SECTION 2 – OPERATING INSTRUCTIONS

The POWERLINKTM On-Board Generator System will operate continuously at 1000 watts output and up to 1500 watts for brief periods. Operating at loads above 1000 watts may cause the POWERLINK TM system to reset, halting the electrical output. To avoid overloading the generator system, you must check the power (wattage) requirements of the appliance or tool before plugging it into the power receptacle. The generator maintains 120 volts output throughout the engine speed range; however, output wattage increases with engine speed. Always select the engine speed that will power the electrical device satisfactorily without triggering the POWERLINKTM system reset.

The POWERLINKTM On-Board Generator System includes three devices that will interrupt power output to the receptacle. Please refer to the POWERLINKTM Operator’s manual for details on the function of these devices.

2.12.1Starting the POWERLINKTM GENERATOR

A.Complete Pre-Start Check List.

B.Set park brake and shift transmission into neutral. (NOTE: POWERLINK™ system will not operate unless park brake has been set and transmission is in neutral.)

C.Start engine. Refer to Section “Starting Engine”.

D.Set generator engine speed control to ‘FAST’ (Rabbit) position. (See Figure 2.7.)

E.Actuate the POWERLINKTM system reset switch:

Move the switch to the OFF (‘0’) position, then return it to the ON (‘I’) position.

F.Test the GFCI to insure it is functioning properly. Please refer to Section “Testing the GFCI”.

G.Before plugging in the electrical appliance or tool, make sure it is turned OFF and the wattage does not exceed the output of the POWERLINKTM generator.

2.12.2Resetting the POWERLINKTM GENERATOR If the system loses electrical power:

A.Turn off any appliance or tool that was in use prior to the loss of power.

B.Verify the reset button on the GFCI has not been tripped. The reset button will pop out if tripped. To restore, press the reset button.

C.The engine must be running, the park brake set, and the transmission in neutral.

D.Actuate the POWERLINKTM reset switch: Move the switch to the OFF position and then return it to the ON position.

NOTE: The system must be reset any time the engine is stopped for any reason.

E.If power does not resume after reset, it may be a thermal overload. Wait 15 minutes before actuating the reset.

2.12.3Testing the GFCI

To insure proper operation and avoid injury, the GFCI receptacle should be tested before every use.

A.Have the POWERLINK system running and the power reset.

B.Plug in a radio or lamp to verify that electrical power is present.

C.Press the GFCI TEST button in order to trip the system and stop the flow of electricity.

D.If the radio or lamp is still functioning, the GFCI is not working properly. Contact an Authorized Service Dealer.

E.If the power goes off, the GFCI is working properly. To restore power, press the GFCI RESET button.

2.12.4Stopping the POWERLINKTM GENERATOR

A.Turn off electrical appliance or tool.

B.Move system reset switch to OFF position

C.Set generator engine speed control to ‘SLOW’ (Turtle) position.

WARNING

GFCI RECEPTACLE

SYSTEM RESET SWITCH

GFCI TEST/RESET BUTTONS

FAST

The POWERLINKTM Generator is equipped with a safety interlock system. The generator speed control lever must be set all the way down to ‘SLOW’ before disengaging the parking brake or shifting the transmission from neutral. Failure to do so will cause the engine to die. DO NOT ATTEMPT TO OVERRIDE, REMOVE OR MODIFY THIS SAFETY FEATURE. INJURY, DEATH, OR EQUIPMENT DAMAGE MAY RESULT.

GENERATOR

SPEED SLOW CONTROL

POWERLINK™ GENERATOR SYSTEM (LOCATED UNDER OPERATOR’S SEAT)

FIGURE 2.7

D.Allow engine to idle for several minutes to cool down.

E.Unplug electrical cord(s) from receptacle(s).

F.Turn ignition switch to STOP and remove the key.

2119

Page 21
Image 21
Simplicity UVGT1621BV, UVG1621BV Starting the Powerlinktm Generator, Testing the Gfci, Stopping the Powerlinktm Generator