SCH2 Scale High: Select 100 to 9999 counts above SCL2. The total span between SCL2 and SCH2 must be within 11998 counts. Maximum setting range is
SPL2 Set Point Low: Select from the lowest input range value to SPH1 value. This will set the minimum SP2 value that can be entered. The value for SP2 will not stop moving when this value is reached. Attempting to set a value for SP2 lower than SPL2 will result in a CHEC SP2 error. The value will not be accepted.
SPH2 Set Point High: Select from the highest input range value to SPL2 value. This will set the maximum SP2 value that can be entered. The value for SP2 will not stop moving when this value is reached. Attempting to set a value for SP2 higher than SPH2 will result in a CHEC SP2 error. The value will not be accepted.
S2St Set Point State: Select dir or rE.
dir Direct Action. As the input increases the output will increase. Most commonly used in cooling processes.
rE Reverse Action. As the input increases the output will decrease. Most commonly used in heating processes.
If Out2 is set for ##tP, or #PUL, then S2OH and S2OH (following) appear. If Out2 is set for ONOF, then skip to S2rE.
S2OL Set Point Output Low Limit: Select 0 to 90% but not greater than S2OH. This item limits the lowest output value. This is useful for adding a bias to the process when needed. Factory set to 0 for output codes 1,2, 3, and 8. Factory set to 20 for output code 5 (20% output equals 4 mA output).
S2OH Set Point 1 Output High Limit: Select 10 to 100% but not less than S2OL for output codes 1, 2, 3, or 8. Select 10 to 102% but not less than S2OL for output code 5. This item allows setting the maximum output limit. This is useful with pro- cesses that are over powered. Adjustment to 102% allows setting current output to force a full on condition for output
Page 32 of 40