devices which do not have bias adjustments. Factory set to 100 for all output codes.

If Out2 is set for ##tP, #PUL, or ProP,then skip to S2LP.

S2rE Set Point Reset. Select OnOF or Hold.

OnOF Control will automatically reset when process passes back through SP2d.

HoLd Manual Reset. Reset (acknowledge) by simulta- neously pressing the INDEX & DOWN ARROW keys for 5 seconds.

S2Pi Set Point Power Interrupt. Select On or OFF.

On Alarm Power Interrupt is On. Control will automati- cally reset on power-up if no alarm condition exists.

OFF Alarm Power Interrupt is OFF. Control will power- up in alarm condition regardless of condition of process.

S2iH Set Point Inhibit: Select On or OFF.

On Alarm Inhibit is On. Alarm action is suspended until the process value first enters a non-alarm condi- tion.

OFF Alarm Inhibit is OFF.

S2LP Set Point Lamp: Select O on or OoFF.

O on Lamp ON when Output is ON.

OoFF Lamp OFF when Output is ON.

S2t Set Point 2 type: Select Abs or dE.

AbS Absolute SP2. SP2 is independent of SP1, and may be set anywhere between the limits of SPL2 and SPH2.

dE Deviation SP2. SP2 is set as a deviation from SP1, and allows SP2 to retain its relationship with SP1 when SP1 is changed.

Note: The SPL2 and SPH2 settings must be set to correspond with the SPL1 and SPH1 settings. If not, a CHEC SP2 error may be generated by a change of SP1.

Page 33 of 40

Image 35
Contents User’s Guide Servicing North America Omega Engineering Contents Model Identification Panel CollarGasket Page Wiring for Optional Inputs and Outputs Wiring for Z1 Input Page Security Level Selection Password TablePage Programming SET Points for Alarm Functions Operation of Self Tune Function Set Point 2 TrackingOperation and Programming of Options Program Setup and OperationFactory Default Procedure Secondary Menu Menu Selections Primary MenuEnd of Secondary Menu when Edit is set to Page Lrn1 Select YES or no Page Page Page Page Page Page Secure Menu End of Secure Menu when Edit is set toPage Page Page Page Page Page Page Page Page Specifications Depth Behind Mounting Surface 111.6 mm Diagnostic Error Messages Page Page FR# Page Shop online at omega.com