Nordmende 2401935EN0801 System- and servicing indications, Remote indication, Safety functions

Page 13

6.4 System- and servicing indications

LED shining “green” continuously

Operation

Humidification is demanded. The humidifier operates automatically. Without demand of humidity the LED remains dark.

red flash in the shining “green” Niveau max. attained

Occurs when the Niveau max. sensor is activated. This causes a momentary closure of the inlet valve.

LED blinking “red-green-red-green”

Manual drainage open

Manual drainage is activated, the drainage-button has been pressed.

LED blinking “green”

Cylinder service “U1”

The steam cylinder can no longer attain the nominal output and needs to be cleaned or perhaps replaced (refer to chapter 7.3). This is purely a servicing code, the unit does not switch off automatically. The humidifier continues to function at a reduced output.

LED shining “red” continuously

Excess current “U2”

Whenever there is excess current (140 % of nominal value) the humidifier switches itself off for safety reasons. After the fault has been rectified, the humidifier is put back into operation by pressing the main power switch.

LED blinking “red”

Continuous fill “U3”

The humidifier tries to fill the cylinder continuously. Either a heating phase or the water is missing. The humidifier switches itself off automatically after 30 minutes. After the fault has been rectified, the unit is put back into operation by pressing the main power switch.

LED blinking “red-red-green-green”

Microcontroller uncoded “U4”

This signal appears if a replacement electronic control unit has been fitted to the humidifier without being coded. The humidifier is prevented from operating. The signal disappears as soon as the controls unit has been coded.

6.6 Remote indication

A standard, potential-free relay output enables the alarm messages to be remotely displayed.

6.7 Safety functions

NORDMANN humidifiers are protected against running dry, i.e. the power is cut off automatically as soon as the electrodes in the steam cylinder protrude above the water level.

If current consumption becomes excessive (25 % above the nominal level), the outlet valve is opened automatically. Because the electrodes are then in contact with less water, current consumption falls back to the nominal value.

If the current fails to fall below 140 % of the nominal level even after several drainage operations, the humidifier turns itself off automatically and the failure message “U2” (continuously red) appears on the LED display.

13

Image 13
Contents Nordmann econoVap Introduction List of contentsHow the humidifier works Safety InstructionsDimensions InstallationDimensions of the units Positioning HumidifierSteam Nozzle Dimensions of the steam distribution pipesDimensions of the steam blowers 4-23 kg/h Fitting the humidifier General guidelines for the installationFitting the steam-distribution pipe Various fitting methodsSteam-distribution pipe fitted on suction side Fitting the blowersMinimum distances for steam blowers 4-23 kg/h Minimum distances for steam blowers 32-65 kg/hInstallation Material Technical specifications steam blowersPossible installation Laying the steam hoseWater quality Water connectionsWater intake and drainage Safety instructionsElectrical connections Control voltagePutting the humidifier into operation Setting the output limitationStart-up LED DisplaySystem- and servicing indications Safety functionsRemote indication Rectifying faults MaintenanceRegular checks Replacing the steam cylinderOptions Taking the humidifier out of operationProportional adaptor SC-System4564 Technical specifications