Sunlife Enterprises DM180, DM300, DM240 installation manual GAS Heat Troubleshooting Guide

Page 50

356214-XIM-A-0108

15.If none of the above correct the error, replace the UCB.

GAS HEAT TROUBLESHOOTING GUIDE

Troubleshooting of components may require opening the electrical control box with the power connected to the unit. Use extreme care when working with live circuits! Check the unit nameplate for the correct line voltage and set the voltmeter to the correct range before making any connections with line termi- nals.

When not necessary, shut off all electric power to the unit prior to any of the following mainte- nance procedures so as to prevent personal injury.

Label all wires prior to disconnection when ser- vicing controls. Wiring errors can cause improper and dangerous operation, which could cause injury to person and/or damage unit components. Verify proper operation after servicing.

NOTE: To find the Btu input, multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality (contact your gas company for this information - it varies widely from city to city.).

The furnace may shut down on a high temper- ature condition during the procedure. If this occurs, the UCB energize the supply air blower motor until the high temperature limit has reset. Caution should be used at all times as the sup- ply air blower may energize regardless of the room thermostat fan switch position.

On calls for heating, the draft motor operates and the furnace lights but the supply air blower motor does not energize after a short delay (the room thermostat fan switch is in “AUTO” position).

1.Place the thermostat fan switch in the “ON” posi- tion. If the supply air blower motor energizes, go to Step 10.

2.If the supply air blower motor does not energize when the fan switch is set to “ON,” check that line voltage is being supplied to the contacts of the M3 contactor, and that the contactor is pulled in. Check for loose wiring between the contactor and the sup- ply air blower motor.

3.If M3 is pulled in and voltage is supplied at M3, lightly touch the supply air blower motor housing. If it is hot, the motor may be off on inherent protec- tion. Cancel any thermostat calls and set the fan switch to “AUTO”, wait for the internal overload to reset. Test again when cool.

4.If M3 is not pulled in, check for 24 volts at the M3 coil. If 24 volts is present at M3 but M3 is not pulled in, replace the contactor.

5.Failing the above, if there is line voltage supplied at M3, M3 is pulled in, and the supply air blower motor still does not operate, replace the motor.

6.If 24 volts is not present at M3, check that 24 volts is present at the supply air blower motor terminal on the UCB. If 24 volts is present at the UCB termi- nal, check for loose wiring between the UCB and M3.

7.If 24 volts is not present at the UCB supply air blower motor terminal, check for 24 volts from the room thermostat. If 24 volts is not present from the room thermostat, check for the following:

a.Proper operation of the room thermostat (contact between R and G with the fan switch in the “ON” position and in the “AUTO” position during operation calls).

b.Proper wiring between the room thermostat and the UCB.

c.Loose wiring from the room thermostat to the UCB.

8.If 24 volts is present at the room thermostat but not at the UCB, check for proper wiring between the thermostat and the UCB, i.e. that the thermostat G terminal is connected to the G terminal of the UCB, and for loose wiring.

9.If the thermostat and UCB are properly wired, replace the UCB.

50

Johnson Controls Unitary Products

Image 50
Contents Installation Table of Contents List of Figures List of TablesInspection Safety ConsiderationsGeneral ReferenceRenewal Parts ApprovalsProduct Nomenclature Ton Sunline & Magnum & MagnaDRY Model Number NomenclatureLimitations InstallationInstallation Safety Information Unit Application Data LocationRigging and Handling ClearancesDuctwork Fixed Outdoor AIR Intake DamperService Access FiltersField Wiring DM ELECTRIC/ELECTRIC and GAS/ Electric Units Thermostat Power and Control WiringControl Wire Sizes Electric Heat Application Data Optional Electric HeatGAS Piping Optional GAS HeatGAS Heat Application Data Pipe SizingExternal Supply Connection External SHUT-OFF Vent and Combustion AIR Hoods Vent and Combustion AIR HoodOptional Power EXHAUST/BAROMETRIC Relief Damper Rain Hood Enthalpy Setpoint Adjustment Four and SIX Point Loads Physical Data ModelsDM Electrical Data -WITHOUT Powered Convenience Outlet SizeDM Electrical Data -WITH Powered Convenience Outlet Front View Rear View Dimensions Unit Clearances and Rain Hood Dimensions 15, 20 & 25 TON Altitude Correction Factors AIR Temp Altitude MeterALTITUDE/TEMPERATURE Conversion Factor High Static Drive CFM 80 m3/s 30 m3/s 10 m3/s 40 m3/s 1030 378 321 258 199 134 1070 417 361 299 240 XIM-A-0108 DM300 Unit Downflow Duct Connections CFM Blower Motor and Drive Data Power Exhaust PerformanceStatic RESISTANCES1 Phasing Checking AIR Supply CFMIWG Drop Pressure Nominal CFM Thousands Supply AIRCooling Sequence of Operation OperationSequence of Operations Overview LOW-PRESSURE Limit Switch Compressor Protection Safety ControlsReset Flash CodesHeat Anticipator Setpoints Heating Operation ErrorsLimit Control Setting Electric Heat Anticipator SetpointsGAS Heating Operation Errors GAS Valve PipingGAS Valve START-UP Cooling PRE-START Check List START-UP GAS HeatShut Down POST-START Check List GASBurner Instructions Manifold GAS Pressure AdjustmentBurner AIR Shutter Adjustment Checking GAS InputCooling Troubleshooting Guide TroubleshootingAdjustment of Temperature Rise GAS Rate Cubic Feet PER HourXIM-A-0108 XIM-A-0108 XIM-A-0108 XIM-A-0108 GAS Heat Troubleshooting Guide XIM-A-0108 Unit Flash Codes Unit Control Board Flash Codes Unit Control BoardUnit Control Board Option Setup Option Byte SetupXIM-A-0108 Johnson Controls Unitary Products Johnson Controls Unitary Products York Drive Norman, OK

DM300, DM240, DM180 specifications

Sunlife Enterprises has made significant strides in the competitive market of digital management tools with their innovative lineup of products: the DM240, DM300, and DM180. Each of these devices has been engineered to cater to specific operational needs while sharing a common foundation of advanced technology, versatility, and user-centric design.

The DM240 is an entry-level model that caters to small businesses looking for an efficient digital management solution without the hefty price tag. With a compact design and intuitive user interface, the DM240 allows for seamless integration into various work environments. Key features include a high-resolution touchscreen display, which facilitates easy navigation and quick access to essential functions. The device supports wireless connectivity options, ensuring users can manage tasks from anywhere within their operating environment. The energy-efficient design of the DM240 also promotes sustainability without compromising performance.

Moving up the line, the DM300 offers enhanced capabilities for medium-sized enterprises. This model is powered by advanced processing technology, allowing for faster data handling and superior multitasking. The DM300 features expanded memory and storage options, ensuring that users can manage larger datasets effortlessly. Additionally, with built-in advanced security features like biometric authentication and encrypted data storage, businesses can ensure that sensitive information remains protected. The intuitive software interface of the DM300 is designed for ease of use while providing advanced analytics tools to enable users to make data-driven decisions.

At the top of the range is the DM180, a sophisticated solution tailored to large organizations with complex digital management needs. The DM180 showcases a state-of-the-art design with high-performance computing capabilities. It features an expansive multi-touch display, allowing multiple users to interact simultaneously, facilitating collaboration and teamwork. The DM180 is equipped with cloud integration options, promoting real-time data access and sharing among teams, regardless of location. Its scalability ensures that businesses can adapt the system to accommodate growth without compromising functionality. Moreover, it offers comprehensive reporting and analytics tools, empowering organizations to gain valuable insights into their operations.

In summary, Sunlife Enterprises’ DM240, DM300, and DM180 models stand out for their unique features designed to meet the evolving needs of businesses. With a focus on user experience, performance, and security, these devices are poised to help organizations enhance productivity and drive innovation in the digital management landscape.