Lochinvar WH 55 - 399 manual Prevent combustion air contamination, Products to avoid

Page 4

User’s Information Manual

1 Prevent combustion air contamination

￿WARNING

￿WARNING

If the boiler combustion air inlet is located in any area likely to cause contamination, or if products which would contaminate the air cannot be removed, you must have the combustion air and vent re-piped and terminated to another location. Contaminated combustion air will damage the boiler, resulting in possible severe personal injury, death, or substantial property damage.

If the boiler combustion air inlet is located in a laundry room or pool facility, for example, these areas will always contain hazardous contaminants.

Table 1A Corrosive Contaminants and Sources

Products to avoid:

Spray cans containing chloro/fluorocarbons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the boiler, they can form strong acids. The acid can eat through the boiler wall, causing serious damage and presenting a possible threat of flue gas spillage or boiler water leakage into the building.

Please read the information listed in Table 1A. If contaminating chemicals will be present near the location of the boiler combustion air inlet, have your installer pipe the boiler combustion air and vent to another location, per the Knight Wall Mount Installation and Operation Manual.

Paint or varnish removers

Hydrochloric acid/muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms

Adhesives used to fasten building products and other similar products

Areas likely to have contaminants

Dry cleaning/laundry areas and establishments

￿WARNING

To prevent the potential of severe personal injury or death, check for areas and products listed in Table 1A before installing the boiler or air inlet piping.

If contaminants are found, you MUST:

Remove contaminants permanently. —OR—

Relocate air inlet and vent terminations to other areas.

Swimming pools

Metal fabrication plants

Beauty shops

Refrigeration repair shops

Photo processing plants

Auto body shops

Plastic manufacturing plants

Furniture refinishing areas and establishments

New building construction

Remodeling areas

Garages with workshops

4

Image 4
Contents User’s Information Manual Models WH 55 Contents Boiler service and maintenance Please read before proceedingProducts to avoid Prevent combustion air contaminationAreas likely to have contaminants Owner maintenance Maintenance schedule Service technicianSee pages 6 8 for detailed instructions Maintenance schedule Inspect/check condensate lines and fittingsClean/Inspect Trap Assembly Condensate disposalTest low water cutoff if installed Operating instructions 1Operating Instructions Models 55Operating instructions Installer Smart System control moduleUser Time and dateNight Setback Override Temperature UnitsSpace heating SH1, SH2, SH3 and tank set points Call for Heat Information Right Select no