Steam-distribution pipe fitted on suction side:
Pressure- compensation
Stench trap
Type: Sperrfix 3
Fig. 3.21
Because of the
An alternative method of bleeding off the condensate can be seen in the diagram.
3.5 Fitting the blowers
For the humidifier to work best, correct steam distribution is essential. For this reason, the minimum distances must be observed when installing the equipment.
Please note that only wall installation is possible with the econoVap.
Minimum distances for steam blowers 4-23 kg/h
A |
B |
Fig. 3.22
Type | A | B |
| min. | min. |
4 kg | 600 mm | 3 m |
|
|
|
8 kg | 900 mm | 5 m |
|
|
|
15 kg | 1000 mm | 7 m |
|
|
|
23 kg | 1000 mm | 10 m |
|
|
|
Minimum distances for steam blowers 32-65 kg/h
Typ 32: min. 1500 mm
Typ 45: min. 2000 mm
min.
15 m
Fig. 3.22
450 mm |
450 |
Fig. 3.22