Lochinvar 1 service manual No Display, No Burner, Operation, Unit Does, Not Modulate, Above 50%

Page 44

Service Manual

3 Troubleshooting

Table 3A Troubleshooting Chart - No Display

FAULT

CAUSE

 

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

- No 120 VAC supplied to unit.

Check external line switch, fuse, or breaker.

 

 

 

 

Check position of ON/OFF switch. Turn switch to the

 

 

 

ON position.

 

 

 

 

 

 

 

 

• Check 120 VAC through the ON/OFF switch.

 

 

 

 

Check

wiring

harness

connection

between display

 

 

 

board

and

main

control

board.

Connect

No Display

 

 

harness at both points.

 

 

 

 

 

- No voltage through the switch.

Replace switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Bad display board.

Replace board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Bad main control board.

Replace the main control board.

 

 

 

 

 

 

 

 

 

- Blown fuse.

Replace fuse F3 on the main control board, see

 

 

 

page 43 of this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Main control board temperature set point

Review temperature setting.

 

 

 

 

 

satisfied.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Remote thermostat satisfied.

Review remote thermostat setting.

 

 

 

No Burner

 

 

 

 

 

 

 

 

 

 

- Outside air temperature above Warm

Check location of outside air sensor. Check

Operation

Weather Shutdown (WWSD) set point for

 

resistance of outdoor air sensor and compare to Table

 

 

 

main control board.

 

3D on page 45 of this manual.

 

 

 

 

 

 

 

 

 

 

 

 

- Unit locked out on fault.

Consult display for specific fault.

Refer

to

fault

 

 

 

descriptions on page 47 of this manual for corrective

 

 

 

actions.

 

 

 

 

 

 

 

 

 

 

 

 

- Ramp delay active.

Check ramp delay parameter settings. Optional PC

 

 

 

software required.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ramp delay feature off.

See

page 19 of

this

 

 

 

manual for instructions on how to turn this feature off.

Unit Does

 

 

 

 

 

 

- Boiler controlled by BMS.

• Check

BMS

parameter settings.

Optional

PC

Not Modulate

 

software required.

 

 

 

 

 

Above 50%

 

 

 

 

 

 

 

 

 

 

- Flue sensor open.

Verify that the flue sensor is located in the flue outlet.

 

 

 

 

 

 

 

 

 

Check wiring connections at the flue sensor.

 

 

 

 

 

 

 

 

Check the resistance of the flue sensor and compare

 

 

 

to Table 3C on page 45 of this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

44

Image 44
Contents Models 1.0, 1.3, Contents Handling ceramic fiber materials Niosh stated First AidTroubleshooting ServiceMaintenance Service Near boiler pipingSync display Control inputs BoardSecondary Smart Touch Control Module Primary Control outputsGeneral Operation How the boiler operatesHow the control module operates Sequence of operationSequence of operation Sequence of operation space heating and HWThis table lists the parameters and where to access them Parameter tableOutdoor Reset Viewable and changeable control parameters Status ScreenService Details Screen Service Main Screen Setup Screen Service/Setup Parameters Screen Service Set Point Parameters Screen Outdoor Reset Parameters Screen Service Night Setback Parameters Screen Cascade Parameters Screen Cascade OperationPumps Parameters Screen 10Vdc BMS Parameters Screen 10Vdc OperationService Cascade Screen Service Temps Screen Burners Screen Graph Select Screen History Screen Service Mode Screen Maintenance Maintenance and annual startup Address reported problems Clean condensate trapInspect boiler area Inspect boiler interiorCheck expansion tank Check boiler relief valve Flue vent system and air pipingCheck water system Check ignition ground wiring Check all boiler wiringCheck control settings Inspect ignition and flame sense electrodesReview with owner Check flame signalCleaning boiler heat exchanger Test procedure Test low water flow conditionsTroubleshooting Alarm ScreenCheck control module fuses Before troubleshootingCheck the following No Display No BurnerOperation Unit DoesChecking temperature sensors Temperature ResistanceNoisy No PumpOperation Boiler Pump System PumpFlow Switch CondensateDrain Blocked Flame outWhile Running Light cont’dFlame Lost Troubleshooting Automatic Reset High Limit / HEXTemp SW Blower RPM’sLouver Proving Switch Too HighSensor Open Sensor ShortedResets Try Later Air Flow TooLow Flap ValveInternal Fault No Error StoredWriting to MemosCombustion Analysis Procedure Gas Valve AdjustmentOr Obstruction Gas Supply PressureModels 1.3 Gas valve adjustment procedureModel
Related manuals
Manual 20 pages 6.19 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb Manual 80 pages 59.46 Kb Manual 56 pages 40.75 Kb

1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.