5 Fault Finding
The following tables provide information on possible malfunctions during the operation of the solar cylinder as well as their cause and remedy.
NOTE: Only use original spare parts from
Malfunction | Cause | Remedy | |
Solar cylinder |
|
| |
The cylinder cools down at night. The | 1. The gravity brake is blocked. | 1. Check the position of the blue handle. | |
flow and return temperatures vary after |
| 2. Check the gravity brake for tightness | |
switching off the pump. The collector |
| (jammed cuttings, particles of dirt in the | |
temperature is higher than the air |
| sealing face). | |
temperature at night. |
| 3. Do not connect the solar heat | |
|
| exchanger directly, rather pull the supply | |
|
| pipes downwards and then upwards to | |
|
| the collector (syphon supports the gravity | |
|
| brake) or install a | |
|
| is switched on at the same time as the | |
|
| pump. | |
| 2. | Install a gravity brake (as close as | |
| short pipe networks with low pressure | possible to the cylinder). | |
| loss. |
| |
Reheating is not working. The boiler | 1. Air in the reheating heat exchanger. | Bleed the reheating heat exchanger. | |
runs for a short time, goes off and then | 2. Heat exchanger surface area too small. | Compare the specifications of the boiler | |
back on again. This is repeated until the | |||
| manufacturer with those of the cylinder | ||
cylinder is at its target temperature. |
| ||
| manufacturer. The problem may be able | ||
|
| ||
|
| to be solved by a higher setting of the | |
|
| flow temperature at the boiler. | |
Only cold or lukewarm water comes out | 1. Cold and hot water connections on the | Turn off the cold water supply, then | |
of the taps. | cylinder have been mixed up. | let water flow out via the hot water | |
|
| connection. Only a few litres of water | |
|
| flow out if the connection is laid correctly. | |
|
| The inlet of the hot water | |
|
| then rests in the air space; no further | |
|
| emptying is possible. If the entire solar | |
|
| cylinder runs empty via the hot water | |
|
| connection, the connections have been | |
|
| laid incorrectly. Change the connections! | |
| 2. Hot water thermostat mixer set too low. | Increase the setting. | |
| 3. Solar heating insufficient; boiler does | Check whether the boiler is working. | |
| not reheat. |
| |
| External control device faulty. | Check whether the external control | |
|
| device is working. | |
|
| Check whether the two port valve is in the | |
|
| hot water position. | |
|
| Replace the two port valve. | |
| Air in the reheating heat exchanger | Bleed the reheating heat exchanger. | |
| Cylinder temperature sensor defective. | Check the thermal cut out and reset it. | |
|
| Replace the cylinder thermostat. | |
|
| Table 5.1 Fault Finding |
20