Hisense Group KFR-3208GW instruction manual Knob of the manifold valve must, Air purging

Page 25

Appendix: Installation

5.Air purging

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.

pressure in the system rises

operating current rises

cooling efficiency drops

moisture in the air may freeze and block capillary tubing

water may lead to corrosion of parts in the refrigerant system

Air Purging with a Vacuum Pump (for Test Run)

Indoor unit

Outdoor unit

Pressure

gauge

Lo

Hi

Manifold valve

(1)Check that each tube (both narrow and wide tubes between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.

(2)Using an adjustable wrench or box wrench, remove the valve caps from the service valve on both narrow and wide tubes.

(3)Connect a vacuum pump and a manifold valve (with pressure gauges) to the service port on the wide tube service valve.(Fig.A)

Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The ¡°Hi¡±

90 (1/4 turn)

Vacuum pump

Fig.A

Narrow tube

Hex wrench

Wide tube

knob of the manifold valve must

CAUTION always be kept closed.

(4)With the ¡°Lo¡±knob of the manifold valve open, run the vacuum pump. The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time for evacuation:

Table

Required time for evacuation when capacity

of 100 liter/h vacuum pump is used

If tubing length is less than 10 m

If tubing length is more than 10 m

10 min. or more

15 min. or more

NOTE

The required time in the above table is calculated based on the assumption that the ideal (or target) vacuum condition is around 10 mmHg abs.

(5) With the vacuum pump still running, close the Lo knob of the manifold valve. Then stop the vacuum pump.

(6)With the accessory hex wrench, turn the valve stem on the narrow tube service valve counterclockwise by 90 degrees (1/4 turn) for 10 seconds, and then turn the stem clockwise to close it again. (Fig.B)

Be sure to completely insert the hex wrench before attempting to turn the

valve.

CAUTION

23

Valve cap

Vacuum hose to manifold valve

Fig.B

(7)Leak test all joints at the tubing (both indoor and outdoors) with liquid soap. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.

(8)With the hex wrench, turn the wide tube service valve stem counter-clockwise to fully open the valve.

(9)Turn the narrow tube service valve stem counter-clockwise to fully open the valve.

(10)Loosen the vacuum hose connected to the wide tube service port slightly to release the pressure. Then, remove the hose.

(11)Replace the bonnet and flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 200kg-cm). This process is very important to prevent gas from leaking from the system.

(12)Test run the air conditioner.

(13)While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps.

(14)If there is no leakage, stop the air conditioner. (15)Wipe off the soap on the tubing.

This completes air purging with a vacuum pump and the air conditioner is ready for actual operation.

6.Please contact the technical service for further information.

Image 25
Contents Instruction Manual Installation Compact Size Alert Symbols ContentsPage Composition of the Air Conditioner Power lamp Hipower lampTimer lamp ON/OFF buttonSymbols Timer ON/OFF button HR. Timer button High Power buttonTransmitter Sleep buttonAutomatic switching between cooling and heating HR Timer buttonFlap button FAN Speed selectorOperation Guide HOW to Install BatteriesOperation with the Remote Control Unit Adjusting the Airflow Direction Adjusting the Fan SpeedHorizontal ¡ñNight Setback Mode High Power OperationSetting procedure Cancellation proceduresTimer on mode Example Using the 12-Hour on and OFF TimerTimer OFF mode Example Setting ProceduresCancellation procedure Using the 1-Hour OFF TimerSpecial Remarks Operation without the Remote Control Unit Care and CleaningCare and Cleaning Tips for Energy Saving TroubleshootingRefrigerant Flow Diagram Schematic DiagramSummery Appendix InstallationLocation Installation of the indoor unit Installation of the outdoor unit Air purging Knob of the manifold valve mustAir Purging with a Vacuum Pump for Test Run Packing List

KFR-3208GW specifications

Hisense Group, a key player in the global consumer electronics market, has made significant advancements in air conditioning technology with its model KFR-3208GW. Designed to meet the demands of both comfort and energy efficiency, this air conditioning unit stands out for its impressive blend of features and modern technologies.

One of the main features of the KFR-3208GW is its powerful cooling capability. With a cooling capacity of 3.2 kW, this unit can quickly lower indoor temperatures, making it ideal for residential and small commercial settings. The inverter technology integrated into the KFR-3208GW allows for precise temperature control while ensuring lower energy consumption, leading to substantial cost savings on electricity bills. This technology enables the compressor to adjust its speed according to the room temperature, thus maintaining a consistent climate without unnecessary energy spikes.

Another highlight of this air conditioning system is its Quiet Operation mode. The KFR-3208GW is designed to operate at low noise levels, making it suitable for bedrooms and other quiet environments. This is especially important for users who prefer a peaceful atmosphere for sleeping or working.

The air conditioning unit also features a multi-functional remote control, allowing users to effortlessly switch between the various modes such as cooling, heating, and dehumidification. The unit is equipped with a precise temperature sensor that ensures optimal performance and enhances user comfort.

Moreover, the KFR-3208GW is designed with advanced filtration systems that improve indoor air quality. The built-in filters are capable of capturing dust, allergens, and other airborne particles, contributing to a healthier living environment. This feature is particularly beneficial for individuals with respiratory issues or allergies.

In terms of installation, the KFR-3208GW offers flexibility, catering to different room layouts. Its compact design allows for easy wall mounting, making it an attractive option for space-constrained areas.

Overall, the Hisense Group KFR-3208GW air conditioning unit combines energy efficiency, cutting-edge technology, and user-friendly features, making it a desirable choice for those looking to enhance their indoor comfort while promoting a healthier atmosphere. As consumers continue to seek reliable and efficient cooling solutions, the KFR-3208GW is well positioned to meet these evolving needs.