Bryant BW2, BW4B, BS1, BW1, BS2, BW5B, BW3 manual Models BW9, Specifications

Page 5

MODELS BW9

The BW9 is a gas fired direct vent condensing hot water boiler with cast aluminum heat exchanger sections. A revolutionary cast aluminum heat exchanger means better heat transfer and thermal storage than similarly sized cast iron boiler, which results in higher efficiency. The heating system water absorbs large amounts of heat from the cast aluminum heat exchanger, cooling the flue gases and causing condensation. Sealed combustion, premix gas burner, and low flame temperature means drastically reduced CO and NOx emissions, which contribute to a cleaner and healthier environment.

The BW9, unlike normal residential atmospheric and induced draft boilers, takes its combustion air directly from the outdoors (sealed combustion) and does not compete with building occupants for fresh air. Sealed combustion (also known as “direct vent”) is the safest and best way to obtain plenty of clean combustion air. The induced draft fan draws in the outside combustion air, then takes the cooler flue gases from the heat exchanger and provides a positive removal of the flue gases from the building through inexpensive and readily available PVC and CPVC pipes.

FEATURES

RANGE OF CAPACITIES—Three sizes ranging from 50,000 through 100,000 Btuh input.

COMPLETELY PACKAGED—Each boiler is completely assembled, including all controls (except room thermostat). All necessary wiring is factory installed. The boiler is ready for gas piping, room thermostat, and electrical power connections as shipped. Circulator is shipped pre-wired with 6 ft bx conduit for easy installation for supply side pumping.

VENTING—This boiler is direct vented with PVC and CPVC pipe. See the Installation Instructions for common venting requirements.

ALUMINUM SECTIONS—These sections speed heat transfer to the boiler water. With faster thermal response, greater comfort and economy are achieved.

PRE-MIXBURNER—Provides quiet operation and improved combustion efficiency.

CONTROLS—Integrated Boiler Control provides safe, dependable operation of burners. Factory-installed safety components provide maximum safety against overheating, pressure buildup, and low-water operation.

SECTIONS TESTED—Each section is hydrostatically tested to 50 psig. Individual sections are tested to 125 psig at factory. Assembled sections are tested to 75 psig at the factory. The maximum allowable pressure is 50 psig for hot water boilers.

PROPANE CONVERTIBLE—With factory approved conversion kit accessory.

WARRANTY—The aluminum sections are covered by a limited 15-year warranty on the entire assembly. Circulator pump is covered by a limited 3-year warranty. All other parts are covered by a 1-year limited warranty.

SPECIFICATIONS

UNIT SIZE

050

075

100

 

Sections

 

 

1

 

 

 

GAS CONTROLS

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Valve

 

 

Honeywell

 

 

 

Inlet Size

In.

 

1/2

 

 

 

Ignition

 

 

Hot Surface Ignition

 

 

 

Burner—Stainless/Titanium Alloy

 

 

1

 

 

 

 

 

 

 

 

 

 

Burner Orifice

No.

0.0615

#48

#44

 

 

CONTROLS

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit Control Range

°F

 

100-200

 

 

 

 

 

 

 

 

 

 

Pressure Relief Valve Setting

Psig

 

30

 

 

 

 

 

 

 

 

 

 

Integrated Boiler Control

 

 

UTEC factory installed

 

 

 

 

 

 

 

 

 

 

CIRCULATOR

 

 

 

 

 

 

 

 

 

 

 

 

 

Taco

Model

 

007

 

 

 

Full Load Amps

 

 

2.0 AMPS/330 WATTS

 

 

 

 

 

 

 

 

 

 

Flange Size FPT

In.

 

1-1/4

 

 

 

 

 

 

 

 

 

—5—

Image 5
Contents Model BW4B, BW5B Model BW9 Model BW1, BW2 Model BW3Model BS1, BS2 Model Number Nomenclature Boiler AccessoriesBW9AAN000075AAAA DescriptionBW4/BW5 Standard Boiler Warranties Yrs Circulator CurveWater Boiler Circulator Curve ALL ModelsModels BW9 SpecificationsClearances DimensionsRatings and Capacities Unit Type Btuh Capacity Btuh Afue %General Data Models BS1 and BS2Unit Size Vent Diameter Models BS1 and BS2Models BW1 and BW2 Sections Unit Size Vent ConnectionShip GAS Controls Intermittent Pilot Model BW3Unit Type Btuh BW3 ModelsModels BW4 and BW5 Ratings and Performance