PB Heat EC Series Chimney / Vent and Draft Control, Installation Survey, Planning the Layout

Page 5

PREINSTALLATION

C. CHIMNEY / VENT AND DRAFT CONTROL

An oil-fired unit shall be connected CAUTION to a flue having sufficient draft at all

times, to assure safe proper operation of the unit.

1.Draft Requirement – Minimum draft required in the vent system is -.03" to -.05" W.C. depending on boiler model, see Table 7.1 (Section 7). This draft is necessary to provide the necessary draft over fire of -.01" to -.02" W.C. See discussion in paragraph 5 below regarding draft.

2.Use barometric provided to control draft. Follow manufacturer's instructions to locate and adjust the control.

3.Inspect the existing chimney or vent system. Make sure it is in good condition. Inspect chimney liner and repair or replace if necessary.

4.The vent system and installation must be in accordance with the current edition of the American National Standard ANSI/NFPA 211, "Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances," or applicable provisions of the local building codes. See Table 7.1 (Section 7) for typical chimney size. If the vent system is not sized properly, the burner may not operate properly. This can cause poor combustion, sooting and odors to occur.

5.Background Information Regarding Draft:

Modern boilers operate with higher efficiencies than older boilers. Smaller flueways, as well as bars, pins and fins are designed into modern boilers to transfer as much heat as possible from the hot gases to the water or steam and prevent heat loss up the chimney. However, these design features result in higher pressure, or draft loss, in the boiler.

This draft loss must be taken into account when installing an oil boiler into a new or old chimney. New chimneys are less likely to have poor draft.

However, they must have sufficient draft to support combustion. A -.06" draft is desirable and preferred. Older chimneys may require a replacement liner to have them perform well enough to support combustion.

For Example:

 

Old

New

Comments

 

Installation

Installation

 

 

 

 

 

 

 

 

 

No change, but older

Chimney

-.04"

-.04"

chimneys (especially unlined

Draft

ones) have leaks which

 

 

 

 

 

reduce draft.

 

 

 

 

Boiler

 

 

 

Design

+.01"

+.04"

Required for mandated

Pressure

efficiency increases.

 

 

Drop

 

 

 

 

 

 

 

 

 

 

The old installation would

 

 

 

have had a higher

Draft

-.03"

0.00"

temperature in the chimney

Over Fire

[as high as 800 degrees vs.

 

 

 

 

 

400 degrees F], which would

 

 

 

increase the draft.

 

 

 

 

The above readings are "cold" readings (before the boiler and chimney are heated up).

Note also that the higher the firing rate on a unit which has multiple firing rates, the higher the draft required. For example, increasing the firing rate 1/4 gallon may increase the draft loss in a unit by approximately +.01".

D.INSTALLATION SURVEY

For new and existing installations, a Water Installation Survey or a Steam Installation Survey is available from P.B. Heat, LLC. The surveys will provide information on how the boiler works with your specific system and will provide an overview of boiler system operation in general.

You can also use this survey to locate system problems which will have to be corrected. To obtain copies of these Surveys, contact your PB Heat representative or download it from PeerlessBoilers.com.

E.PLANNING THE LAYOUT

Prepare sketches and notes of the layout of the installation. Include boiler location, venting system, existing piping and wiring. Show existing equipment that may interfere with installation of new equipment.

3

Image 5
Contents Series EC/ECT Table of Contents Special Attention Boxes Using this ManualInstallation Clearance Clearances PreinstallationAIR for Combustion and Ventilation Never burn garbage or paperOld New Comments Installation Installation SurveyChimney / Vent and Draft Control Planning the LayoutSetting the Boiler Boiler Placement and AssemblyObservation Cover Assembly Knockdown Boilers Jacket AssemblyBoiler Exploded View See .1 in for parts identification Do not pipe boiler before jacket is Notice installed Pressure Test Block AssemblyPiping and Controls Boiler Return ClearanceWater Boiler Piping Water Boiler PipingHeater No Capacity Boiler Series Maximum Tankless Water Heater RatingsUse only the Hydrolevel CG450 as ControlsGeneral Burner WiringElectrical Steam Boiler with Probe Low Water Cut-Off Water Boilers Zoning with Zone Valves Burner Installation Burner Setup & Boiler OperationBurner START-UP and Adjustment Check Boiler ControlsCleaning the boiler requires the use Clean the Boiler Steam Boilers onlyAir Band Model No85 70 a DEL Model No Shutter Pressure Head Dim. a Air BandMaintenance Weekly Maintenance with Boiler Operating Daily Maintenance with Boiler OperatingMaintenance of Safety Relief Valve Monthly Maintenance with Boiler OperatingOpened to facilitate this operation If a Long Shutdown is RequiredBurner mounting plate must be Location Size NPT Water Steam Boiler Dimensions & RatingsWidth Depth Height Input Output5Net I=B=R Ratings4 Water SteamEC/ECT-03 EC/ECT-04 EC/ECT-05 EC/ECT-06 Repair PartsPage Page Series EC/ECT

ECT Series, EC Series specifications

The PB Heat EC Series and ECT Series represent a significant advancement in residential and commercial heating technology, providing reliable and efficient solutions for a variety of heating applications. These series are designed to meet the needs of homeowners and businesses seeking dependable heating while also prioritizing energy efficiency and comfort.

One of the standout features of the EC Series and ECT Series is their advanced engineering, which includes a range of high-efficiency boilers. These units utilize a cast iron heat exchanger that ensures excellent thermal transfer and durability. The cast iron construction is known for its longevity, enabling these boilers to withstand high temperatures and pressures, which is essential for long-term performance and reliability.

In terms of efficiency, both series feature energy-saving technologies that comply with the latest environmental standards. The EC Series, for example, boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating, indicating that a significant portion of the fuel consumed is converted into usable heat. This results in lower fuel bills and a reduced carbon footprint. The ECT Series further enhances efficiency with features like modulating burners that adjust the heat output based on demand, providing optimal comfort while minimizing energy waste.

Another notable characteristic of these series is their user-friendly controls and digital interfaces. The boilers come equipped with intuitive controls that allow homeowners to easily set and monitor their heating preferences. Many units also support advanced features, including Wi-Fi connectivity, enabling users to manage their heating systems remotely via smartphone applications.

In addition to their efficiency and user-friendly design, the PB Heat EC and ECT Series prioritize safety. These boilers incorporate multiple safety features, such as pressure relief valves and low water cut-off mechanisms, which help prevent operational hazards and ensure safe operation.

Overall, the PB Heat EC Series and ECT Series offer a robust combination of advanced heating technologies, efficiency, and safety. With their durable construction, energy-saving capabilities, and user-friendly controls, these heating solutions are ideal for those looking to invest in reliable and efficient heating systems. Whether for a residential property or a commercial facility, the EC and ECT Series stand out as exceptional choices in the modern heating landscape.