PB Heat ECT Series Burner Setup & Boiler Operation, Burner Installation, Check Boiler Controls

Page 16

BURNER SETUP & BOILER OPERATION

5. BURNER SETUP & BOILER OPERATION

Burn only #2 Fuel Oil in this

CAUTION appliance. Do not use gasoline, crankcase drainings or any oil containing gasoline.

A.BURNER INSTALLATION

1.The oil burner is supplied with a mounting flange fixed in position.

2.Mount the burner to the Burner Mounting Plate (item 3) with four (4) 5/16" studs and nuts provided.

Be sure hi temp gasket is between NOTICE the burner mounting flange and the

Burner Mounting Plate.

3.Care must be taken when routing the oil lines so not to interfere with the opening and closing of the burner mounting plate. Flexible oil lines or flared copper disconnects with valves (when copper lines are used) may be installed to assure full opening of the burner mounting plate when servicing.

Two-pipe oil supply for Riello burner NOTICE requires a separate kit. Order part

#C7001026 from Riello dealer.

4.Oil burner specifications:

For information pertinent to the oil burner such as nozzle sizing, fuel supply piping, adjusting or servicing, refer to the charts in this section and the burner installation manual.

B.BURNER START-UP AND ADJUSTMENT

CAUTION

Do not start the burner unless all

 

cleanout doors are in place.

1.Burner should start automatically when thermostat is turned up and main boiler service switch is turned on. If burner does not start, check to be sure there is oil in the tank and push reset button on burner control:

Beckett: Square red button. Carlin: Round red button.

Riello: Round red button inside clear flexible

cover on back of burner cover.

If burner still does not start, contact serviceman.

Do not attempt to start the burner CAUTION when excess oil has accumulated,

when the unit is full of vapor, or when the combustion chamber is very hot.

2.Adjust burner and barometric draft control for

highest CO² (Maximum 13% [EC-03 - EC-05] or

12-1/2% [EC-06]) while maintaining a 0 Smoke and -.01 to -.02" W.C. draft overfire.

All adjustments must be made using suitable instruments such as found in a Bacharach Combustion Test Kit.

3.Burner and boiler can be shut down by turning down the thermostat and moving the main boiler service switch to the "off" position.

4.See burner manufacturer's manual for further information regarding the burner.

C.CHECK BOILER CONTROLS

1.Limit and Operating Controls:

a.Lower the set point of each control until the burner shuts down. Note that the system pressure (or temperature) corresponds to the desired set point.

b.Return the controls to the desired set point.

2.Low Water Cut-off (if used) - consult the manufacturer's instructions for the low water cut-off operational check procedure.

D.PURGE AIR FROM THE SYSTEM (WATER BOILERS ONLY)

1.Purge the system using purge valves, isolating zones in the process or use system vents. Do not operate the pump(s) while purging. Pumps will hold air in the eye of the impeller.

2.Allow the system to reach 180°F and use manual vents, if installed, to remove any remaining air. Watch the pressure gauge as the system approaches 180°F. If the pressure exceeds the design operating pressure, check:

a.Fill valve pressure.

b.Expansion or compression tank operation and sizing.

14

Image 16
Contents Series EC/ECT Table of Contents Installation Clearance Using this ManualSpecial Attention Boxes Preinstallation ClearancesAIR for Combustion and Ventilation Never burn garbage or paperInstallation Survey Old New Comments InstallationChimney / Vent and Draft Control Planning the LayoutBoiler Placement and Assembly Setting the BoilerObservation Cover Assembly Knockdown Boilers Jacket AssemblyBoiler Exploded View See .1 in for parts identification Pressure Test Block Assembly Do not pipe boiler before jacket is Notice installedPiping and Controls Boiler Return ClearanceWater Boiler Piping Water Boiler PipingMaximum Tankless Water Heater Ratings Heater No Capacity Boiler SeriesControls Use only the Hydrolevel CG450 asElectrical Burner WiringGeneral Steam Boiler with Probe Low Water Cut-Off Water Boilers Zoning with Zone Valves Burner Setup & Boiler Operation Burner InstallationBurner START-UP and Adjustment Check Boiler ControlsClean the Boiler Steam Boilers only Cleaning the boiler requires the useModel No Air Band85 70 a DEL Model No Shutter Pressure Head Dim. a Air BandMaintenance Daily Maintenance with Boiler Operating Weekly Maintenance with Boiler OperatingMaintenance of Safety Relief Valve Monthly Maintenance with Boiler OperatingBurner mounting plate must be If a Long Shutdown is RequiredOpened to facilitate this operation Width Depth Height Boiler Dimensions & RatingsLocation Size NPT Water Steam Output5 InputNet I=B=R Ratings4 Water SteamRepair Parts EC/ECT-03 EC/ECT-04 EC/ECT-05 EC/ECT-06Page Page Series EC/ECT

ECT Series, EC Series specifications

The PB Heat EC Series and ECT Series represent a significant advancement in residential and commercial heating technology, providing reliable and efficient solutions for a variety of heating applications. These series are designed to meet the needs of homeowners and businesses seeking dependable heating while also prioritizing energy efficiency and comfort.

One of the standout features of the EC Series and ECT Series is their advanced engineering, which includes a range of high-efficiency boilers. These units utilize a cast iron heat exchanger that ensures excellent thermal transfer and durability. The cast iron construction is known for its longevity, enabling these boilers to withstand high temperatures and pressures, which is essential for long-term performance and reliability.

In terms of efficiency, both series feature energy-saving technologies that comply with the latest environmental standards. The EC Series, for example, boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating, indicating that a significant portion of the fuel consumed is converted into usable heat. This results in lower fuel bills and a reduced carbon footprint. The ECT Series further enhances efficiency with features like modulating burners that adjust the heat output based on demand, providing optimal comfort while minimizing energy waste.

Another notable characteristic of these series is their user-friendly controls and digital interfaces. The boilers come equipped with intuitive controls that allow homeowners to easily set and monitor their heating preferences. Many units also support advanced features, including Wi-Fi connectivity, enabling users to manage their heating systems remotely via smartphone applications.

In addition to their efficiency and user-friendly design, the PB Heat EC and ECT Series prioritize safety. These boilers incorporate multiple safety features, such as pressure relief valves and low water cut-off mechanisms, which help prevent operational hazards and ensure safe operation.

Overall, the PB Heat EC Series and ECT Series offer a robust combination of advanced heating technologies, efficiency, and safety. With their durable construction, energy-saving capabilities, and user-friendly controls, these heating solutions are ideal for those looking to invest in reliable and efficient heating systems. Whether for a residential property or a commercial facility, the EC and ECT Series stand out as exceptional choices in the modern heating landscape.