,167$//$7,21
The hole in the right rear of the unit is a large flat oval. Mount a Listed 2 x 4 inch, "HandiBox" type junction box over the oval hole in such manner that part of the hole is left open. When installing the junc- tion box, center the box vertically over the oval hole by using the center knockout in the box. Install a ½ inch trade size cable connector or insulating bushing in the knockout. Secure the box with screws as required.
The open part of the oval hole can be either above or below the junction box depending upon the choi- ce of wire routing. The Class 2 control circuit leads will exit the open part of the hole.
Route the factory supplied main power pigtail leads through the connector from inside the unit and secu- re the connector clamp on the wires.
Install a second cable or conduit connector in ano- ther knockout in the box for the power wiring system as required. Connect the power wires and groun- ding conductors to the pigtail leads in the box using Listed wire connectors and install a cover.
Route the factory supplied control circuit pigtail leads through the open part of the oval hole from in- side the unit. Connect the room thermostat wires to the control circuit pigtail leads using a suitable Class 2 wiring connection method.
833(5/()75($5&251(52)81,7 (Facing rear of unit)
1 | 2 |
3 | 4 | 5 |
|
-XQFWLRQER[
0DLQ3RZHU3LJWDLO/HDGV
8QLW8SSHU%DFN3DQHO
2YDO+ROH