SCH1 Scale High: Select 100 to 9999 counts above SCL1. The total span between SCL1 and SCH1 must be within 11998 counts. Maximum setting range is -1999to +9999 counts. Minimum span is 100 counts. For Current and Voltage inputs, this will set the high range end. Viewable only for Thermocouple and RTD ranges.

SPL1 Set Point Low: Select from the lowest input range value to SPH1 value. This will set the minimum SP1 value that can be entered. The value for SP1 will not stop moving when this value is reached. Attempting to set a value for SP1 lower than SPL1 will result in a CHEC SP1 error. The value will not be accepted.

SPH1 Set Point High: Select from the highest input range value to SPL1 value. This will set the maximum SP1 value that can be entered. The value for SP1 will not stop moving when this value is reached. Attempting to set a value for SP1 higher than SPH1 will result in a CHEC SP1 error. The value will not be accepted.

S1St Set Point State: Select dir or rE.

dir Direct Action. As the input increases the output will increase. Most commonly used in cooling processes.

rE Reverse Action. As the input increases the output will decrease. Most commonly used in heating processes.

If Out1 is set for (following) appear.

##tP, #PUL, or ProP, then S1OL and S1OH If Out1 is set for ONOF, then skip to S1rE.

S1OL Set Point Output Low Limit: Select 0 to 90% but not greater than S1OH. This item limits the lowest output value. This is useful for adding a bias to the process when needed. Factory set to 0 for output codes 1,2, 3, and 8. Factory set to 20 for output code 5 (20% output equals 4 mA output).

S1OH Set Point Output High Limit: Select 10 to 100% but not less than S1OL for output codes 1, 2, 3, or 8. Select 10 to 102% but not less than S1OL for output code 5. This item allows setting the maximum output limit. This is useful with pro- cesses that are over powered. Adjustment to 102% allows setting current output to force a full on condition for output

Page 28 of 40

Image 30
Contents User’s Guide Servicing North America Omega Engineering Contents Model Identification Panel CollarGasket Page Wiring for Optional Inputs and Outputs Wiring for Z1 Input Page Password Table Security Level SelectionPage Programming SET Points for Alarm Functions Set Point 2 Tracking Operation of Self Tune FunctionProgram Setup and Operation Operation and Programming of OptionsFactory Default Procedure Menu Selections Primary Menu Secondary MenuEnd of Secondary Menu when Edit is set to Page Lrn1 Select YES or no Page Page Page Page Page Page End of Secure Menu when Edit is set to Secure MenuPage Page Page Page Page Page Page Page Page Specifications Depth Behind Mounting Surface 111.6 mm Diagnostic Error Messages Page Page FR# Page Shop online at omega.com