Weil-McLain CGA25SPDN Gas piping, Cold fill and operating pressures, Air vents and air elimination

Page 47

GOLD CGa Gas-Fired Water Boiler — Boiler Manual

10b Service & maintenance – annual start-up (cont.)

OCheck/test

Gas piping

1.Sniff near floor and around boiler area for any in- dication of a GASALEAK.

2.4ESTSGASAPIPING USINGIBUBBLE TEST per Section  of this manual, if there is any indication of a leak.

Cold fill and operating pressures

1.While the system is cold, note the PRESSURE READING

ON THEHBOILER PRESSURETEMPERATURE GAUGE 6ERIFY THAT cold fill pressure is correct.

2.7ATCHHTHEHPRESSURE as the boiler and system heat up to ensure pressure rise is normal. Too high a rise would indicate a waterlogged or undersized expan- sion tank.

Air vents and air elimination

1.Inspect automatic air vents (if used). Also inspect air separators to ensure they are operational.

2.The cap must be unscrewed one turn to allow air to escape.

3.See &IGURE . If the air vent is leaking, remove cap !!and briefly push valve ""and then release to clean the valve seat.

4.Replace cap !!by twisting all the way onto valve "" and then unscrewing one turn.

&IGURE R Automatic air vent, typical

Limit controls and cutoffs

 )NSPECTPANDNTEST THEHBOILER LIMITMCONTROL 6ERIFY OP-

eration by turning control set point below boiler

TEMPERATURE "OILER SHOULD CYCLECOFF 2ETURN DIAL TO original setting.

2.Inspect and test additional limit controls or low water cutoffs installed on system.

Expansion tank

1.Expansion tanks provide space for water to move in an out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed or diaphragm or bladder type. See Section  of this manual for suggested best location of expansion tanks and air eliminators.

/PENTYPE — located above highest radiator or

BASEBOARDBUNIT RUSUALLYNIN THE ATTIC ORACLOSET (ASNA gauge glass and overflow pipe to a drain.

#LOSEDTYPE — welded gas tight and located above boiler. Tank is partially filled with water, leaving an air cushion for expansion.

ss-AKE SURE THIS TYPE OF TANK IS lTTEDTWITH AATANK lTTING SUCH AS THEH""  '' Tank-Trolor Taco Taco-Trol. This fitting reduces gravity circula- tion of air-saturated tank water back to the system and prevents the air from bubbling up through the water as it returns from the sys- tem.

ss$O NOTOUSESAUTOMATICMAIRIVENTSNIN SYSTEMST WITH CLOSEDTYPE TANKS The air will escape from the system instead of returning to the tank. Eventually, the tank will waterlog and no longer control pressurization. The boiler relief valve will weep frequently.

$IAPHRAGMMOR BLADDERTYPE — welded gas tight with a rubber membrane to separate the tank pres- surizing air and the water. May be located at any point in the system, but most often found near the boiler.

s3YSTEMSTWITH THIS TYPE OF EXPANSIONNTANK REQUIRE at least one AUTOMATICMAIRIVENT, preferably lo- cated on top of an air eliminator, as shown in examples in manual Section .

2.If relief valve has tended to weep frequently, the ex- pansion tank may be waterlogged or undersized.

#LOSEDTYPED TANK — tank is most likely water- logged. Install a tank fitting if not already installed. Then check fill level per fitting manufacturer’s instructions. If fill level is correct, check tank size against manufacturer’s instructions. Replace with a larger tank if necessary.

$IAPHRAGMMOR BLADDERTYPE — first, check tank size to be sure it is large enough for the system. If size is too small, add additional tank(s) as neces- sary to provide sufficient expansion. If tank size is large enough, remove tank from system and check charge pressure (usually 12 psig for residential ap- plications). If tank won’t hold pressure, membrane has been damaged. Replace tank.

Part Number 550-101-009/0107

47

Image 47
Contents Gold CGa Other boiler components How it worksGold CGa Gas-Fired Water Boiler Contents User InstallerPlease read before proceeding Ss .ATIONAL %LECTRICAL%#ODE 1a Prepare boiler location codes & checklistInstallations must follow these codes Before locating the boiler, check the followingFoundation Residential garage installationsMinimum dimensions are v Length by 1b Prepare boiler location clearancesLine chimney with corrosion-resistant metal When removing boiler from an existing common vent system1c Prepare boiler location vent system Chimney or vent require- mentsProducts to avoid 1d Prepare boiler location air contaminationTo a, THEHBOILER #HECKETHEHBOILER Placementecompared1e Prepare boiler location air openings Air openings must be providedException for large spaces Exhaust fans and air moversMotorized air dampers Single air opening optionInspect orifices and burners 2a Prepare boiler placement and setupOrifice replacement procedure Place boiler/crate near positionPrepare boiler for test 2b Prepare boiler pressure testHydrostatic pressure test Drain and remove fittingsSpill switch installation Prepare boiler draft hood & spill switchPrepare boiler install vent piping Draft hood installationMinimum clearances 2e Prepare boiler vent damper installationInstallation Damper blade3a Water piping general information Closed-type expansion tank 3b Water piping single-zone systemDiaphragm-type or bladder- type expansion tank Figure Piping multiple zones 3c Water piping multiple zones3c Water piping multiple zones Primary/secondary preferred Bypass piping method 3d Piping low temperature systemsTemperature gauges Valve adjustment Figures 13 and 14 onlyONE Valve $RAINAVALVE LendetemperaturemgaugeOiler Isolation BALANCING Valves BOILER-bypass piping method Valve adjustment13 !IRISEPARATORRANDNAUTOMATICMVENT NIF Used .OTEOTHAT Theh SYSTEM-bypass piping method Gold CGa Gas-Fired Water Boiler Boiler Manual Propane Gas Gas pipingConnect gas supply piping to boiler Natural GasAtional %LECTRICAL #ODE !.3.&0! LATESTA EDI- tion Field wiringInstallation must comply with Wiring connectionsVerify water chemistry Freeze protection when used6a Start-up preparation Check for gas leaks Determine if water treatment is needed #LOSEOZONE Isolation VALVES Fill the system with waterInspect system water piping Inspect base insulationSs 6ERIFY the Boilerhand System are Full Oflwater 6b Start-up operate boilerEfore STARTINGSTHEABOILER NDO the FOLLOWING Check for 6c Start-up if boiler doesn’t startStart the boiler Check system and boilerCheck vent system operation 6d Start-up verify operationCheck burner flames Check vent damper operation #ALCULATEUGASAINPUT Check-out procedure checklistOO Utton Onospilloswitch PUSHEDLIN OO !IRIPURGED FROMGSYSTEMMain ignited until thermostat circuit or limit circuit 8a Operation standing pilot boilers8b Lighting instructions CGa-25 to CGa-8 8b Lighting instructions CGa-25 to CGa-8 Damper is de-energized, and cycles to closed posi 9a Operation spark-ignited pilot boilersGAS mOWSSTO Pilot or Main GAS VALVE #ALL for HEATHthermostat circuit closes9a Operation spark-ignited pilot system Schematic wiring diagram Spark-ignited pilot systemLadder wiring diagram Spark-ignited pilot system 9b Operating instructions CGa-25 to CGa-8 9b Operating instructions CGa-25 to CGa-6 9b Operating instructions CGa-25 to CGa-6 9b Operating instructions CGa-7 to CGa-8 Owner maintenance 10a Service and maintenance scheduleService technician 10b Service & maintenance annual start-up Repair.URNERSNANDRBASE Boiler heating surfacesOiled-bearing circulators Limit controls and cutoffs Gas pipingCold fill and operating pressures Air vents and air eliminationBoiler relief valve Safety relief valves should beFollowing installation, the valve Review with owner #ONTINUITY CHECKER 11a Troubleshooting procedureBefore troubleshooting  ASAPRESSURES Check the followingEvent of vent damper failure Effikal or Field Controls damperChart 1 Standing pilot Boiler will not fire 11b Troubleshooting standing pilot boilersTroubleshooting the control module 11c Troubleshooting spark-pilot boilersControl indicator lights Lockout modes Control indicator lights NON-LOCKOUT modes11c Troubleshooting spark-pilot boilers Tstat Circ Usually indicates 48 VAC on thermostat circuit stray voltage Chart 4 Spark-ignited pilot Damper light flashing Chart 5 Spark-ignited pilot Flame & Power lights flashing Item 8 , Verify Sequence Section assembly Base Jacket Trim Controls 12a Replacement partsPart number 12b Replacement parts section assemblyIgure R Base assembly, manifold, orifices and burners 12c Replacement parts baseIgure R Jacket assembly 12d Replacement parts jacketIgure R Trim assembly 12e Replacement parts trimIgure R Gas control assembly 12f Replacement parts controls13a Dimensions DOE 13b RatingsSs 5SES E./3 .CERTIlED Dust Crespirator E.  Handling ceramic fiber and fiberglass materialsJobosite CONDITIONS #URRENT ./3 Recommen REATHING H&RESHGAIR

CGA25SPDN specifications

The Weil-McLain CGA25SPDN is a high-efficiency gas-fired boiler designed to deliver dependable heating performance while maintaining a strong focus on energy savings and user-friendly operation. Ideal for residential applications, this boiler is engineered to provide consistent warmth and comfort in homes with various heating demands.

One of the main features of the CGA25SPDN is its durable construction. Built with high-quality materials, this boiler is designed to withstand the rigors of frequent operation while maximizing longevity. It features an advanced cast iron heat exchanger that efficiently transfers heat to the water, resulting in lower energy costs and improved overall performance.

Efficiency is a key characteristic of the Weil-McLain CGA25SPDN. Its design promotes efficient combustion, allowing for a higher Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 82%, this boiler ensures that more of the fuel used is converted into usable heat, which translates to reduced energy bills for homeowners.

The boiler exhibits a user-friendly control system that allows for easy operation and maintenance. It comes equipped with an integrated vent damper that maximizes efficiency by reducing heat loss during standby periods. Additionally, the CGA25SPDN features an adjustable thermostat, enabling homeowners to customize their heating preferences easily.

Another significant feature of the CGA25SPDN is its versatility. The boiler is compatible with various heating applications, including hot water heating systems and home heating configurations. This adaptability makes it a great choice for both new installations and retrofitting existing systems.

Safety is always a concern with gas-fired appliances, and the Weil-McLain CGA25SPDN addresses this through its advanced safety mechanisms. The boiler incorporates safety controls that prevent overheating and ensure proper operation, providing peace of mind to homeowners.

In summary, the Weil-McLain CGA25SPDN stands out as a reliable and efficient heating solution for residential settings. With its durable construction, high-efficiency performance, user-friendly controls, and impressive safety features, it is an exceptional choice for those seeking a dependable gas-fired boiler that meets modern heating demands while keeping energy costs in check. Homeowners can trust the Weil-McLain CGA25SPDN for warmth and comfort through the cold months.