Service Manual

1 Service

1

On

34

80

55

The Building Screen displays information that is specific to the Building Automation System and is being transmitted through the Modbus communication link:

Modbus Address - This is the address of a specific SYNC boiler. This address is set by dip switches on the Modbus communication board. The value displayed here should be the same as the value of the dip switches. The Building Automation System should use this address to communicate with the boiler.

Boiler Enable - This displays the enable status that has been transmitted to the boiler by the Building Automation System.

Boiler State - This displays the state code of the boiler. Please reference the SYNC Modbus Instruction Manual for a full definition of each code.

Boiler Command - This displays the value written to register 40003 of the Modbus communication board by the Building Automation System. The value is displayed as the percent of firing rate, 80 = 80% firing rate.

Effective Setpoint - This displays the value written to register 40003 of the Modbus communication board by the Building Automation System. The value is displayed as the effective setpoint in degrees (°F or °C).

Note: The boiler can be configured to operate off the boiler command or the effective setpoint. The boiler configuration determines which value is meaningful.

30

Image 30 Contents
Models 1.0, 1.3, Contents Handling ceramic fiber materials Niosh stated First AidService MaintenanceTroubleshooting Service Near boiler pipingSync display Control inputs BoardSecondary Smart Touch Control Module Primary Control outputsHow the control module operates General OperationHow the boiler operates Sequence of operationSequence of operation Sequence of operation space heating and HWThis table lists the parameters and where to access them Parameter tableOutdoor Reset Viewable and changeable control parameters Status ScreenService Details Screen Service Main Screen Setup Screen Service/Setup Parameters Screen Service Set Point Parameters Screen Outdoor Reset Parameters Screen Service Night Setback Parameters Screen Cascade Parameters Screen Cascade OperationPumps Parameters Screen 10Vdc BMS Parameters Screen 10Vdc OperationService Cascade Screen Service Temps Screen Burners Screen Graph Select Screen History Screen Service Mode Screen Maintenance Maintenance and annual startup Inspect boiler area Address reported problemsClean condensate trap Inspect boiler interiorFlue vent system and air piping Check water systemCheck expansion tank Check boiler relief valve Check control settings Check ignition ground wiringCheck all boiler wiring Inspect ignition and flame sense electrodesCheck flame signal Cleaning boiler heat exchangerReview with owner Test procedure Test low water flow conditionsTroubleshooting Alarm ScreenBefore troubleshooting Check the followingCheck control module fuses Operation No DisplayNo Burner Unit DoesChecking temperature sensors Temperature ResistanceOperation Boiler Pump NoisyNo Pump System PumpDrain Blocked Flow SwitchCondensate Flame outLight cont’d Flame LostWhile Running Troubleshooting Temp SW Automatic ResetHigh Limit / HEX Blower RPM’sSensor Open Louver Proving SwitchToo High Sensor ShortedLow Resets Try LaterAir Flow Too Flap ValveWriting to Internal FaultNo Error Stored MemosOr Obstruction Combustion Analysis ProcedureGas Valve Adjustment Gas Supply PressureGas valve adjustment procedure ModelModels 1.3