Reliance Water Heaters HE50 76N Series 100, 317775-000 Installation of Vent SYSTEM, Sidewall

Page 24

INSTALLATION OF VENT SYSTEM, SIDEWALL

With the route of the venting system and selection of materials completed, as discussed in the section of this manual titled PLANNING THE VENT

SYSTEM, the through the wall vent terminal in place and the first section of piping, up to first elbow, installed at the blower it is time to complete the

installation of the venting system for the sidewall installation.

GRADE

SNORKEL

*MIN. 12” (30 cm)

ABOVE GRADE OR

*MIN. 12” (30 cm)

ABOVE

ANTICIPATED

SNOW LEVEL

INSTALL A SNORKEL AS SHOWN

HERE ONLY IF NECESSARY TO

ACHIEVE THE 12” MINIMUM

CLEARANCE ABOVE

THE HIGHEST ANTICIPATED

SNOW LEVEL.

FIGURE 20

It is recommended that the completion of the venting system start at the blower assembly and run to the coupling on the inside wall of the vent terminal, Figure18.

The vent system piping should be supported every 5 feet (1.5 m) of vertical run and every 3 feet (91 cm) of horizontal run. Follow vent pipe manufacturer’s instructions for proper joining procedures.

If necessary to achieve the 12” minimum clearance above the highest anticipated snow level, install a snorkel as shown in bottom portion of Figure 20.

NOTE: With the installation of a snorkel it is necessary to use two 90° elbows that shall be considered along with the

additional vent pipe when calculating maximum equivalent feet of venting.

INSTALLATION OF VERTICAL VENT SYSTEM

A proper flashing or “BOOT” should be used to seal the pipe

where it exits the roof. The total vent system should not exceed the equivalent feet of pipe as listed in Table 1.

Provide support for all pipe protruding through the roof. All piping should be properly secured. The vent system piping should be supported

every 5 feet (1.5 m) of vertical run and every 3 feet (91 cm) of horizontal run. Follow vent pipe manufacturer’s instructions for proper

joining procedures.

FIGURE 21

IMPORTANT

The vent system must terminate so that proper clearances are maintained as cited in local codes or the current edition

of the National Fuel Gas Code (ANSI Z223.1) or the Natural Gas and Propane Installation Code (CAN/CSA-B149.1) and as

listed below:

1.Vent Termination must extend a minimum of 12 inches (30 cm) above roof or 12 inches (30 cm) above the anticipated snow level to prevent blockage of the vent termination, as shown in Figures 20 and 21.

24

Image 24
Contents Power Vented GAS Models W/HOT Surface Ignition Whenever maintenance adjustment or service is requiredPrinted 317775-000Safe INSTALLATION, USE and Service ApprovalsImportant Definitions General Safety Information General Safety Information Table of Contents IntroductionInstallation of Carbon Monoxide Detectors Approved Carbon Monoxide DetectorsSignage ExemptionsTypical Installation Replacement Parts and Deliming ProductsElbow Access Door Condensate Hose and Drain PAN Mixing Valves ROUGH-IN-DIMENSIONS Rough-In-DimensionsCapacity and Gas and Electrical Characteristics Recovery capacity based on 90% thermal efficiencyLocating the NEW Water Heater Facts to Consider About the LocationInsulation Blankets Air REQUIREMENTsUnconfined Space Confined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through Two OpeningsOutdoor AIR Through TWO Horizontal Ducts Outdoor AIR Through TWO Vertical DuctsAIR from Other Indoor Spaces Installing the NEW Water Heater Chemical Vapor CorrosionWater Piping Space Heating and Potable Water SystemTemperature-Pressure Relief Valve Thermal ExpansionValve and Pipe Insulation if supplied High Altitude Installation Contact qualified installer or service agencyGas Piping Sediment Traps Filling the Water HeaterPer square inch 3.5 kPa Vent Pipe Assembly VentingTermination Clearances Sidewall Power Vent Vent Pipe TerminationPlanning the Vent System CondensateBreathing Hazard Carbon Monoxide Gas Blower Assembly Installation Installation of Vent SystemVent Terminal INSTALLATION, Sidewall Power Vent Wiring Schematic Figure Chisel an opening approximately one half inch 1.3 cm largerThan the marked circle Pointed in the correct position, see FigureInstallation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemVent Attenuation Assembly Installation Vent attenuation assembly Flexible tubing Instruction sheetVertical VAA Installations Recommended Inch vent Vertical VAA Installations Vent Pipe Preparation Recommended BRUSH* Size for Primer Cement ApplicationsStep B Step EStep F Step GPower Before Servicing Do not try to light the burner by handWhat to do if YOU Smell GAS Do not TRY to Light the Burner by HandTemperature Regulation Temperature Indicators Temperature Adjustment ButtonsDisplay D E FFor Your Information Start UP ConditionsOperational Conditions Periodic Maintenance Anode ROD InspectionTemperature-Pressure Relief Valve Test Keep hands clear of drainTo Flush the Water Heater Storage Tank Open the water heater drain valve to flush the storage tankService Leakage CheckpointsTroubleshooting Guidelines Trouble ShootingEnsure the flame sensor is clean use ultra fine steel Turn off power to the water heaterAssembly if damaged or defective Unplug ignitor assembly plug from control. Check resistanceUnplug the ignitor assembly plug from the control. Check Resistance of the black resistor wire between pinsAssembly .2 If the reading taken is less than 100,000 Check vent temperature limit switch if it is determinedTroubleshooting Guidelines Limited Warranty

317775-000, HE50 76N Series 100 specifications

The Reliance Water Heaters HE50 76N Series 100,317775-000 is a remarkable product tailored to meet the increasingly demanding needs of modern households. Known for its reliability and efficiency, this water heater stands out in both functionality and design, making it a preferred choice for many homeowners.

One of the primary features of the HE50 76N series is its impressive 50-gallon capacity, which provides ample hot water for various domestic tasks such as bathing, cooking, and cleaning. This generous size makes it suitable for medium to large families, ensuring that you can enjoy hot water when you need it most without any disruptions.

The heater is equipped with an Energy Factor (EF) rating that reflects its efficiency in converting energy into hot water. Designed for optimal energy savings, the HE50 76N series features advanced insulation that minimizes heat loss, thus reducing energy bills and promoting sustainability. The insulation also contributes to maintaining a consistent water temperature, ensuring comfort and convenience.

One of the standout technologies integrated into this model is the use of a powerful heating element, which rapidly heats the water. This system ensures quick recovery times, allowing for uninterrupted hot water supply even during peak usage. Additionally, the HE50 76N is equipped with a thermostat that enables users to easily adjust the temperature settings according to their preference, enhancing user control and safety.

Reliance has also prioritized durability and longevity in the design of the HE50 76N series. With a corrosion-resistant tank and protective coatings, this water heater is built to withstand the rigors of daily use and resist the elements that typically contribute to wear and tear. The anode rod included in the tank provides extra protection against rust and helps prolong the lifespan of the heater.

Another significant characteristic of the HE50 76N series is its user-friendly interface. With straightforward controls and clear indicators, it makes operation simple for all users. Furthermore, installation is hassle-free, with standard connections that allow for easy integration into existing setups.

In summary, the Reliance Water Heaters HE50 76N Series 100,317775-000 combines efficiency, capacity, technology, and user-friendliness, making it one of the most reliable options on the market. With its emphasis on energy savings and durability, this water heater is designed to support the modern household while providing peace of mind and comfort.