4.If 24 volts is present, remove the pilot burner and remove the pilot orifice from the pilot burner. The orifice is removed in the direction opposite the flow of gas. Inspect the orifice for obstruction. If it is clear, replace the main gas valve.

The ignitor sparks at the pilot burner but the pilot does not ignite and a gas odor is detected at the draft motor outlet.

1.Adjust the pilot adjust screw on the gas valve as described in “PILOT CHECKOUT” page 44.

2.Check the supply pressure as described in “POST START CHECK LIST” page 43. Make adjustments as necessary.

3.Check the pilot orifice for obstruction as described in paragraph above. Clean as needed but the prob- lem should not be the gas valve.

The pilot burner ignites but the ignitor continues to spark and the main burners do not ignite.

1.Make the same checks and adjustment as described in “PILOT CHECKOUT” page 44.

2.Check the supply pressure as described in “POST START CHECK LIST” page 43. Make adjustments as necessary.

3.Make sure that the pilot burner is not bent or dam- aged.

4.Make sure that the ground connections at the pilot burner, gas valve and ignitor control are intact. Check the high tension wire for good electrical con- nection. If all are intact, replace the ignitor module.

The pilot burner lights and the spark stops but the main burners do not light.

1.Check electrical connections between the ignitor control and the gas valve. If intact, check for 24 volts across terminals “MV” and “COMMON” termi- nals. If no voltage detected, replace ignitor control. If voltage is present, replace gas valve.

Furnace lights with roll-out or one burner has delayed ignition.

1.Make sure that the pilot burner is aligned properly with the carryover as described in “PILOT CHECK- OUT” page 44.

2.Make sure that the carryovers on adjoining burners are screwed fast and are level with respect to one another.

Main burners light but exhibit erratic flame characteris- tics.

1.Adjust air shutters as described in “BURNER AIR SHUTTER ADJUSTMENT” page 44.

2.Check the main burner orifices for obstruction and alignment. Removal procedure is described in BURNER INSTRUCTIONS page 44. Clean or replace burner orifices and burners as needed.

UNIT FLASH CODES

Various flash codes are utilized by the unit control board (UCB) to aid in troubleshooting. Flash codes are distinguished by the short on and off cycle used (approximately 200ms on and 200ms off). To show normal operation, the control board flashes a 1 second on, 1 second off "heartbeat" during normal operation. This is to verify that the UCB is functioning correctly. Do not confuse this with an error flash code. To prevent confusion, a 1-flash, flash code is not used.

Alarm condition codes are flashed on the UCB lower left Red LED, See Figure 24. While the alarm code is being flashed, it will also be shown by the other LEDs: lit continuously while the alarm is being flashed. The total of the continuously lit LEDs equates to the number of flashes, and is shown in the table. Pressing and releasing the LAST ERROR button on the UCB can check the alarm history. The UCB will cycle through the last five (5) alarms, most recent to oldest, separating each alarm flash code by approximately 2 seconds. In all cases, a flashing Green LED will be used to indicate non-alarm condition.

In some cases, it may be necessary to "zero" the ASCD for the compressors in order to perform trouble- shooting. To reset all ASCDs for one cycle, press and release the UCB TEST/ RESET button once.

Flash codes that do and do not represent alarms are listed in Table 24.

52

Johnson Controls Unitary Products

Image 52
Contents Installation Table of Contents List of Figures List of TablesSafety Considerations GeneralInspection ReferenceRenewal Parts ApprovalsProduct Nomenclature Ton Sunline & Magnum & MagnaDRY Model Number NomenclatureInstallation Safety Information InstallationLimitations Unit Application Data LocationRigging and Handling ClearancesDuctwork Fixed Outdoor AIR Intake DamperService Access FiltersField Wiring DM ELECTRIC/ELECTRIC and GAS/ Electric Units Power and Control Wiring Control Wire SizesThermostat Electric Heat Application Data Optional Electric HeatOptional GAS Heat GAS Heat Application DataGAS Piping Pipe SizingExternal Supply Connection External SHUT-OFF Vent and Combustion AIR Hoods Vent and Combustion AIR HoodOptional Power EXHAUST/BAROMETRIC Relief Damper Rain Hood Enthalpy Setpoint Adjustment Four and SIX Point Loads Physical Data ModelsDM Electrical Data -WITHOUT Powered Convenience Outlet SizeDM Electrical Data -WITH Powered Convenience Outlet Front View Rear View Dimensions Unit Clearances and Rain Hood Dimensions 15, 20 & 25 TON Altitude Correction Factors AIR Temp Altitude MeterALTITUDE/TEMPERATURE Conversion Factor High Static Drive CFM 80 m3/s 30 m3/s 10 m3/s 40 m3/s 1030 378 321 258 199 134 1070 417 361 299 240 XIM-A-0108 DM300 Unit Downflow Duct Connections CFM Static RESISTANCES1 Power Exhaust PerformanceBlower Motor and Drive Data Phasing Checking AIR Supply CFMIWG Drop Pressure Nominal CFM Thousands Supply AIRSequence of Operations Overview OperationCooling Sequence of Operation LOW-PRESSURE Limit Switch Safety Controls ResetCompressor Protection Flash CodesHeating Operation Errors Limit Control SettingHeat Anticipator Setpoints Electric Heat Anticipator SetpointsGAS Heating Operation Errors GAS Valve PipingGAS Valve START-UP Cooling START-UP GAS Heat Shut DownPRE-START Check List POST-START Check List GASManifold GAS Pressure Adjustment Burner AIR Shutter AdjustmentBurner Instructions Checking GAS InputTroubleshooting Adjustment of Temperature RiseCooling Troubleshooting Guide GAS Rate Cubic Feet PER HourXIM-A-0108 XIM-A-0108 XIM-A-0108 XIM-A-0108 GAS Heat Troubleshooting Guide XIM-A-0108 Unit Flash Codes Unit Control Board Flash Codes Unit Control BoardUnit Control Board Option Setup Option Byte SetupXIM-A-0108 Johnson Controls Unitary Products Johnson Controls Unitary Products York Drive Norman, OK

DM300, DM240, DM180 specifications

Sunlife Enterprises has made significant strides in the competitive market of digital management tools with their innovative lineup of products: the DM240, DM300, and DM180. Each of these devices has been engineered to cater to specific operational needs while sharing a common foundation of advanced technology, versatility, and user-centric design.

The DM240 is an entry-level model that caters to small businesses looking for an efficient digital management solution without the hefty price tag. With a compact design and intuitive user interface, the DM240 allows for seamless integration into various work environments. Key features include a high-resolution touchscreen display, which facilitates easy navigation and quick access to essential functions. The device supports wireless connectivity options, ensuring users can manage tasks from anywhere within their operating environment. The energy-efficient design of the DM240 also promotes sustainability without compromising performance.

Moving up the line, the DM300 offers enhanced capabilities for medium-sized enterprises. This model is powered by advanced processing technology, allowing for faster data handling and superior multitasking. The DM300 features expanded memory and storage options, ensuring that users can manage larger datasets effortlessly. Additionally, with built-in advanced security features like biometric authentication and encrypted data storage, businesses can ensure that sensitive information remains protected. The intuitive software interface of the DM300 is designed for ease of use while providing advanced analytics tools to enable users to make data-driven decisions.

At the top of the range is the DM180, a sophisticated solution tailored to large organizations with complex digital management needs. The DM180 showcases a state-of-the-art design with high-performance computing capabilities. It features an expansive multi-touch display, allowing multiple users to interact simultaneously, facilitating collaboration and teamwork. The DM180 is equipped with cloud integration options, promoting real-time data access and sharing among teams, regardless of location. Its scalability ensures that businesses can adapt the system to accommodate growth without compromising functionality. Moreover, it offers comprehensive reporting and analytics tools, empowering organizations to gain valuable insights into their operations.

In summary, Sunlife Enterprises’ DM240, DM300, and DM180 models stand out for their unique features designed to meet the evolving needs of businesses. With a focus on user experience, performance, and security, these devices are poised to help organizations enhance productivity and drive innovation in the digital management landscape.