Bacharach 3015-4286 manual Mounting Instructions, Connecting Gas Sample, Purge, and Exhaust Lines

Page 10

Mounting Instructions

The AGMSZ should be installed plumb and level and securely fastened to a rigid mounting surface.

The enclosure utilizes keyhole mounting brackets designed for #12 pan head screws. Locate the four screws as shown in the diagram below and leave the screw heads protruding approximately 3/16".

Enclosure Mounting Specs

Hold the monitor flat against the mounting surface and allow it to slide down engaging the screw heads in the keyhole slots of the mounting brackets. Adjust the screws as necessary to hold the monitor securely against the mounting surface.

Connecting Gas Sample, Purge, and Exhaust Lines

Overview

A single gas-sample line needs to be run from the AGMSZ to the area of the facility to be monitored. An optional purge line can be run to bring fresh (zero) air into the monitor for detector zeroing purposes. And an optional exhaust line can be installed to vent the sample gas away from the monitor. All tubing connections are made on the bottom of the enclosure as shown in the illustration below.

AGMSZ Bottom View

½" / ¾" SERVICE

 

PURGE AIR

 

½" / ¾" SERVICE

KNOCKOUT*

 

INLET PORT

 

KNOCKOUT*

* There is an additional Service Knockout on top of the case

GAS SAMPLE INLET PORT

GAS SAMPLE EXHAUST PORT

6

Instruction 3015-4286

Image 10
Contents Agmsz Ammonia Gas Monitor Single Zone Installation / Operation / MaintenanceRev September Warranty Register Your Warranty by VisitingTable of Contents Maintenance Hazard Symbols on Monitor How to Use This ManualIntroduction Safety Precautions General Description Functional OverviewUnderstanding Monitoring Levels Agmsz Refrigerant Gas Leak Monitor Mechanical Room Placement Suggested Location of Sampling PointInspection InstallationInstallation Considerations Locating the MonitorOverview Connecting Gas Sample, Purge, and Exhaust LinesMounting Instructions Enclosure Mounting SpecsConnecting the Exhaust Line Connecting the Gas-Sample LineConnecting the Purge Line Tubing ConsiderationsInterior Schematic Interior SchematicElectrical Wiring AC Power ConnectionsExternal Alarm Relay Connector Connecting External AlarmsConnection MA Current Loop Connector Typical External Alarm Relay 1 WiringMA Current Loop Interface Instruction Front Panel Display and Controls OperationGeneral Operation Display Screens Initial Power UpData Display Screen Function Screens Edit Evac Level 0500 PPM R717 Calfactor Clearing / Silencing a Gas Alarm Working with Gas AlarmsWorking with System Faults Viewing the Gas Alarm LogViewing the Fault Log Fault CodesKeypad Functions Clearing the Stored PPM Log, Alarm & Fault DataWorking with the P-CHK Function Screen DisplaySecond Diagnostic Screen First Diagnostic ScreenWorking with the Diagnos Function Adjusting Calibration Factor Calibration ProcedureWorking with the Calibration Function Maintenance Replacement Parts Replacement Parts & Optional AccessoriesOptional Accessories Service Centers Specifications Years from date of shipmentInstruction Headquarters Hunt Valley Circle, New Kensington, PA

3015-4286 specifications

Bacharach 3015-4286 is an innovative and versatile instrument, specifically designed for professionals in industries where air quality monitoring is paramount. This model stands out due to its advanced features and technologies, making it a preferred choice for those needing accurate and reliable measurements of various gases.

One of the main features of the Bacharach 3015-4286 is its multi-gas detection capability. It can simultaneously monitor up to five different gases, providing users with a comprehensive understanding of their environment in real-time. This is particularly beneficial in applications such as HVAC, refrigeration, and industrial processes, where the presence of gases like carbon dioxide, ammonia, and refrigerants can have significant safety and regulatory implications.

The device utilizes state-of-the-art sensors that ensure high sensitivity and selectivity to the target gases. These sensors are designed for quick response times, allowing users to detect any changes in gas concentrations almost instantaneously. This responsiveness is crucial for environments where rapid decision-making is necessary to ensure safety and compliance with environmental regulations.

In addition to its gas detection capabilities, the Bacharach 3015-4286 features a user-friendly interface. The large display screen provides clear readouts, and the intuitive navigation system allows users to easily switch between different measurement modes and settings. This accessibility makes it suitable for both experienced professionals and those who may be new to gas monitoring technologies.

Battery life is another characteristic that sets the Bacharach 3015-4286 apart from its competitors. With efficient power management, the device can operate continuously for extended periods without the need for frequent recharging or battery replacement. This reliability is crucial for fieldwork, where access to power sources may be limited.

Moreover, the device is compact and lightweight, enhancing its portability. Users can easily transport the Bacharach 3015-4286 to various job sites without inconvenience. Its robust design ensures durability in diverse working conditions, further establishing it as a dependable tool in the field.

In summary, the Bacharach 3015-4286 is a cutting-edge gas detection instrument offering multi-gas detection, advanced sensors, user-friendly operation, long battery life, and portability. These features make it an indispensable asset for professionals seeking to ensure safety and compliance in their working environments.