Honeywell K9696V2 Alarm panel, Software setup, To set the FAULT RELAY to trigger

Models: K9696V2

1 96
Download 96 pages 44.92 Kb
Page 67
Image 67
Alarm panel

Other Site Hardware

Alarm panel

An alarm panel or other external device can be preset to warn your organization, if failure occurs. Failure to operate due to a power failure also triggers the relay, but does so immediately.

Software setup

!54 To set the FAULT RELAY to trigger

1.Using View software, start a maintenance session.

2.On the System tab, enable either:

Enable Status Pulse…

Monitor Alarm Reporting

both. See figure 47.

3.Click Apply/Reset.

4.On the Events tab, click the Outputs subtab.

5.The name of Output 6 has changed to “System Status Pulse”. You have the option of changing the name of the output by typing in the box.

6.You have the option of ending the maintenance session.

Fig. 47. Settings for monitoring a unit.

Enable Status Pulse. Enables the FAULT RELAY to trigger.

Monitor Alarm Reporting. Interruptions in reporting of alarms, greater than 19 minutes, trigger the fault relay. The monitoring is designed to report alarms that have not reached their designated alarm station, because of that alarm station being unavailable.

5–9

Page 67
Image 67
Honeywell K9696V2 Alarm panel, Software setup, To set the FAULT RELAY to trigger, Click Apply/Reset, Other Site Hardware