Technical specifications steam blowers:

Max. steam

Air volume

Power

Nominal

Weight

Steam pipe

Condensate

Noise

output

m3/h

supply

rating

kg

 

pipe

level (1m)

 

 

 

 

 

 

 

 

4–8 kg/h

110

200/240 V

25 W

5

Ø 22 mm

Ø 8 mm

46 dB (A)

 

 

 

 

 

 

 

 

15–23 kg/h

650

50/60 Hz

170 W

15

Ø 35 mm

Ø 8 mm

54 dB (A)

 

 

 

 

 

 

 

 

32 kg/h

800

220/240 V

110 W

8

Ø 35 mm

Ø 8 mm

72 dB (A)

 

 

 

 

 

 

 

 

45–65 kg/h

800

50/60 Hz

110 W

8

2 x Ø 35 mm

Ø 8 mm

72 dB (A)

 

 

 

 

 

 

 

 

3.6 Laying the steam hose

The steam hose should be kept as short as possible. It should not be possible to block or obstruct the steam supply lines in any way. Furthermore, they must be protected from outside interference (e.g. deformities, kinking etc.). After the hose has been laid, it is advisable to re-check everything when the hose is warm.

It is equally important to avoid condensation pockets in the hose. Any curves should have as large a radius as possible.

Installation Material

If a hose is used for the steam line it must be the original one supplied by NORDMANN.

!If other hoses are utilised, NORDMANN cannot be held responsible for any damage that may occur.

°

0

2

.

n

i

m

300

Fig. 3.25

A hose clamp should be used to link the hose to the steam-distri- bution pipe.

When laying the steam hose in pipes, cable ducts etc., their resi- stance to high temperature (min. 100 °C) must be ensured. All insulation material must also be checked for its resistance to high temperature.

If the steam line installed is of copper, small radii should be avoi- ded wherever possible. Every bend causes an additional resi- stance. A steam line of copper must have the same diameter as the hose.

If the steam lines are long, with a lot of bends and a relatively high internal duct pressure, water may be continuously forced out of the steam cylinder, which impairs the performance.

Possible installation

Wrong installation

5%

300

Fig. 3.26

Fig. 3.27

Possible installation

300

Fig. 3.28

9

Image 9
Contents Nordmann econoVap Introduction List of contentsHow the humidifier works Safety InstructionsDimensions InstallationDimensions of the units Positioning HumidifierSteam Nozzle Dimensions of the steam distribution pipesDimensions of the steam blowers 4-23 kg/h Fitting the humidifier General guidelines for the installationFitting the steam-distribution pipe Various fitting methodsSteam-distribution pipe fitted on suction side Fitting the blowersMinimum distances for steam blowers 4-23 kg/h Minimum distances for steam blowers 32-65 kg/hInstallation Material Technical specifications steam blowersPossible installation Laying the steam hoseWater quality Water connectionsWater intake and drainage Safety instructionsElectrical connections Control voltagePutting the humidifier into operation Setting the output limitationStart-up LED DisplaySafety functions System- and servicing indicationsRemote indication Rectifying faults MaintenanceRegular checks Replacing the steam cylinderOptions Taking the humidifier out of operationProportional adaptor SC-System4564 Technical specifications