Beckett CF2500 manual Initial Air Settings, Damper Motor with Cover

Page 18

Section: Prepare the Burner for Start-up

Initial Air Settings

If your burner was built for a specific OEM application, the “Mfr’s Settings” label (see Figure 1) will indicate the application and the initial air settings made at Beckett. Please verify those settings using the following procedure.

If your burner was not built for a specified application, the following steps outline the procedure for initially setting the damper (these settings may be different from settings specific to a particular OEM).

Refer to Figure 17A/B and Table 4 for this procedure.

1.Remove the cover screw (A) then the cover (B) and set aside.

2.Push in on pin (G) to disengage the motor from the damper shaft and cam stack. Rotate the damper shaft by hand to place the adjustment cams in a position where their adjustment scale can be easily seen. Release pin (G) to secure the damper shaft and cam stack to the motor.

3.Using the wrench (C) supplied with the damper motor, adjust the blue low fire cam (D) to the initial setting listed in Table 6.

4.Using the same wrench, adjust the red high fire cam (H) to the initial settings listed in Table 6.

5.To adjust the high fire transition, use a small straight edge screwdriver. Turn the white adjustment screw located in the orange transition cam (J) until the cam indicator is half way between the high and low settings on the scale.

6.After setting all the cams, make sure the damper shaft and cam stack is set between its low fire setting and its high fire setting. (If you don’t it may not move when it is powered.) Push in pin (G), move the damper by hand so that notch (E) is between the low fire setting and high fire setting on scale (F), then release pin (G) to re-engage the motor. When the motor is powered it will go to its low fire setting.

This initial setting should be adequate for starting the burner at low fire. Once the burner is in operation, the air setting will be adjusted for best performance as discussed later in this manual. Don’t forget to re-install the cover after all adjustments have been made.

The damper plate is attached by screws to its shaft, and bears

against a flat on the shaft for alignment. The shaft is secured to the damper motor by a sleeve coupling with two setscrews bearing against the damper shaft and two more against the motor shaft. The motor shaft has a flat matching the one on the damper shaft. The flats on the damper shaft and the motor shaft should be aligned so that the position indicator in the damper motor reads accurately. The best way to align the flats is to tighten the setscrews that bear against the flats on the shafts

first, and then tighten the ones that bear against the round surface of the shafts afterward.

The test for proper alignment is to disengage the damper motor from its shaft using the disengaging pin (Item G in Figure 17B) and rotate the damper plate to its full closed position. The position indicator should point to 0° within + 5° tolerance.

Figure 17A - Damper Motor with Cover

Figure 17B - Damper Motor

Legend (Figures 17A & 17B)

ACover screw

BCover

CWrench

DLow fire cam (blue)

ECam notch

FDamper motor scale

GDisengaging pin

HHigh fire cam (red)

JTransition cam (orange)

18

Image 18
Contents Potential for Fire, Smoke and Asphyxiation Hazards To the Homeowner or Equipment OwnerContents General Information Hazard DefinitionsFrozen Plumbing Water Damage Hazard Pre-installation Checklist ClearancesFuel Supply Oil Supply Pressure Control Required Vent System Nozzle Pressure Correct Nozzle and Flow Rate RequiredElectrical Supply Fire, Smoke & Asphyxiation HazardVerify Air Tube Air Tube Combination CodesProtect the Air Tube From Overheating Mount the BurnerDust and Moisture Protect Against Dust Mount Flanges on Air TubeInstall Nozzle Line Assembly Install NozzleCheck Electrode Settings Maintain Electrode Specifications Mount Air Tube to BurnerSet Dimension Z Insert BurnerConnect Fuel Lines Psig to Electrical Shock Hazard Wire the BurnerIncorrect Wiring Will Result in Improper Control Operation Fire or Explosion HazardStandby Cad Cell Resistance MeasurementTypical Wiring 7505P Typical Burner Sequence of Operation RM7897A Control Typical Burner Sequence Operation RM7897AProfessional Installation Service Required Do Not Bypass Safety ControlsKeep Service Access Covers Securely Installed Dimension Adjusting Plate AssemblyInitial Head Position Initial Air Settings Damper Motor with CoverSet Appliance Limit Controls Professional Service RequiredStart the Burner Prepare the Fuel Unit for Air VentingIf burner stops during venting Set High-fire AirSet Low-fire Air If burner stops after flame establishedPerform Regular Maintenance Annual Professional Service RequiredMonthly Maintenance by owner Replacement Parts Description CF2500 Part No CF3500 Part NoFlange a Limited Warranty Information