Lennox International Inc 505, 021 Check List, Demand Signals − Humiditrol EDA Enabled

Page 12

Check List

n

Checkpoint

What to Check

Action

 

 

 

 

 

Thermostat and

Wiring

Confirm Sensor connected to SignatureStatt using twisted pair

 

Sensor

 

wire (see wiring diagram figure 13)

 

 

 

 

 

Thermostat

Humiditrol® Installer Settings

Confirm HUMIDITROL is enabled (see figure 8)

 

Thermostat

Humiditrol® User Settings

Confirm HUMIDITROL − Dehumidify − ON is selected (see figure 8)

 

Thermostat

Humiditrol® User Settings

Confirm Relative Humidity setting (see figure 8)

 

Indoor Unit

Variable-Speed Blower Settings

Confirm Settings for age cool

 

 

 

(see indoor unit installation instructions and table 1, below)

 

 

 

 

 

Insulation

Charge Compensator

 

 

 

 

Confirm insulation is properly installed (see charge compensator kit

 

Insulation

Liquid Line

 

instructions; also, see figure 5)

 

 

 

 

Insulation

Vent Line to Suction Line

 

 

 

 

 

 

Charge Compen-

1/4"Line

Confirm 1/4" port oriented downward (see charge compensator

 

sator

 

details, figure 5)

 

 

 

 

 

Check/Flow Re-

3/8" Line

Confirm restrictor installed/oriented properly (see check/flow restric-

 

strictor

 

tor details figure 5)

 

 

 

 

 

System Charge

Refrigerant

With unit running in cooling mode, check and confirm system is

 

 

 

properly charged (see outdoor unit installation instructions).

 

 

 

 

 

Outdoor Unit

Fan Relay

Confirm (if unit has variable speed outdoor fan) relay is installed

 

 

 

properly (see wiring diagram figures 12 and 13)

 

 

 

 

 

Outdoor Unit

EDA Label

Confirm label is installed in prominent location and will be easily

 

 

 

visible during servicing.

 

 

 

 

 

NOTE − System will NOT operate in dehumidification mode with outdoor temperature at or above 95ºF.

 

 

 

 

 

Operational Status

Dehumidification Mode

Record supply air temperature and confirm temperature that it is

 

 

 

higher than in cooling mode.

 

 

 

 

 

Operational Status

Dehumidification Mode

On units with variable speed outdoor fan, check that fan operates

 

 

 

at approximately 250 rpm (lowest speed).

 

 

 

 

Table 1

Demand Signals − Humiditrol® EDA Enabled

Operating Sequence

 

System Demand

 

 

 

System Response

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat Demand

Relative Humidity

 

Blower

 

 

 

 

 

 

 

 

 

 

Com-

CFM

 

 

 

Y1

Y2

O

 

G

Status

D

 

System Type

Step

 

pressor

(Cool) %

Comments

 

 

 

 

 

 

 

 

 

 

 

 

Cooling Operation − No call for dehumidification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-stage outdoor unit

1

ON

(na)

ON

 

ON

Acceptable

24 VAC

High

100

Compressor and indoor

 

 

 

 

 

 

 

 

 

 

 

blower follow thermostat

Two-stage outdoor unit Y1

1

ON

ON

 

ON

Acceptable

24 VAC

Low

70

 

demand

 

 

 

 

 

 

 

 

 

 

 

Two-stage outdoor unit Y2

2

ON

ON

ON

 

ON

Acceptable

24 VAC

High

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Demand for Dehumidification and Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-stage outdoor unit

1

ON

(na)

ON

 

ON

Demand

24 VAC

High

100

Cooling operation has

 

 

 

 

 

 

 

 

 

 

 

priority

Two-stage outdoor unit Y1

1

ON

ON

 

ON

Demand

24 VAC

Low

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two-stage outdoor unit Y2

2

ON

ON

ON

 

ON

Demand

24 VAC

High

100

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification Mode Only − No Cooling Demand

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-stage outdoor unit

1

ON

(na)

ON

 

ON

Demand

0 VAC

High

50 − 70*

A Humiditrol® EDA−

 

 

 

 

 

 

 

 

 

 

 

equipped system is allowed

 

 

 

 

 

 

 

 

 

 

 

to operate and cool room

 

 

 

 

 

 

 

 

 

 

 

temperature below set point

 

 

 

 

 

 

 

 

 

 

 

(but only by 2ºF) when try-

Two-stage outdoor unit Y2

2

ON

ON

ON

 

ON

Demand

0 VAC

High

50 − 70*

ing to satisfy a persisting

 

 

 

 

 

 

 

 

 

 

 

humidity set point; it is not

 

 

 

 

 

 

 

 

 

 

 

allowed to operate at all

 

 

 

 

 

 

 

 

 

 

 

when outdoor temperature

 

 

 

 

 

 

 

 

 

 

 

is >95ºF.

 

 

 

 

 

 

 

 

 

 

 

* NOTE − Blower CFM speed (percentage) will vary depending on selected indoor equipment (furnace, coil blower, etc.).

 

Page 12

EDA 01/06

Image 12
Contents Humiditrol Enhanced Dehumidification Accessory EDA Units Table of ContentsHumiditrol EDA Series Unit Shipping & Packing ListUnit Dimensions EDA Model Dimensions − Inches mmInstallation Dimensions and Arrangement Furnace ShownPosition Furnace Shown Component Functions Check/Flow Restrictor OperationEDA Unit Parts Arrangement EDA−024B EDA−036C EDA−060D General Installation Information Electrical WiringEDA Installation and Checkout Flow Chart EDA Installation & Checkout Flow Chart Required Parts all applicationsTypical Installation Horizontal Air Handler shown DetailsLeak Testing, Evacuating, Charging Setting Thermostat Insulating and Sealing the UnitOther System Components Blower ControlEDA Unit Operation Operation NotesCooling Cycle with EDA Coil Active Model EDA−036C shown Cooling Cycle with EDA Coil Inactive Model EDA−036C shown Demand Signals − Humiditrol EDA Enabled Check ListRepair Parts Wiring DiagramsControl Wiring Requirements Air ResistanceTypical EDA/Condensing Unit Wiring Diagram Control WiringTypical EDA/Heat Pump Wiring Diagram Start