Lennox International Inc 505, 021 installation instructions EDA Installation & Checkout Flow Chart

Page 6

EDA Installation & Checkout Flow Chart

start

ARE

ALL REQUIRED NO PARTS

AVAILABLE

?

PROCURE

MISSING PARTS

Required Parts (all applications)

EDA Unit, with check/flow restrictor & label Appropriate SignatureStatt Thermostat 46M98 − Outdoor Sensor

84X49 − Twisted Pair Wire Appropriate Insulation and Piping Kit

Required Parts (2−Stage Heat Pump appl.)

12P61 − 75VA Transformer (for HP applications)

YES

Installation Process

Check Dehumidification Operation

ENSURE ALL POWER IS OFF

INSTALL EDA UNIT IN DUCT

SYSTEM

INSTALL THE CHARGE

COMPENSATOR (IF REQUIRED)

IN CONVENIENT LOCATION

(SEE FIGURE 5)

MAKE WIRING CONNECTIONS AS SHOWN IN FIGURES 12 & 13 (SEE PAGES 14 AND 15)

INSTALL

OUTDOOR UNIT

POWER UP THE INDOOR UNIT

SET COOLING SETPOINT ON ROOM THERMOSTAT TO 2 DEGREES ABOVE INDOOR TEMPERATURE (OUTDOOR UNIT WILL TURN OFF)

NOTE − A Humiditrol® EDA−equipped system is allowed to operate and cool room temperature below set point (but only by 2ºF) when trying to satisfy a persisting hu- midity set point.

SET DEHUMIDIFICATION SETPOINT TO 5% BELOW CURRENT ROOM RELATIVE HUMIDITY

MAKE ALL REFRIGERATION CONNECTIONS, BEING SURE TO INSTALL THE CHECK/FLOW RESTRICTOR (SEE FIGURE 5)

LEAK CHECK THE SYSTEM

WITH 3−WAY VALVE ASSEMBLY

SET TO ACUATE" (SEE

CHECK THAT 3−WAY VALVE

ASSEMBLY IS SET TO

SHOWN IN FIGURE 7

ENABLE HUMIDITROL ON ROOM THERMOSTAT (SEE FIGURE 8)

IS

THE OUTDOOR NO

TEMPERATURE BELOW

95ºF

?

YES

DEHUMIDIFICATION IS DE−ACTIVATED; CHECK FOR CORRECT OPERATION AT A TIME WHEN AMBIENT TEMPERATURE IS BELOW 95ºF.

FIGURE 7)

INSULATE ALL REFRIGERANT

LINES

EVACUATE THE SYSTEM AS

DESCRIBED IN THE OUTDOOR

UNIT INSTALLATION

INSTRUCTIONS

INSTALL OUTDOOR SENSOR

SET THERMOSTAT FOR

MAXIMUM COOLING

OPEN REFRIGERANT VALVES

TURN OUTDOOR UNIT MAIN

POWER ON

CHECK CHARGE AND CHARGE

AS NEEDED (SEE PAGE 8)

OUTDOOR UNIT:

COMPRESSOR IN HIGH STAGE;

FAN IN LOWEST SPEED;

EDA:

3−WAY VALVE ASSEMBLY TOTION" POSITION

INDOOR UNIT:

FAN IN DEHUMIDIFICATION SPEED

CHECK THE TEMPERATURE DIFFERENCE ACROSS THE EDA COIL AND THE LIQUID LINE TEMPERATURES AS NOTED IN FIGURE 9 ON PAGE 10

Figure 4

Page 6

EDA 01/06

Image 6
Contents Humiditrol EDA Series Unit Humiditrol Enhanced Dehumidification Accessory EDA UnitsTable of Contents Shipping & Packing ListUnit Dimensions EDA Model Dimensions − Inches mmInstallation Dimensions and Arrangement Furnace ShownPosition Furnace Shown Component Functions Check/Flow Restrictor OperationEDA Unit Parts Arrangement EDA−024B EDA−036C EDA−060D General Installation Information Electrical WiringEDA Installation and Checkout Flow Chart EDA Installation & Checkout Flow Chart Required Parts all applicationsTypical Installation Horizontal Air Handler shown DetailsLeak Testing, Evacuating, Charging Other System Components Setting ThermostatInsulating and Sealing the Unit Blower ControlEDA Unit Operation Operation NotesCooling Cycle with EDA Coil Active Model EDA−036C shown Cooling Cycle with EDA Coil Inactive Model EDA−036C shown Demand Signals − Humiditrol EDA Enabled Check ListControl Wiring Requirements Repair PartsWiring Diagrams Air ResistanceTypical EDA/Condensing Unit Wiring Diagram Control WiringTypical EDA/Heat Pump Wiring Diagram Start