Lennox International Inc 505, 021 installation instructions Leak Testing, Evacuating, Charging

Page 8

Leak Testing, Evacuating, Charging

IMPORTANT

Prior to starting the outdoor unit for charging, be

IMPORTANT sure the 3-way valve is energized and in the ing" (forward) position (see figure 7).

The 3−way diverting valve actuator shaft setscrew

3. Very little charge is required for the additional volume

(see figure 7) is factory set and is not to be adjusted.

of the EDA unit. When in normal cooling, the compo-

 

 

nents will all be occupied by vapor that has very little

3−way Diverting Valve Operation

weight. At most (depending on the model) an addition-

NOTE − During system operation, the 3-way valve requires

al 1/4 pound of refrigerant may be required.

24-volt power to drive between cooling and dehumidifica-

4. When shifting from dehumidify mode to cooling, or

tion.

vice versa, wait at least 10 minutes for the system to

The 3−way diverting valve is actually two valves connected

reach stable operating pressure before checking tem-

by a common shaft, designed to open one valve while clos-

peratures and pressures, or adjusting refrigerant

ing the other, and vice versa. For evacuating (with power

charge.

off), the diverting valve can be REPOSITIONED using its

NOTE − Prior to starting the outdoor unit for charging,

actuator lever, a long setscrew that has been factory-set to

set the thermostat to call for cooling (dehumidification

a precise point on the common shaft. Do not loosen (un-

OFF). It will take about 90 seconds for the 3−way di-

screw) the setscrew. Should the setscrew become

verting valve to energize and shift to the cooling posi-

loose, carefully follow the note in figure 6 to position

tion. To ensure that the 3-way diverting valve is ener-

and tighten it.

gized and in the

 

 

the position of the 3-way diverting valve actuator shaft

Re−aligning Setscrew

setscrew in figure 7; if properly shifted, the setscrew

will be in the forward position.

 

NOTE − Actuator shaft setscrew is factory set and must not be ad-

 

justed. If the set screw should become loose, use a pliers to grip the

Setting 3−Way Diverting Valve to

shaft where shown (1) and rotate the shaft (in direction of the black

Evacuate Position

arrow) until the pin stops (inset shows pin and stops). Press the red

button (2) in the direction of the white arrow and move the lever (3)

1. PUSH RED TAB IN DIRECTION INDICATED.

to the forward position and tighten setscrew to 60 in-lbs torque.

2. PUSH ACTUATOR SHAFT DOWN TOWARD THE

 

 

CENTER−OF−TRAVEL POSITION

2

 

1

1

 

3

2

STOP

 

PIN

 

SHAFT

 

STOP

 

 

COOLING

Figure 6

(FORWARD)

 

 

EVACUATE

 

(CENTER)

Leak Testing, Evacuating, Charging

DEHUMIDIFICATION

1. Set the 3−way diverting valve actuator shaft to the cen-

(REARWARD)

ter (evacuate) position for leak testing and evacuation

Figure 7

(see figure 7). IMPORTANT! The actuator shaft

 

must be set as described to allow the EDA to evac-

5. The charge must be checked with the system in cool-

uate more quickly.

ing operation (dehumidification OFF). After testing

2. Refer to instructions provided with the outdoor unit for

and charging as required, set the thermostat to force

leak testing, evacuating and charging procedures.

a demand for dehumidification.

Page 8

 

EDA 01/06

 

Image 8
Contents Humiditrol Enhanced Dehumidification Accessory EDA Units Table of ContentsHumiditrol EDA Series Unit Shipping & Packing ListUnit Dimensions EDA Model Dimensions − Inches mmPosition Furnace Shown Installation Dimensions and ArrangementFurnace Shown EDA Unit Parts Arrangement EDA−024B EDA−036C EDA−060D Component FunctionsCheck/Flow Restrictor Operation EDA Installation and Checkout Flow Chart General Installation InformationElectrical Wiring EDA Installation & Checkout Flow Chart Required Parts all applicationsTypical Installation Horizontal Air Handler shown DetailsLeak Testing, Evacuating, Charging Setting Thermostat Insulating and Sealing the UnitOther System Components Blower ControlCooling Cycle with EDA Coil Active Model EDA−036C shown EDA Unit OperationOperation Notes Cooling Cycle with EDA Coil Inactive Model EDA−036C shown Demand Signals − Humiditrol EDA Enabled Check ListRepair Parts Wiring DiagramsControl Wiring Requirements Air ResistanceTypical EDA/Condensing Unit Wiring Diagram Control WiringTypical EDA/Heat Pump Wiring Diagram Start