The following Menu Items operate on the entire Instrument. There is no Set Point distinction. These items will appear in both the Edit1, Edit2, and Edit3 menus.

SP1o Set Point 1 Output Select: Select OutA or Outb.

OutA Set Point 1 is routed through Output A, Set Point 2 is routed through Output B.

Outb Set Point 1 is routed through Output B, Set Point 2 is routed through Output A.

COPY Copy Zone Parameters. Copies program parameters from one zone to the other.

none No copy function is performed. Factory default. 1to2 Copies all parameters from Zone 1 to Zone 2. 2to1 Copies all parameters from Zone 2 to Zone 1.

Addr (Option C 4, Serial Communications) Control Address: Select from 1 to 3FE. This number (hexadecimal, base 16) must match the address number used by the host computer. The value displayed is for Zone 1. The address for Zone 2 is the value for Zone 1 plus one (e.g. if Addr is set to 17, Zone 1 is assigned to address 17 and Zone 2 is assigned to address

18). Addresses 100, 200, and 300 are reserved for Factory use.

bAUd (Option C 4, Serial Communications) Communication Baud Rate: Select 300, 1200, 2400, 4800, 9600, or 19200. This number must match the baud rate used by the host computer.

nAt (Option C 4, Serial Communications) No Activity Timer: Set from OFF or 1 to 99 minutes.

1- 99 Maximum time between host computer accesses. If timer counts to 0, CHEC LorE will be displayed.

OFF No Activity Timer function is disabled.

Page 34 of 40

Image 36
Contents User’s Guide Servicing North America Omega Engineering Contents Model Identification Panel CollarGasket Page Wiring for Optional Inputs and Outputs Wiring for Z1 Input Page Password Table Security Level SelectionPage Programming SET Points for Alarm Functions Set Point 2 Tracking Operation of Self Tune FunctionProgram Setup and Operation Operation and Programming of OptionsFactory Default Procedure Menu Selections Primary Menu Secondary MenuEnd of Secondary Menu when Edit is set to Page Lrn1 Select YES or no Page Page Page Page Page Page End of Secure Menu when Edit is set to Secure MenuPage Page Page Page Page Page Page Page Page Specifications Depth Behind Mounting Surface 111.6 mm Diagnostic Error Messages Page Page FR# Page Shop online at omega.com