Honeywell K9696V2 5.5Alarm Sensors, 5.6Inputs for Sensors, Tools, Cable, To configure inputs

Models: K9696V2

1 96
Download 96 pages 44.92 Kb
Page 64
Image 64
5.5Alarm Sensors

Multi-Media Unit: Installation Instructions

5.5Alarm Sensors

Tools

You need:

a slot screwdriver—supplied. The screws are slightly smaller than those for a 1/8" screwdriver.

-and -

a wire stripper.

Cable

To connect alarm-type hardware to a Multi-Media unit, use hookup wire in the 20-gauge range.

!52 To connect an alarm sensor

1.From the alarm wires’ tips, strip approximately 0.6 cm (1/4 inch) of insulation.

2.Insert each alarm wire into the screw-type, terminal connector on the ALARM terminal strip: one wire to the numbered terminal connection and the other wire to ground.

To avoid short-circuits, ensure that bare wire is not visible at the rear panel.

5.6Inputs for Sensors

!53 To configure inputs

1.Using View, start a maintenance session for the Rapid Eye site. Please wait until the “System Operational” message is displayed.

2.Click the Events tab. More tabs are displayed.

3.Click the Inputs tab.

4.Next to an input reported as “in use” by an installer, type the name of the input in the Input box. You can type a name of your choice.

5.Click the NO, NC or EOL button, as needed.

6.Ignore the “Log” and “Alarm” checkboxes.

7.Click Apply/Reset.

5–6

Page 64
Image 64
Honeywell K9696V2 5.5Alarm Sensors, 5.6Inputs for Sensors, Tools, Cable, To connect an alarm sensor, To configure inputs