Weil-McLain 88 Make final adjustments, Adjust burner and damper assembly, Skim steam boilers

Page 33

Boiler manual: • Installation • Start-Up • Maintenance • Parts

Make final adjustments

Adjust burner and damper assembly:

1. Lock flue damper OPEN (Figure 49).

Make final burner adjustments using combustion test equipment to assure proper operation. Do not fire boiler without water. Sections will overheat, damaging boiler and resulting in severe property damage.

2.Refer to burner manual for start-up and service.

3.Let burner advance to high fire. Heat boiler to design conditions.

4.Using combustion test equipment, adjust burner for:

a.12% (± ¼%) CO2 for No. 2 fuel oil, 0 smoke.

b.9 – 10% CO2 natural gas; CO in flue gas not to exceed 50 ppm (0.01%).

c.Flue gas temperature no lower than 330°F.

On some applications, if draft conditions or burner char- acteristics cause the burner flame pattern to impinge on the combustion chamber wall, you may notice pinging sounds from the boiler. Adjust the burner if possible to redirect the flame. If this does not work, contact your boiler supplier or Weil-McLain to obtain an optional combustion chamber kit (see page 38 for contents).

5.Adjust flue collar damper (Figure 49) to ensure 0.1" W.C. positive pressure at test opening.

6.Tighten screws to secure in position.

7.Plug test opening with 1/8" plug provided with flue collar/damper assembly.

8.Adjust barometric draft control, when used, to design condi- tions.

9.Repeat steps 4 through 6. Adjust as required.

Skim steam boilers:

Clean all newly installed steam boilers to remove oil. Failure to properly clean can result in violent water level fluctuations, water passing into steam mains, or high maintenance costs on strainers, traps and vents. Skim boiler only. Do not clean old piping or leaks can occur.

Do not use petroleum-based cleaning or sealing com- pounds in boiler system. Severe damage to system components can result, causing substantial property damage.

1.Remove 2" plug from skim tapping tapping "A" (see Fig- ure 38, page 27).

2.Provide 2" skim piping from tapping to floor drain.

3.Raise waterline to midpoint of skim piping.

4.Fire burner to maintain temperature below steaming rate during skimming process.

5.Feed in water to maintain water level.

6.Cycle burner ON/OFF as needed to prevent rise in steam pres- sure.

7.Continue skimming until discharge is clear. This may take several hours.

Part No. 550-100-068/0308

Figure 49 Flue collar/damper assembly

8.Drain boiler.

9.While boiler is warm, but not hot, flush all inte- rior surfaces under full pressure until drain water runs clear.

10.Remove skim piping.

11.Re-insert plug at boiler skim tapping.

12.Close drain cock.

13.Fill with fresh water to normal water line.

14.Start burner and steam for 15 minutes to remove dissolved gases.

15.Stop burner.

16.Check traps and air vents for proper operation.

Check boiler for gas-tight seal:

Boiler must be sealed gas-tight to prevent possible flue gas leakage and carbon monoxide emissions, resulting in severe personal injury or death.

1. Remove boiler jacket side and top panels.

The boiler contains ceramic fiber and fiberglass materials. Use care when han- dling these materials per instructions on page 38 of this manual. Failure to comply could result in severe personal injury.

2.Start burner. Observe all sealing points and chalk mark any not gas-tight.

3.To seal all chalk-marked areas:

a.Use silicone sealant on section flueways.

b.Check gaskets and sealing rope placement.

4.Reinstall all jacket panels.

33

Image 33
Contents Boiler Manual Read before proceeding Hazard DefinitionsRead before proceeding Contents Installation must comply with Before installing boilerBefore selecting boiler location Provide clearance around boilerCombustion and ventilation air openings Required volume of interior spacesCombustion air openings to inside Combustion air openings to outsideCombustion air combination indoor and outdoor openings Engineered InstallationsLouvers, Grilles, and Screens Mechanical Combustion Air SupplyFor block assembly Set boiler in placeFor packaged boiler Prepare and position back section Assembling the blockIf using tankless heater TI sections Install intermediate sectionsBoiler model Section arrangementNumber Perform hydrostatic pressure test Prepare boiler and testSteam boiler Between 45 and 55 psig Complete block assembly Install burner mounting plate on front sectionInsert HXT-bars Install draft hood collar Install cleanout platesInstall piping Connect water boiler pipingGeneral water piping information By-pass circulator sizing Piping multiple boilersGeneral steam piping information Connect steam boiler pipingDrawing legend & notes Steam boiler piping guidelinesMinimum height of header above water line must be 24 inches Hartford loop piping for all steam boilersModel 1288 through 1888 steam 3 or 4 risers required Multiple Steam Boiler Piping Gravity Condensate Return Before installing jacket Install jacketInstall support brackets/channels Remove jacket parts from cartonsInstall jacket Install jacket side panels Install jacket front and back panelsInstall jacket top panels Install jacket trimJacket side panel placement Jacket top panel placement Pipe tankless heaters To pipe tankless heatersHot water can scald Install controls Install water boiler controlsSteam control locations Install steam boiler controlsSteam control siphon and fittings General venting information Connect breeching and venting systemsSelect type of venting system Construct metal breechingStub vent forced draft single boiler Install burner & wiring and fill system Install fuel piping Fuel oil pipingGas piping Adjust burner and damper assembly Make final adjustmentsFlue gas temperature no lower than 330F Skim steam boilersHandling ceramic fiber and fiberglass materials Removal of Front Plate or Cleanout Plate Materials=B=R RatingsDimensions inches Model DimensionsModel Supply & return tappings Burner lengths Dimension F 1788 1888Dimensions see lettered dimensions on opposite Description Part number PartsParts Weil-McLain Limited Warranties Warranty

88 specifications

The Weil-McLain 88 series is a commercial cast iron boiler recognized for its durability, efficiency, and versatile design, making it a preferred choice for various heating applications. Designed primarily for commercial and industrial use, the Weil-McLain 88 combines advanced technology with proven engineering principles to deliver reliable performance and long-lasting service.

One of the standout features of the Weil-McLain 88 is its cast iron construction. Cast iron is renowned for its ability to retain heat, resulting in lower fuel consumption and more consistent heating. This robust material ensures that the boiler can withstand high temperatures and pressures, making it suitable for heavy-duty applications. The sectional design of the boiler allows for easy installation and maintenance, enabling quick access to components and minimizing downtime.

In terms of efficiency, the Weil-McLain 88 is designed to achieve high thermal efficiency ratings. The boiler employs a flue gas recirculation system, which significantly reduces heat loss and maximizes energy utilization. Additionally, its low water content provides rapid heating response times, ensuring that spaces are heated promptly, even during peak demand periods.

Another noteworthy characteristic of the Weil-McLain 88 is its versatility. The boiler can be configured for a variety of applications, including hot water heating, hydronic heating systems, and steam heating. It is compatible with multiple fuel types, including natural gas, propane, and various oil options, allowing for flexibility in fuel choice based on availability and pricing.

The Weil-McLain 88 also incorporates advanced control technologies that enhance operational efficiency. The integrated electronic controls feature diagnostic capabilities to streamline troubleshooting and maintenance, ensuring optimal performance throughout the boiler’s lifespan. Moreover, the boiler's design is compatible with modern building management systems, allowing for seamless integration into existing heating setups.

Overall, the Weil-McLain 88 series stands out for its combination of quality construction, efficient operation, and adaptability to different heating needs. Whether for a commercial building, industrial facility, or institutional application, the Weil-McLain 88 provides a reliable and efficient heating solution that meets the demands of the modern world.