Regency F2402M manual Combustible Wall Chimney Connector PASS-THROUGHS

Page 12

INSTALLATION

COMBUSTIBLE WALL CHIMNEY

CONNECTOR PASS-THROUGHS

Minimum chimney clearance to brick and combustibles 2 in. (50.8mm)

Method A: 12" (304.8 mm) Clearance to Combustible Wall Member:

Using a minimum thickness 3.5" (89 mm) brick and a 5/8" (15.9 mm) minimum wall thickness clay liner, construct a wall pass-through. The clay liner must conform to ASTM C315 (Standard Specifi cation for Clay Fire Linings) or its equivalent. Keep a minimum of 12" (304.8

mm)of brick masonry between the clay liner and wall combustibles. The clay liner shall run from the brick masonry outer surface to the inner surface of the chimney fl ue liner but not past the inner surface. Firmly grout or cement the clay liner in place to the chimney fl ue liner.

Method B: 9" (228.6 mm) Clearance to Combustible Wall Member:

Using a 6" (152.4 mm) inside diameter, listed, factory-built Solid-Pak chimney section with insulation of 1" (25.4 mm) or more, build a wall pass-through with a minimum 9" (228.6 mm) air space between the outer wall of the chimney length and wall combustibles. Use sheet metal supports fastened securely to wall surfaces on all sides, to maintain the 9" (228.6 mm) air space. When fastening supports to chimney length, do not penetrate the chimney liner (the inside wall of the Solid-Pak chimney). The inner end of the Solid-Pak chimney section shall be fl ush with the inside of the masonry chimney fl ue, and sealed with a non-water soluble refractory cement. Use this cement to also seal to the brick masonry penetration.

Method C: 6" (152.4 mm) Clearance to Combustible Wall Member:

Starting with a minimum 24 gage (.024" [.61 mm]) 6" (152.4 mm) metal chimney connector, and a minimum 24 gage ventilated wall thimble which has two air channels of 1" (25.4 mm) each, construct a wall pass-through. There shall be a minimum 6" (152.4) mm separation area containing fiberglass insulation, from the outer surface of the wall thimble to wall combustibles. Support the wall thimble, and cover its opening with a 24-gage minimum sheet metal support. Maintain the 6" (152.4

mm)space. There should also be a support sized to fi t and hold the metal chimney connector. See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure the metal chimney connector do not penetrate chimney fl ue liner.

Method D: 2" (50.8 mm) Clearance to Combustible Wall Member:

Start with a solid-pak listed factory built chimney section at least 12" (304 mm) long, with insulation of 1" (25.4 mm) or more, and an inside diameter of 8" (2 inches [51 mm] larger than the 6" [152.4 mm] chimney connector). Use this as a pass-through for a minimum 24-gage single wall steel chimney connector. Keep solid-pak section concentric with and spaced 1" (25.4 mm) off the chimney connector by way of sheet metal support plates at both ends of chimney section. Cover opening with and support chimney section on both sides with 24 gage minimum sheet metal supports. See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure chimney fl ue liner.

Minimum

12 in. (304.8mm) to combustibles

Chimney Flue

Masonry chimney

Minimum clearance 12 in. (304.8mm) of brick

Chimney

connector

Fire clay liner

12

Regency Freestanding Woodstove

Image 12
Contents Please Keep These Instructions For Future Reference Model F2402MRegency Fireplace Product Modular PartsTable of Contents Safety Label Unit Dimensions Installation Residential InstallationModular Installation Options Residential Installation Clearances to Combustible Walls Minimum Clearance to Combustible MaterialsFloor Protector Minimum Alcove Clearance to Combustible Materials Floor Protection15 381 mm 165 mm 27 685 mm 13 330 mm 54 1371 mm 49 1244 mm 152 mm 45* 1143 mm 127 mm 45 1143 mm With Rear DeflectorStove Assembly Prior to Installation Rear Heat Deflector AssemblyAirmate Assembly Pedestal AssemblySTEP-BY-STEP Chimney Connector Installation Leg and Bottom Shield AssemblyMasonry Chimney Masonry FireplaceFactory Built Chimney Combustible Wall Chimney Connector PASS-THROUGHS Method a 12 304.8 mm Clearance to Combustible Wall MemberRecommended Heights for Woodstove Flue Recommended Flue HeightElevation Example a Example b Mobile Home Installation Listed Components For Mobile Home Installation InstallationCanadian Installations Flue BaffleBrick Installation STEP-BY-STEP Optional Accessories InstallationGlass Installation Door HandleBlower/Fan Operating Instructions Operating InstructionsDraft Control First FireSafety Guidelines Safety PrecautionsFAN Operation ASH DisposalMaintenance Parts List Stove Main AssemblyDescription Description 846-515PEDESTAL, Bottom Shield & LEG Options Firebrick Regency Freestanding Woodstove Regency Freestanding Woodstove Regency Freestanding Woodstove Warranty Warranty LifetimeDistributors Western Australia Eastern Australia