Macurco SS102HC-1 manual Setting the Controls, Alarm Delay Programming SS103-10A, Alarm Action

Page 4

MACURCO CONTROLLERS & DETECTORS (CONT.)

SETTING THE CONTROLS

If your installation has no pre-determined Fan and Alarm set points, Macurco makes the following suggestions: Set the FAN 1 level 50% higher than the average time weighted average of carbon monoxide (CO), usually 50 ppm, that is desired in the facility. This will be a FAN 1 setting of 75.

Set the SS103-10AFAN 2 level 50% higher than FAN 1, or about 112 ppm

Set the SS103-3AFAN 2 and the SS103-10AALARM to 200ppm. Set both Alarm Delays to about 30 minutes. NOTE: Do not set the SS103-10AALARM higher than 200 ppm when using SS102HC-1sensors.

If the Alarm relay is used to operate a fan, Macurco suggests that the Time Delay be set to about 3 minutes, and on the SS103-10A, the ALARM level be set to 50% higher than the FAN 2 or about 170.

ALARM DELAY PROGRAMMING: SS103-10A

Set the ALARM adjustment pot to the desired STEL (Short Term Exposure Limit). Usually, this is the Uniform Building Code (UBC) standard of 200 ppm. (OSHA suggests using a 200 ppm CEILING, but currently has no standard for STEL for carbon monoxide.) To set the Alarm delay on the SS103-10Ause the four section programming switch, which is located on the printed circuit board near the fan and alarm relays. A chart inside the cover of the case shows the settings for popular delays. Figure 1 shows more settings.

Figure 1.

ON

OFF

1

2

3

4

1

2

3

4

1

2

3

4

1

2

3

4

1

2

3

4

1

2

3

4

 

50 min.

 

44 min.

 

 

35 min.

 

25 min.

 

 

8 min.

 

15 sec.

NOTE: If using SS102HC-1sensors, do not set the Alarm above 200.

ALARM ACTION

If an alarm is used, a procedure should be set up in the facilities emergency response procedures for what action to take when the alarm occurs. Consider the following in making those decisions:

The Carbon Monoxide levels of 50 ppm averaged over 8 hours and 200 ppm for some time period, are based on full shift exposures of workers. This usually does not happen in parking garages, where most people are there for only a few minutes.

Unless there are full time workers in the facility, Macurco suggests that CO alarms be not considered as life threatening emergencies. Instead use them as advisories to check that all control system components are operating OK.

For the SS102H, in addition to Carbon Monoxide, this system will actuate on smoke and various gases such as gasoline fumes, propane, alcohol and other combustible vapors.

LIMITED WARRANTY

The SS102H, SS102HC-1, SS103-3A, and SS103-10A gas detectors are warranted to be free from defective material and workmanship for a period of one (1) year from the date of installation. If any component becomes defective during the warranty period, it will be replaced or repaired free of charge, if the unit is returned in accordance with the instructions below. This warranty does not apply to units that have been altered or had repair attempted, or that have been subjected to abuse, accidental or otherwise. The above warranty is in lieu of all other express warranties, obligations or liabilities. THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF ONE (1) YEAR FROM THE PURCHASE DATE. Macurco shall not be liable for any incidental or consequential damages for breach of this or any other warranty express or implied arising out of or related to the use of said gas detector. Manufacturer or its agent’s liability shall be limited to replacement or repair as set forth above. Buyer’s sole and exclusive remedies are return of the goods and repayment of the price, or repair and replacement of non-conforming goods or parts. (The Uniform Commercial Code applicable in the State of Colorado shall govern.)

RETURN INSTRUCTIONS

Call (303) 781-4062 for a Return Authorization number. Then carefully pack the gas detector with a written description of the nature of the return. Send the unit to the following address:

Macurco Inc.

3946 South Mariposa Street

4

Image 4
Contents General Information LocationSS102H & SS102HC-1 General Information SS102H Sensor OperationSS103 Installation SS103 WiringSS102HC-1 Sensor Operation Stabilization TimeTesting the System SS103 OperationSetting the Controls Alarm Delay Programming SS103-10AAlarm Action Limited WarrantyEnglewood, Colorado

SS102HC-1, SS103-10A, SS103-3A, SS102H specifications

Macurco provides advanced gas detection solutions with the SS102H, SS103-10A, SS102HC-1, and SS103-3A models, designed to ensure safety in various environments. These models are known for their reliability, accuracy, and ease of integration into existing systems.

The Macurco SS102H is a standalone carbon monoxide detector, renowned for its high sensitivity and quick response time. It features a self-diagnostic function that continuously tests the sensor and output circuits to ensure they are operating correctly. The unit is equipped with a 4-20 mA output for easy connectivity with building management systems. It also comes with a durable housing that makes it suitable for both residential and commercial applications.

The SS103-10A model is a versatile gas detector capable of sensing both carbon dioxide and carbon monoxide. This dual-functionality is crucial in environments like restaurants and industrial kitchens where multiple gas detection is vital. This model features a robust sensor technology that ensures precise measurements and a long operational life. It also includes an adjustable relay output, allowing users to set alarm conditions according to specific needs.

For environments requiring continuous monitoring and alert systems, the Macurco SS102HC-1 is designed to detect harmful gases like carbon monoxide, methane, and propane. Its advanced analytical technology can distinguish between these gases effectively, making it ideal for residential, commercial, and industrial applications. The SS102HC-1 is also designed for easy calibration and features a visual and audible alarm, ensuring quick response in emergencies.

Lastly, the SS103-3A model offers enhanced detection capabilities for various combustible gases. With its wide array of sensor technologies, this model excels in providing accurate readings, even in challenging conditions where other detectors might fail. It is ideal for both indoor and outdoor applications. Additionally, the SS103-3A supports multiple output options including relay, analog voltage, and serial communication, making it easy to integrate into existing alarm systems.

In summary, the Macurco SS series provides reliable, accurate, and robust gas detection solutions tailored to meet the demands of various environments. Their innovative technologies ensure durability, longevity, and safety, making them indispensable in maintaining air quality and preventing hazardous situations.