Weil-McLain CGA25SPDN manual BOILER-bypass piping method, Valve adjustment

Page 22

GOLD CGa Gas-Fired Water Boiler — Boiler Manual

3d Piping — low temperature systems (continued)

BOILER-bypass piping method

This piping method (&IGURE  or , page 23) is called a BOILERBYPASS because part of the circulator flow is bypassed around the boiler (through valve A). This method reduces the flow rate throughout the boiler, in order to raise the average water temperature in the boiler ENOUGH TO PREVENTVmUEUGASACONDENSATIONS"OILERBYPASS

PIPING IS EFFECTIVECFOROSOME BOILERSL ˆINCLUDINGUTHEH#'A

provided the flow rates are adjusted according to the instructions following.

&IGURESU and  are alternative piping suggestions for CONVERTEDEGRAVITY (large water content or steam systems) or RADIANTIHEATINGTSYSTEM — for use when primary/secondary piping can’t be applied. (&IGURE , page 25, is another alternative, using system bypass in place of boiler-bypass piping. &IGURE  however, is not suitable for radiant heating applications because it does not protect the radiant system from possible high water temperature.)

"OILERBYPASSPIPING KEEPSESYSTEM mOWORATE AS HIGH AS possible and temperature drop as low as possible, help- ing to equalize the building heat distribution.

Temperature gauges

'AUGEU A is optional if the bypass valves will be ad- justed using cold (or room temperature) return water

to the boiler. (When setting the valves without gauge A installed — using cold or room temperature water

assume the return water temperature to be 60°F. Set the valves so gauge  reads at least 120°F.

'AUGEU B is optional on converted gravity systems, but REQUIRED on radiant heating systems — to display the water temperature being supplied to the radiant tubing.

'AUGEU  is REQUIRED on all systems to assure reliable adjustment of the bypass valves. The boiler-mounted temperature/pressure gauge can be used if a separate temperature gauge is not installed.

Valve adjustment

1. Start with valve A fully closed and B fully open.

 'RADUALLYU OPEN VALVEL A while closing valve B until the temperature at gauge  reads 60 °F higher than gauge A. A minimum 60°F temperature rise through the boiler assures a low enough flow rate and high enough average temperature to prevent condensation even with low system return water temperature.

 6ALVELA regulates the system flow rate, while valve B regulates the boiler flow rate.

4.The boiler-mounted temperature/pressure gauge may be used in place of a separate gauge .

Failure to PREVENT LOWWRETURN WATERTTEMPERATURE to the boiler could cause corrosion of the boiler sections or burners, resulting in severe personal injury, death or substantial property damage.

Radiant heating system piping should include a means of REGULATING THEHBOILER RETURN

WATERTTEMPERATURE and the SYSTEM SUPPLYYTEMPERATURE (such as provided by an INJEC

TION PUMPING CONTROL).

"OILER RETURN WATERTTEMPERATUREAWILL BE ADEQUATELY CONTROLLEDEUSINGITHEGMETHODSESHOWNE in this manual provided the SYSTEM SUPPLYYTEMPERATURE is RELATIVELYYCONSTANT

DO NOT apply the methods of this manual if the system is equipped with an OUTDOORD

RESETSCONTROL Instead, PROVIDE CONTROLSLAND PIPING which can REGULATE THE BOILERTRE

TURN WATERTTEMPERATURE at NO LESS THAN —& regardless of system supply temperature.

#ONTACTTYOUR 7EIL-C,AIN REPRESENTATIVECFORASUGGESTEDEPIPING ANDDCONTROLNMETHODS

Failure to PREVENT COLD RETURN WATERTTEMPERATURE to the boiler could cause corrosion damage to the sections or burners, resulting in possible severe personal injury, death or substantial property damage.

22

Part Number 550-101-009/0107

Image 22
Contents Gold CGa How it works Other boiler componentsGold CGa Gas-Fired Water Boiler Contents Please read before proceeding InstallerUser Before locating the boiler, check the following 1a Prepare boiler location codes & checklistInstallations must follow these codes Ss .ATIONAL %LECTRICAL%#ODE1b Prepare boiler location clearances Residential garage installationsMinimum dimensions are v Length by FoundationChimney or vent require- ments When removing boiler from an existing common vent system1c Prepare boiler location vent system Line chimney with corrosion-resistant metal1d Prepare boiler location air contamination Products to avoidAir openings must be provided THEHBOILER #HECKETHEHBOILER Placementecompared1e Prepare boiler location air openings To a,Single air opening option Exhaust fans and air moversMotorized air dampers Exception for large spacesPlace boiler/crate near position 2a Prepare boiler placement and setupOrifice replacement procedure Inspect orifices and burnersDrain and remove fittings 2b Prepare boiler pressure testHydrostatic pressure test Prepare boiler for testDraft hood installation Prepare boiler draft hood & spill switchPrepare boiler install vent piping Spill switch installationDamper blade 2e Prepare boiler vent damper installationInstallation Minimum clearances3a Water piping general information Diaphragm-type or bladder- type expansion tank Figure 3b Water piping single-zone systemClosed-type expansion tank 3c Water piping multiple zones Piping multiple zones3c Water piping multiple zones Valve adjustment Figures 13 and 14 only 3d Piping low temperature systemsTemperature gauges Primary/secondary preferred Bypass piping methodOiler Isolation BALANCING Valves LendetemperaturemgaugeONE Valve $RAINAVALVE Valve adjustment BOILER-bypass piping method13 !IRISEPARATORRANDNAUTOMATICMVENT NIF Used .OTEOTHAT Theh SYSTEM-bypass piping method Gold CGa Gas-Fired Water Boiler Boiler Manual Natural Gas Gas pipingConnect gas supply piping to boiler Propane GasWiring connections Field wiringInstallation must comply with Ational %LECTRICAL #ODE !.3.&0! LATESTA EDI- tionCheck for gas leaks Determine if water treatment is needed Freeze protection when used6a Start-up preparation Verify water chemistryInspect base insulation Fill the system with waterInspect system water piping  #LOSEOZONE Isolation VALVESEfore STARTINGSTHEABOILER NDO the FOLLOWING 6b Start-up operate boilerSs 6ERIFY the Boilerhand System are Full Oflwater Check system and boiler 6c Start-up if boiler doesn’t startStart the boiler Check forCheck vent damper operation 6d Start-up verify operationCheck burner flames Check vent system operationOO !IRIPURGED FROMGSYSTEM Check-out procedure checklistOO Utton Onospilloswitch PUSHEDLIN  #ALCULATEUGASAINPUT8a Operation standing pilot boilers Main ignited until thermostat circuit or limit circuit8b Lighting instructions CGa-25 to CGa-8 8b Lighting instructions CGa-25 to CGa-8 #ALL for HEATHthermostat circuit closes 9a Operation spark-ignited pilot boilersGAS mOWSSTO Pilot or Main GAS VALVE Damper is de-energized, and cycles to closed posiSchematic wiring diagram Spark-ignited pilot system 9a Operation spark-ignited pilot systemLadder wiring diagram Spark-ignited pilot system 9b Operating instructions CGa-25 to CGa-8 9b Operating instructions CGa-25 to CGa-6 9b Operating instructions CGa-25 to CGa-6 9b Operating instructions CGa-7 to CGa-8 Service technician 10a Service and maintenance scheduleOwner maintenance 10b Service & maintenance annual start-up Oiled-bearing circulators Boiler heating surfacesRepair.URNERSNANDRBASE Air vents and air elimination Gas pipingCold fill and operating pressures Limit controls and cutoffsReview with owner Safety relief valves should beFollowing installation, the valve Boiler relief valveBefore troubleshooting 11a Troubleshooting procedure #ONTINUITY CHECKER Effikal or Field Controls damper Check the followingEvent of vent damper failure  ASAPRESSURES11b Troubleshooting standing pilot boilers Chart 1 Standing pilot Boiler will not fireControl indicator lights NON-LOCKOUT modes 11c Troubleshooting spark-pilot boilersControl indicator lights Lockout modes Troubleshooting the control module11c Troubleshooting spark-pilot boilers Tstat Circ Usually indicates 48 VAC on thermostat circuit stray voltage Chart 4 Spark-ignited pilot Damper light flashing Chart 5 Spark-ignited pilot Flame & Power lights flashing Item 8 , Verify Sequence 12a Replacement parts Section assembly Base Jacket Trim Controls12b Replacement parts section assembly Part number12c Replacement parts base Igure R Base assembly, manifold, orifices and burners12d Replacement parts jacket Igure R Jacket assembly12e Replacement parts trim Igure R Trim assembly12f Replacement parts controls Igure R Gas control assembly13a Dimensions 13b Ratings DOEREATHING H&RESHGAIR Handling ceramic fiber and fiberglass materialsJobosite CONDITIONS #URRENT ./3 Recommen Ss 5SES E./3 .CERTIlED Dust Crespirator E. 

CGA25SPDN specifications

The Weil-McLain CGA25SPDN is a high-efficiency gas-fired boiler designed to deliver dependable heating performance while maintaining a strong focus on energy savings and user-friendly operation. Ideal for residential applications, this boiler is engineered to provide consistent warmth and comfort in homes with various heating demands.

One of the main features of the CGA25SPDN is its durable construction. Built with high-quality materials, this boiler is designed to withstand the rigors of frequent operation while maximizing longevity. It features an advanced cast iron heat exchanger that efficiently transfers heat to the water, resulting in lower energy costs and improved overall performance.

Efficiency is a key characteristic of the Weil-McLain CGA25SPDN. Its design promotes efficient combustion, allowing for a higher Annual Fuel Utilization Efficiency (AFUE) rating. With an AFUE rating of up to 82%, this boiler ensures that more of the fuel used is converted into usable heat, which translates to reduced energy bills for homeowners.

The boiler exhibits a user-friendly control system that allows for easy operation and maintenance. It comes equipped with an integrated vent damper that maximizes efficiency by reducing heat loss during standby periods. Additionally, the CGA25SPDN features an adjustable thermostat, enabling homeowners to customize their heating preferences easily.

Another significant feature of the CGA25SPDN is its versatility. The boiler is compatible with various heating applications, including hot water heating systems and home heating configurations. This adaptability makes it a great choice for both new installations and retrofitting existing systems.

Safety is always a concern with gas-fired appliances, and the Weil-McLain CGA25SPDN addresses this through its advanced safety mechanisms. The boiler incorporates safety controls that prevent overheating and ensure proper operation, providing peace of mind to homeowners.

In summary, the Weil-McLain CGA25SPDN stands out as a reliable and efficient heating solution for residential settings. With its durable construction, high-efficiency performance, user-friendly controls, and impressive safety features, it is an exceptional choice for those seeking a dependable gas-fired boiler that meets modern heating demands while keeping energy costs in check. Homeowners can trust the Weil-McLain CGA25SPDN for warmth and comfort through the cold months.