Weil-McLain CGA25SPDN manual 3d Piping low temperature systems, Temperature gauges

Page 20

GOLD CGa Gas-Fired Water Boiler — Boiler Manual

3d Piping — low temperature systems

Primary/secondary (preferred) Bypass piping method

0RIMARYSECONDARY bypass piping is preferred because the flow rate and temperature drop in the heating circuit(s) is determined only by the heating circuit circulator(s). So adjustment of the bypass valves in the boiler circuit will not cause a change in the heating circuit rate and temperature distribution.

Figures 13 and 14, page 21, show suggested bypass arrangements using PRIMARYSECONDARY bypass piping (preferred) for low temperature systems such as RADIANT HEATINGTSYSTEMS or CONVERTEDEGRAVITY SYSTEMS. For alternatives, see pages 22 through 25.

The bypass valves (items A and B) provide mixing of hot boiler outlet water with cooler system return water

set to assure a minimum return water temperature (at least 130°F) to the boiler. Set the valves as explained below.

Temperature gauges

'AUGEUA is suggested, but optional on any system.

'AUGEU B is optional on converted gravity systems, but REQUIRED on radiant heating systems — to display

the water temperature being supplied to the radiant tubing.

'AUGEU is REQUIRED on all systems to assure the return water temperature is accurately set for a minimum of 130°F. If this gauge is not available however, adjust the valves such that the boiler-mounted temperature/pres- sure gauge reads at least 150°F when the system return water is cold (approximately 60°F water temperature).

Valve adjustment (Figures 13 and 14 only)

1.Set the valves while the system is cool, setting for the coldest expected water temperature (usually 60°F since the system will often drop to room tempera- ture between cycles).

2.Start with valve A fully closed and B fully open.

 'RADUALLYUOPEN VALVELA while closing valve B until the temperature at gauge  reads 130°F when gauge A reads 60°F.

 .OTE THAT VALVELA regulates the amount of hot wa- ter from the boiler supply which mixes with return WATER 6ALVELB regulates the amount of system water flowing through the boiler secondary loop.

Failure to PREVENT LOWWRETURN WATERTTEMPERATURE to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.

Radiant heating system piping should include a means of REGULATING THEHBOILER RETURN WATERTTEMPERATURE and the SYSTEM SUPPLYYTEMPERATURE (such as provided by an INJEC

TION PUMPING CONTROL).

"OILER RETURN WATERTTEMPERATUREAWILL BE ADEQUATELY CONTROLLEDEUSINGITHEGMETHODSESHOWNE in this manual provided the SYSTEM SUPPLYYTEMPERATURE is RELATIVELYYCONSTANT

DO NOT apply the methods of this manual if the system is equipped with an OUTDOORD

RESETSCONTROL Instead, PROVIDE CONTROLSLAND PIPING which can REGULATE THE BOILERTRE

TURN WATERTTEMPERATURE at NO LESS THAN —& regardless of system supply temperature.

#ONTACTTYOUR 7EIL-C,AIN REPRESENTATIVECFORASUGGESTEDEPIPING ANDDCONTROLNMETHODS

Failure to PREVENT COLD RETURN WATERTTEMPERATURE to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.

20

Part Number 550-101-009/0107

Image 20
Contents Gold CGa How it works Other boiler componentsGold CGa Gas-Fired Water Boiler Contents User InstallerPlease read before proceeding 1a Prepare boiler location codes & checklist Installations must follow these codesBefore locating the boiler, check the following Ss .ATIONAL %LECTRICAL%#ODEResidential garage installations Minimum dimensions are v Length by1b Prepare boiler location clearances FoundationWhen removing boiler from an existing common vent system 1c Prepare boiler location vent systemChimney or vent require- ments Line chimney with corrosion-resistant metal1d Prepare boiler location air contamination Products to avoidTHEHBOILER #HECKETHEHBOILER Placementecompared 1e Prepare boiler location air openingsAir openings must be provided To a,Exhaust fans and air movers Motorized air dampersSingle air opening option Exception for large spaces2a Prepare boiler placement and setup Orifice replacement procedurePlace boiler/crate near position Inspect orifices and burners2b Prepare boiler pressure test Hydrostatic pressure testDrain and remove fittings Prepare boiler for testPrepare boiler draft hood & spill switch Prepare boiler install vent pipingDraft hood installation Spill switch installation2e Prepare boiler vent damper installation InstallationDamper blade Minimum clearances3a Water piping general information Closed-type expansion tank 3b Water piping single-zone systemDiaphragm-type or bladder- type expansion tank Figure 3c Water piping multiple zones Piping multiple zones3c Water piping multiple zones 3d Piping low temperature systems Temperature gaugesValve adjustment Figures 13 and 14 only Primary/secondary preferred Bypass piping methodONE Valve $RAINAVALVE LendetemperaturemgaugeOiler Isolation BALANCING Valves Valve adjustment BOILER-bypass piping method13 !IRISEPARATORRANDNAUTOMATICMVENT NIF Used .OTEOTHAT Theh SYSTEM-bypass piping method Gold CGa Gas-Fired Water Boiler Boiler Manual Gas piping Connect gas supply piping to boilerNatural Gas Propane GasField wiring Installation must comply withWiring connections Ational %LECTRICAL #ODE !.3.&0! LATESTA EDI- tionFreeze protection when used 6a Start-up preparationCheck for gas leaks Determine if water treatment is needed Verify water chemistryFill the system with water Inspect system water pipingInspect base insulation  #LOSEOZONE Isolation VALVESSs 6ERIFY the Boilerhand System are Full Oflwater 6b Start-up operate boilerEfore STARTINGSTHEABOILER NDO the FOLLOWING 6c Start-up if boiler doesn’t start Start the boilerCheck system and boiler Check for6d Start-up verify operation Check burner flamesCheck vent damper operation Check vent system operationCheck-out procedure checklist OO Utton Onospilloswitch PUSHEDLINOO !IRIPURGED FROMGSYSTEM  #ALCULATEUGASAINPUT8a Operation standing pilot boilers Main ignited until thermostat circuit or limit circuit8b Lighting instructions CGa-25 to CGa-8 8b Lighting instructions CGa-25 to CGa-8 9a Operation spark-ignited pilot boilers GAS mOWSSTO Pilot or Main GAS VALVE#ALL for HEATHthermostat circuit closes Damper is de-energized, and cycles to closed posiSchematic wiring diagram Spark-ignited pilot system 9a Operation spark-ignited pilot systemLadder wiring diagram Spark-ignited pilot system 9b Operating instructions CGa-25 to CGa-8 9b Operating instructions CGa-25 to CGa-6 9b Operating instructions CGa-25 to CGa-6 9b Operating instructions CGa-7 to CGa-8 Owner maintenance 10a Service and maintenance scheduleService technician 10b Service & maintenance annual start-up Repair.URNERSNANDRBASE Boiler heating surfacesOiled-bearing circulators Gas piping Cold fill and operating pressuresAir vents and air elimination Limit controls and cutoffsSafety relief valves should be Following installation, the valveReview with owner Boiler relief valve #ONTINUITY CHECKER 11a Troubleshooting procedureBefore troubleshooting Check the following Event of vent damper failureEffikal or Field Controls damper  ASAPRESSURES11b Troubleshooting standing pilot boilers Chart 1 Standing pilot Boiler will not fire11c Troubleshooting spark-pilot boilers Control indicator lights Lockout modesControl indicator lights NON-LOCKOUT modes Troubleshooting the control module11c Troubleshooting spark-pilot boilers Tstat Circ Usually indicates 48 VAC on thermostat circuit stray voltage Chart 4 Spark-ignited pilot Damper light flashing Chart 5 Spark-ignited pilot Flame & Power lights flashing Item 8 , Verify Sequence 12a Replacement parts Section assembly Base Jacket Trim Controls12b Replacement parts section assembly Part number12c Replacement parts base Igure R Base assembly, manifold, orifices and burners12d Replacement parts jacket Igure R Jacket assembly12e Replacement parts trim Igure R Trim assembly12f Replacement parts controls Igure R Gas control assembly13a Dimensions 13b Ratings DOEHandling ceramic fiber and fiberglass materials Jobosite CONDITIONS #URRENT ./3 RecommenREATHING H&RESHGAIR Ss 5SES E./3 .CERTIlED Dust Crespirator E. 

CGA25SPDN specifications

The Weil-McLain CGA25SPDN is a high-efficiency gas-fired boiler designed to deliver dependable heating performance while maintaining a strong focus on energy savings and user-friendly operation. Ideal for residential applications, this boiler is engineered to provide consistent warmth and comfort in homes with various heating demands.

One of the main features of the CGA25SPDN is its durable construction. Built with high-quality materials, this boiler is designed to withstand the rigors of frequent operation while maximizing longevity. It features an advanced cast iron heat exchanger that efficiently transfers heat to the water, resulting in lower energy costs and improved overall performance.

Efficiency is a key characteristic of the Weil-McLain CGA25SPDN. Its design promotes efficient combustion, allowing for a higher Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 82%, this boiler ensures that more of the fuel used is converted into usable heat, which translates to reduced energy bills for homeowners.

The boiler exhibits a user-friendly control system that allows for easy operation and maintenance. It comes equipped with an integrated vent damper that maximizes efficiency by reducing heat loss during standby periods. Additionally, the CGA25SPDN features an adjustable thermostat, enabling homeowners to customize their heating preferences easily.

Another significant feature of the CGA25SPDN is its versatility. The boiler is compatible with various heating applications, including hot water heating systems and home heating configurations. This adaptability makes it a great choice for both new installations and retrofitting existing systems.

Safety is always a concern with gas-fired appliances, and the Weil-McLain CGA25SPDN addresses this through its advanced safety mechanisms. The boiler incorporates safety controls that prevent overheating and ensure proper operation, providing peace of mind to homeowners.

In summary, the Weil-McLain CGA25SPDN stands out as a reliable and efficient heating solution for residential settings. With its durable construction, high-efficiency performance, user-friendly controls, and impressive safety features, it is an exceptional choice for those seeking a dependable gas-fired boiler that meets modern heating demands while keeping energy costs in check. Homeowners can trust the Weil-McLain CGA25SPDN for warmth and comfort through the cold months.