American Power Conversion Central Air Conditioning System manual Set Up Module Control

Page 23

Set Up Module Control

The Module Control options are configured and tuned during the commissioning of each Module.

The settings in the Module Control menu are defined at the factory. Changing the settings incorrectly can cause serious malfunctions and damage to your System. Only qualified service personnel should make changes to these settings.

Calibrate airflow manually

The System must be on and the blowers operating to calibrate the airflow manually. If either condition does not exist, the display will prompt you to turn on the System and

Note blowers.

Nom Coil DP: Set the nominal coil differential pressure.

Blower Spd. Adjust the frequency of the blower.

Coil DP: Displays the coil differential pressure at the bottom of the screen. As the blower frequency is adjusted, the coil differential pressure will change. The Std Dry column in the table below gives the recommended coil differential pressure for each Precision Air Conditioner model.

 

 

Coil Differential Pressure Values

 

 

Model

Std Dry

Min

Max

Alarm Clear

Airflow Alarm

 

 

 

 

 

 

IR 40 CA

0.44

0.34

0.54

0.24

0.20

All values are displayed in inches water column ("WC)

Calibrate airflow automatically

Nom Coil DP: Set the nominal coil differential pressure.

Start/Abort. Start the automatic calibration. If calibration is in progress, this line displays Abort.

Coil DP: Displays the coil differential pressure at the bottom of the screen. As the blower frequency is adjusted, the coil differential pressure will change. When the Coil DP value matches the Nom Coil DP value, the System will display Calibration Complete. If the System cannot align the two values, the System will display Calibration Failed after two minutes. You must manually calibrate the airflow if automatic calibration fails.

NetworkAIR IR Operation, Maintenance, and Troubleshooting

17

Image 23
Contents NetworkAIR IR Precision Air Conditioner Page Contents Set Up Alarms Network Management Card Maintenance Display Interface OperationScrolling status screens Using the DisplayNavigating the interface Main menu screenStart the System Password entryChange settings Stop the System System Options Set Up System ConfigurationOperation Set Up System Configuration System Delays Building management Sensor setupOptions for Fluid-Cooled Modules Fluid-Coil Type Applicable SettingsActuator Types Valve TypesCoil Fluid Temp Activation Threshold and Deadband Input contacts Set Up Contacts and RelaysMap Description/Function Output relaysOperation Set Up Contacts and Relays Alarm detectors Set Up Module ConfigurationConfigure Module Calibrate airflow automatically Set Up Module ControlCalibrate airflow manually Set up Humidifier Reset variable frequency driveReset humidifier Reset compressors How the modes work Control the EnvironmentSetpoints Essential Functions DeadbandsModes PID controls Loop Behavior PID Tuning Correction How to tune the PIDsHumidification sensitivity Humidity alarms Set Up AlarmsTemperature alarms Coil fluid thresholds Alarm delayMaint intervals Group config Set Up GroupSys failure events Group settingsOperation Set Up Group Date and time Set Up the DisplayPassword & Time-out Temperature & pressure unitsHow to update the firmware Adjust displayProduct data Reset to defaultsNetwork config Set Up Network ConfigurationModule status View Status ReadingsSystem status View Log Group statusView Event Log Control beeper Respond to AlarmsMajor or minor alarm LEDs View active alarmsReset sys failure Clear active alarmsDisplayed Alarm Message Action Required Alarm messages and suggested actionsDisplayed Alarm Message Action Required Check that the # Systems setting Path Main Setup Group Group Module Module in which the alarm occurred Module Control Displayed Alarm Message Action Required Displayed Alarm Message Action Required Page Overview Quick ConfigurationBootp & Dhcp configuration TCP/IP configuration methodsAPC Device IP Configuration Wizard Network Management Card Quick Configuration Option 43 = 01 04 31 41 50 Local access to the control console Control console Remote access to the control consoleNetwork Management Card Quick Configuration Telnet/SSH How to Access a Configured UnitWeb interface Snmp FTP/SCP How to Recover From a Lost Password How to Upgrade Firmware Upgrade the AOS. For example Page Environment Monthly Preventive MaintenanceElectrical CleanlinessMechanical Record the amperages for the following components Quarterly Preventive MaintenanceFunctional tests Semi-Annual Preventive Maintenance Page Troubleshooting Troubleshooting Semi-Annual Preventive Maintenance Problem Possible Cause Corrective Action Page APC product covered Limited Product Warranty for APC ProductsTerms of warranty Exclusions Assignment of warrantiesDrawings, descriptions Limited Product Warranty for APC Products Labor Warranty ProceduresClaims Parts Page Page APC Worldwide Customer Support

Central Air Conditioning System specifications

American Power Conversion (APC) is renowned for delivering innovative solutions in the realm of power management, but its contributions don't stop there. The company has also made significant advancements in central air conditioning systems. Featuring cutting-edge technologies and energy-efficient designs, their HVAC systems are tailored to meet modern needs while ensuring comfort and sustainability.

One of the standout features of APC central air conditioning systems is their variable speed compressor technology. This advanced system operates at different speeds rather than just cycling on and off. By adjusting the compressor speed to match the cooling demand, these systems optimize energy consumption, leading to lower electricity bills and extended equipment lifespan.

APC's systems also incorporate smart thermostat capabilities, allowing homeowners to monitor and control their air conditioning remotely. Through a mobile app, users can adjust temperature settings, create schedules, and receive maintenance alerts, all of which enhance convenience and efficiency. Furthermore, these smart thermostats can learn user habits over time, automatically adjusting temperature settings to maximize comfort and savings.

Another key characteristic of APC central air conditioning systems is their commitment to eco-friendly refrigerants. Utilizing low global warming potential (GWP) refrigerants, these systems minimize the environmental impact while maintaining high-performance standards. With energy efficiency ratings that often exceed industry benchmarks, APC systems contribute to reduced greenhouse gas emissions and help homeowners adopt sustainable practices.

The design of APC air conditioning units is also noteworthy. They are constructed with durable materials that withstand various weather conditions, ensuring reliability during the hottest months. Additionally, the streamlined design of these systems enhances aesthetic appeal, making them a suitable choice for modern homes.

In conclusion, the American Power Conversion central air conditioning system exemplifies the synergy of innovative technology, energy efficiency, and user-friendly features. With variable speed compressors, smart controls, eco-friendly refrigerants, and robust construction, APC provides homeowners with a dependable and sustainable climate control solution. As demand for energy-efficient products continues to grow, APC is poised to lead the way in intelligent air conditioning solutions that prioritize both comfort and environmental responsibility.