Heat Controller BHD-301-G, BHD-501-G Defective Compressor, Compressor Winding Test, Ground Test

Page 8

BHD-G Service Manual

Portable Dehumidifier with R-410A

Heat Controller, Inc.

 

 

 

5.Basic Test Procedures

5.1 DEFECTIVE COMPRESSOR

Compressors are single phase, 115 volt. All compressor motors are permanent split capacitor type using only a running capacitor across the start and run terminal.

All compressors are internally spring mounted and externally mounted on rubber isolators.

COMPRESSOR WINDING TEST

Remove compressor terminal box cover and disconnect wires from terminals.

Using an ohmmeter, check continuity across the following:

1. Terminal “C” and “S” - no continuity

 

- open winding - replace compressor.

 

2. Terminal “C” and “R” - no continuity

 

- open winding - replace compressor.

 

3. Terminal “R” and “S” - no continuity

 

- open winding - replace compressor.

Figure 1: Compressor winding test

 

GROUND TEST

Use an ohmmeter set on its highest scale. Touch one lead to the compressor body (clean point of contact as a good connection is a must) and the other probe in turn to each compressor terminal (see Figure 2.) If a reading is obtained, the compressor is grounded and must be replaced.

CHECKING COMPRESSOR EFFICIENCY

The reason for compressor inefficiency is normally due to broken or damaged suction and/or discharge valves, reducing the ability of the compressor to pump refrigerant gas.

This condition can be checked as follows:

1.Install a piercing valve on the suction and discharge or liquid line.

2.Attach gauges to the high and low sides of the system.

3.Start the system and run a “cooling or heating performance test.” If test shows:

A. Below normal high side pressure.

B. Above normal low side pressure.

Figure 2: Typical ground test

C. Low temperature difference across coil.

 

The compressor valves are faulty - replace the compressor.

 

THERMAL OVERLOAD (External)

Some compressors are equipped with an external overload which is located in the compressor terminal box adjacent to the compressor body. The overload is wired in series with the common motor terminal. The overload senses both amperage and compressor temperature. High motor temperature or amperage heats the disc causing it to open and break the circuit to the common motor terminal.

Heat generated within the compressor shell is usually due to:

1.High amperage.

2.Low refrigerant charge.

3.Frequent cycling.

4.Dirty condenser.

TERMINAL OVERLOAD – TEST (Compressor - External Type)

1.Remove overload.

2.Allow time for overload to reset before attempting to test.

3.Apply ohmmeter probes to terminals on overload wires. There should be continuity through the overload.

7

Image 8
Contents Portable Dehumidifer Series With R-410A Table of Contents Safety Precautions Unit FeaturesInsulation Resistance Test Control LocationsTimer Set Control TimerOutside Dimensions Operation with Water Tank Operating ConditionsTurning the Unit on or OFF Maintenance Operation with Continuous DrainagePowering on the Unit Setting the Relative HumidityContinuous Dehumidification Mode Powering OFF the UnitDefective Compressor Compressor Winding TestGround Test Checking Compressor EfficiencyHermetic Component Replacement Sealed Refrigeration System RepairsChecking the Internal Overload Equipment RequiredFAN Motor CapacitorCapacitor Test Troubleshooting Guide Identify ALL Possible PCB Fault CodesTrouble Shooting Room Airconditioner Voltage LimitsHumidity sensor check Fail to start or fail to start motor Abnormal noise Complaint Cause RemedyPortable Dehumidifier with R-410A Complaint Cause Remedy Wiring Diagram 05/2010

BHD-301-G, BHD-651-G, BHD-501-G specifications

The Heat Controller BHD series, comprising models BHD-651-G, BHD-301-G, and BHD-501-G, is designed to meet diverse heating needs with efficiency and reliability. Each model incorporates advanced features and technologies that enhance user experience, making them ideal for both home and commercial use.

Starting with the BHD-651-G, this model is a powerhouse, offering significantly higher output capacity suitable for larger spaces. It boasts an intelligent thermostat that ensures precise temperature control, allowing users to maintain their preferred environment effortlessly. The BHD-651-G employs a dual heating technology, combining convection and radiant heat for balanced warmth. Additionally, its energy-saving mode optimizes power consumption without sacrificing comfort, making it an eco-friendly choice.

The BHD-301-G is designed for medium-sized areas, striking a perfect balance between power and portability. Featuring a sleek design, it is lightweight and easy to move around. One of its standout features is the programmable timer, allowing users to set heating schedules that align with their lifestyles. This model also includes a filter system that cleans and purifies the air while heating, ensuring a healthier indoor environment. Moreover, the BHD-301-G operates quietly, making it ideal for use in bedrooms or offices.

Finally, the BHD-501-G caters to a variety of settings where flexibility is crucial. This model is equipped with multi-directional airflow, enabling users to direct heat where it is most needed. The BHD-501-G also features an advanced safety system, including overheat protection and a tip-over switch, ensuring peace of mind during use. Its user-friendly interface with intuitive controls simplifies operation, allowing for effortless adjustments to temperature and settings.

In summary, the Heat Controller BHD series offers a comprehensive range of features designed to provide efficient heating solutions tailored to different environments. With technologies aimed at enhancing power efficiency, air quality, and user comfort, the BHD-651-G, BHD-301-G, and BHD-501-G models stand out as top choices for reliable heat management. Their innovative characteristics ensure that users can enjoy warmth and comfort in any setting while being mindful of energy consumption and safety.