. Install in accordance with the National Fuel Gas Code, ANSI Z223.1. This complies with the revised U.L. 127 standard.

Vent Free Appliances

These units have been tested and approved to ANSI/IAS/AGA Z21.11.2 for use with unvented gas appliances and complies with the stan- dard for Factory-Built fireplaces, UL 127.

The unit has been tested for use with any unvented gas log sets having a maximum rating of 40,000 BTU. The minimum mantle configurations are outlined in Figure 43.

These fireplaces have been marked with a maximum rating of 40,000 BTU to assure that homeowners do not exceed the allowable lim- its for all allowed installations of mantles.

NEVER INSTALL AN UNVENTED GAS LOG SET WITH A BTU GREATER THAN 40,000.

CAUTION: WHEN USING THE DECORATIVE GAS APPLIANCE, THE FIREPLACE DAMPER MUST BE SET IN THE FULLY OPEN POSITION.

CAUTION: PLUMBING CONNECTIONS SHOULD ONLY BE PERFORMED BY A QUALIFIED, LI- CENSED PLUMBER. MAIN GAS SUPPLY MUST BE OFF WHEN PLUMBING GAS LINE TO FIRE- PLACE OR PERFORMING SERVICE.

If you’re installing a gas line, connect it before the fireplace is framed and enclosed in the finished wall. The gas knockout is determined by the indentation located at the bottom and slightly off center in the side refractories. THE

KNOCKOUT IS ALWAYS REMOVED FROM IN- SIDE THE FIREPLACE. DO NOT REMOVE THE KNOCKOUT UNLESS YOU ARE INSTALLING A GAS LINE. If removal is attempted from the outer wrapper, side refractory damage may occur. With a medium-sized hammer, lightly tap the surface of the indentation. The refrac- tory material is very thin in this area and is easily removed. Once a small hole has been made, continue tapping until you have reached suffi- cient diameter for the gas line to fit through. The entire knockout does not have to be removed. Remove insulation in the gas line channel.

IMPORTANT: REPACK INSULATION MATERIAL IN SQUARE HOLE AROUND GAS LINE, INTE- RIOR AND EXTERIOR OF FIREPLACE, TO SEAL.

Glass Doors

If glass doors are to be installed on these fireplaces, refer to specific installation instruc- tions packed with the glass doors. Use only the doors that are listed for use with these fire- places. Use of other non-listed glass door on these fireplaces may constitute a potential fire hazard and is not recommended.

CAUTION: CERTAIN GLASS DOORS OVER- LAP THE BLACK METAL FACING OF THE FIRE- PLACE. IF THE FIREPLACE HAS BEEN FACED WITH NONCOMBUSTIBLE MATERIALS, THERE MIGHT NOT BE SUFFICIENT CLEAR- ANCE TO INSTALL THE GLASS DOORS OF YOUR CHOICE. ENSURE ADEQUATE CLEAR- ANCE IS MAINTAINED AT ALL TIMES SO AS NOT TO INTERFERE WITH THE INSTALLA- TION AND OPERATION OF GLASS DOORS.

COLD CLIMATE INSULATION

If you live in a cold climate, it is especially important to seal all cracks around the fire- place opening with noncombustible material and wherever cold air could enter the room.

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Surrounding materials must be caulked where it meets the black metal facing of the fireplace to avoid cold air intrusion. Use noncombus- tible caulking material only on fireplace facing to seal. Also, the outside air inlet duct should be wrapped with noncombustible insulation to minimize the formation of condensation. Do not place insulation materials on top of fire- place or against chimney sections.

Note: A 2" air space must be preserved for all combustible materials extending for any con- tinuous length adjacent to the chimney.

It is especially important to insulate between the studs of an outside chase cavity and under the floor if the floor is above ground level. Do not place insulation directly against the fire- place or chimney system.

FIREPLACE FINISHES

Mantels and Trim

It is sometimes best to frame your fireplace after it is positioned and the chimney is in- stalled. Frame enclosure for chimney and fire- place with 2 x 4’s (or heavier) lumber.

Note: The header may rest on the two (2) metal top spacers on top of the unit but the header must not be notched to fit around the spacers.

These fireplaces may sit directly on a combus- tible surface. A 2" air space is required be- tween combustible framing and the chimney. Combustible mantels and trim may be in- stalled 12" above the fireplace opening as per NFPA 211, Section 7-2.3.3. and Figure 43. If a mantel is of a noncombustible material, it is exempt from these requirements as long as it does not interfere with the installation or op- eration of glass doors.

 

Finished

 

Wall

Combustible

 

Mantel and Trim

Header

 

12" Max.

Noncombustible

Wall Covering

 

 

Spacer

12"

1 ¹⁄₂"

Min.

 

8 ⁹⁄₁₆"

 

 

Fireplace

 

Opening

Typical Installation

Figure 43

15

Image 15
Contents WH Report No Retain These Instructions For Future ReferenceWood Burning Fireplaces 850,006M REV. C 04/2004Table of Contents Clearances and Height Requirements Typical InstallationPrecautions IntroductionLocation of Fireplace Assembly OutlineChimney Height Chase EnclosureCombustible Wall Hearth Assembly StepsPRE-INSTALLATION Notes Installing the FireplaceLeft Side Fireplace SpecificationsConsult all local codes FrontFraming Specifications Attic Above Firestop Spacer Installing the Chimney System8d nails when completely installed Chimney 30 Offset Through Floor Or Ceiling12 to 12/12 Roof Pitch Model Flat to 6/12Using a FTF13-CT1 Chase Termination Using a FTF13-CT2 Chase TerminationTEN Foot Rule Summary Multiple Terminations Special Offset InstructionsOffset Calculations FTF13 Vertical Elevation Chart HeightChimney Only Installing Offsets FTF13 Offset Elevation ChartOffset Elbow Assembly Return Elbow AssemblyCombustion Air Kits Optional Equipment Considerations Cold Climate InsulationFireplace Finishes Methods of Determining Hearth Extension Equivalents Hearth Extensions and Wall ShieldsInstallation Components Finish to Your TasteSum of all R values is 70 + .10 + .068 + .5825 = Round Termination 63L44 Page West Taft Avenue Orange, CA 850,006M REV. C 04/2004

EST-48 specifications

Lucent Technologies EST-48 is a cutting-edge telecommunications platform designed to enhance voice and data connectivity for enterprises and service providers alike. As a versatile solution, the EST-48 combines robust functionalities with advanced technology to meet the growing demands of modern communication infrastructures.

One of the main features of the EST-48 is its seamless integration capabilities. It allows organizations to unify their voice, video, and data services over a single network, thereby simplifying management and reducing operational costs. This integration is crucial for businesses looking to streamline their communication systems and improve collaboration among employees.

The EST-48 utilizes a modular architecture, providing flexibility and scalability to accommodate varying organizational needs. This modularity enables businesses to start with a basic configuration and expand their systems as they grow, adding new capabilities and services without significant disruptions. This characteristic is particularly beneficial for rapidly evolving enterprises.

In terms of technology, the EST-48 is equipped with advanced switching and routing capabilities, ensuring efficient data transmission and reduced latency. Its support for Voice over Internet Protocol (VoIP) technology allows for high-quality voice communications over the internet, significantly improving the clarity and reliability of calls. Additionally, the platform supports a variety of communication standards, making it compatible with existing infrastructure and third-party equipment.

Another significant characteristic of the EST-48 is its emphasis on security. The platform incorporates various security measures to protect sensitive data and prevent unauthorized access. This includes features such as encryption, secure access controls, and regular software updates to safeguard against potential vulnerabilities.

Moreover, the EST-48 comes with robust management tools that provide real-time monitoring and reporting capabilities. These tools enable administrators to track system performance, identify issues, and optimize the network for better efficiency.

In conclusion, Lucent Technologies EST-48 stands out as a versatile communications platform that combines advanced technology with user-friendly features. Its integration capabilities, modular design, emphasis on security, and management tools make it an ideal choice for organizations seeking to improve their communication systems in a cost-effective manner. As communication technology continues to evolve, platforms like the EST-48 will remain essential in meeting the needs of modern enterprises and service providers.