Regency P48-1 installation manual Horizontal Installations

Page 20

INSTALLATION

HORIZONTAL

INSTALLATIONS

Install the vent system according to the manu- facturer's instructions included with the com- ponents.

1)Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.

2)Direct Vent pipe and fittings are designed with special twist-lock connections to con- nect the venting system to the appliance flue outlet. A twist-lock appliance adaptor is an available option that must be used in conjunction with the Simpson Dura-Vent Direct Vent GS system. Install the adaptor after the unit is set in its desired location otherwise the unit will not fit through the 36-5/8" (930mm) high frame opening.

3)Put a bead of silicone inside the outer section of the adapter and a bead of Stove Mate on the inner collar. Slip the adapter over the existing inner and outer flue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.

4)Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.

They may be located by examining the inside of the female ends.

Note: Apply sealant "Mill-Pac" to inner pipe and high temp silicone seal- ant to outer pipe on every twist- lock joint.

b)Horizontal runs of vent must be sup- ported every 3 feet (0.9meter). Wall straps are available for this purpose.

5)Mark the wall for a 11" x 11" (279mm x 279mm) square hole. The center of the square hole should line up with the center- line of the horizontal pipe. Cut and frame the 11 inch (279mm) square hole in the exterior wall where the vent will be terminated.

If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, a 8" (203mm) diameter hole is acceptable.

Diagram 5

The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

7)Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble (Part # 1247) over the vent pipe.

8)Slide the appliance and vent assembly to- wards the wall carefully inserting the vent pipe into the vent cap assembly. It is impor- tant that the vent pipe extends into the vent cap sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches (32mm). Secure the connection between the vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 6.

Note:

a)Twist-lock procedure: Four indenta- tions, located on the female ends of pipes and fittings, are designed to slide straight onto the male ends of adjacent pipes and fittings, by orienting the four pipe indentations so they match and slide in to the four entry slots on the male ends. (Diagram 1) Push the pipe sections completely together, then twist-lock one section clockwise ap- proximately one-quarter turn, until the two sections are fully locked. The fe- male locking lugs will not be visible from the outside, on the Black Pipe or fittings.

Diagram 1

Diagram 2

Note:

a)The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fire.

b)The location of the horizontal vent ter- mination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Vent Terminal Locations, see diagram on page 11.

6)The arrow on the vent cap should be pointing up. Insure that the 1-1/4"(32mm) clearances to combustible materials are maintained (Diagram 5). Install the termina- tion cap.

Note: If installing termination on a siding covered wall, a vinyl siding stand- off or furring strips must be used to ensure that the termination is not recessed into the siding.

Diagram 6

9)Install wall thimble in the center of the 11" (279mm) square and attach with wood screws (Diagram 7).

Diagram 7

20

Regency P48-1 Zero Clearance Direct Vent Gas Fireplace

Image 20
Contents P48-1 Gas Fireplace Manufactured Mobile Home Requirements To the New OwnerTable of Contents Safety Label Copy of Safety Decal for P48-NG1 and P48-LP1Installation General Safety InformationInstallation Checklist Save These InstructionsUnit Specifications Locating Your GAS Stove Manufactured Mobile Home Additional RequirementsOptional Duct System Optional Heat ReleaseClearances MantelCeiling Max. Depth 36 914mmMantels Mantel LEG ClearancesFraming & Finishing Unit Assembly Prior to Installation Top Standoff AssemblyVenting Introduction Top Facing Support Side Nailing StripsExterior Vent Termination Venting Regency Direct Vent System Flex Horizontal Terminations OnlySimpson DURA-VENT Venting Simpson DURA-VENT Venting Components ListDescription Parts not supplied by Dura-VentVenting Arrangements Horizontal Terminations Regency Direct Vent System FlexHorizontal Venting with Two 2 90o Elbows Horizontal Venting with Three 3 90o ElbowsVertical Venting with Two 2 90o Elbows Min Max Min Max Min MaxVertical Venting with Three 3 90o Elbows Option + H1 V +Venting Arrangements Vertical Terminations Simpson DURA-VENT Direct Vent GS SystemInstallation Horizontal Installations Offset Chart Vertical TerminationInstallation Procedures For Regency Direct Vent System FlexGAS Line Installation Pilot AdjustmentGAS Pipe Pressure Testing High ElevationBrick Panels Installation Bottom ClipsLOG SET Installation 02-88 02-90 02-87 02-89 02-86 02-85 02-84 02-8302-88 02-83 02-86 02-85 02-89 02-84 02-87 02-88 02-8502-83 02-8902-90 02-8602-84Not under the gas line Standard Flush DoorFlush Louvers Optional Bay Trim Optional BAY DoorBAY Louvers Optional Finishing Trim Double Screen DoorOption Remote Control Thermostat Wire TableWiring Diagram Do not cut the ground terminal off under any circumstancesTo Remove the Fan Installing the Optional FANShut the power off Conversion Kit Contains Operating Instructions Normal Operating Sounds GAS Appliances Copy of the Lighting Plate InstructionsMaintenance Door Glass Installing ValveBay Glass Replacement Removing Valve Shut off the gas supplyParts List P48-1 Main Assembly102 100 P48-1 Burner & LOG Assembly P48-1 Flush Door & Louvers P48-1 BAY Front & Louvers Regency P48-1 Zero Clearance Direct Vent Gas Fireplace Regency P48-1 Zero Clearance Direct Vent Gas Fireplace Warranty ConditionsInstaller Please complete the following information

P48-1 specifications

The Regency P48-1 is a prominent model in the realm of modern communication technology, particularly recognized for its innovative features and robust performance. Originally launched as part of a series targeting both casual and professional users, the P48-1 stands out through its unique integration of advanced functionalities and user-friendly design.

One of the main features of the Regency P48-1 is its seamless connectivity capabilities. It supports various communication protocols, including Wi-Fi, Bluetooth, and cellular networks, allowing users to maintain reliable connections irrespective of their location. This versatility makes it an ideal choice for individuals who prioritize mobility without sacrificing functionality.

The device is equipped with a high-resolution display that enhances user experience, whether for browsing, video calls, or multimedia content consumption. The touch interface is responsive and intuitive, contributing to easy navigation through different applications and settings. The display’s vivid colors and sharp contrasts make it suitable for extended use, reducing eye strain during prolonged sessions.

At the heart of the Regency P48-1 is its state-of-the-art processing unit, which ensures fast and efficient performance. This technology allows for multitasking capabilities, enabling users to run multiple applications simultaneously without encountering lags. Coupled with significant internal storage and expandable memory options, the device caters to users who require ample space for their data, applications, and media files.

The P48-1 also incorporates advanced battery management technologies, providing extended usage time on a single charge. Users can enjoy the device's capabilities throughout the day without frequent interruptions for recharging. The battery's longevity, combined with fast-charging features, ensures that users remain connected and productive.

Security is a top priority in the design of the Regency P48-1. It includes biometric authentication methods such as fingerprint scanning and facial recognition, offering users peace of mind regarding their private information. Coupled with regular software updates, these features enhance the device's resilience against cybersecurity threats.

In conclusion, the Regency P48-1 embodies a blend of functionality, performance, and user-centric design. Its advanced communication features, high-resolution display, powerful processing capabilities, and robust security measures make it an exemplary device for a wide array of users, from professionals to tech enthusiasts. As technology continues to evolve, the P48-1 serves as a benchmark for what modern communication devices can achieve.