Bryant BW4B, BW1, BW5B, BW2, BW3, BW9 manual Models BS1 and BS2, Unit Size Vent Diameter

Page 8

 

 

DIMENSIONS

 

 

 

 

MODELS BS1 and BS2

 

 

VENT

PRESSURE

 

 

DAMPER

26 12

 

RELIEF

 

GAGE

 

 

 

4 34

 

VALVE

 

 

2 12

 

 

TRANSFORMER

 

 

 

 

 

 

 

PRESSURE

 

GLASS

 

 

 

GAGE

 

 

LIMIT CONTROL

 

WATER

2 12N.P.T.

 

LOW WATER

 

 

 

LINE

 

 

CUT-OFF

 

 

29

36 38

LOW WATER

2 12

24

 

 

 

CUT-OFF PROBE

S86

 

12 14

 

 

GAS

 

 

 

 

 

 

 

 

VALVE

 

 

 

GAS LINE

 

 

 

 

A

 

 

LEFT SIDE

 

FRONT

RIGHT SIDE

 

DIMENSIONS (In.)

UNIT SIZE

A

VENT DIAMETER

 

 

 

075

11-1/4

5

 

 

 

112

14-1/2

6

150

17-3/4

6

187

21

7

 

 

 

225

24-1/4

7

262

27-1/2

7

299

30-3/4

7

 

CLEARANCES (In.)

 

 

RIGHT SIDE

 

6*

LEFT SIDE

 

6*

TOP

 

6*

BACK

 

6*

FRONT

 

6*

*Service clearance requirement 24 in.

RATINGS AND CAPACITIES*

 

GAS

NUMBER

MAX

HEATING

NET RATING

 

APPROX

 

OF

INPUT

CAPACITY

 

 

AFUE %

SHIP.

 

 

 

UNIT

TYPE

SECTIONS

(BTUH)

(BTUH)

Btuh

Sq Ft

(WITH DAMPER)

WT (Lb)

 

 

 

 

 

 

 

 

 

BS1AAN075

Natural

3

75,000

62,000

47,000

196

81.1

256

BS1AAN112

Natural

4

112,500

91,000

68,000

283

78.8

404

 

 

 

 

 

 

 

 

 

BS1AAN150

Natural

5

150,000

122,000

92,000

383

79.2

483

 

 

 

 

 

 

 

 

 

BS1AAN187

Natural

6

187,500

153,000

115,000

479

79.6

564

BS1AAN225

Natural

7

225,000

183,000

137,000

571

80.1

649

 

 

 

 

 

 

 

 

 

BS1AAN262

Natural

8

262,500

214,000

161,000

671

80.5

719

 

 

 

 

 

 

 

 

 

BS1AAN299

Natural

9

299,000

245,000

184,000

767

80.9

800

BS2AAN075

Natural

3

75,000

62,000

47,000

196

82.7

256

 

 

 

 

 

 

 

 

 

BS2AAN112

Natural

4

112,500

91,000

68,000

283

80.4

404

 

 

 

 

 

 

 

 

 

BS2AAN150

Natural

5

150,000

122,000

92,000

383

80.6

483

BS2AAN187

Natural

6

187,500

153,000

115,000

479

80.9

564

 

 

 

 

 

 

 

 

 

BS2AAN225

Natural

7

225,000

183,000

137,000

575

81.1

649

 

 

 

 

 

 

 

 

 

BS2AAN262

Natural

8

262,500

214,000

161,000

671

81.3

719

BS2AAN299

Natural

9

299,000

245,000

184,000

767

81.6

800

 

 

 

 

 

 

 

 

 

*Ratings are for altitudes to 2000 ft. Ratings for units for altitudes over 2000 ft are 4% less for each 1000 ft above sea level. Ratings in sq ft are computed at 240 Btuh/sq ft for steam boilers.

—8—

Image 8
Contents Model BW4B, BW5B Model BW9 Model BW1, BW2 Model BW3Model BS1, BS2 Boiler Accessories Model Number NomenclatureBW9AAN000075AAAA DescriptionBW4/BW5 Circulator Curve Standard Boiler Warranties YrsWater Boiler Circulator Curve ALL ModelsSpecifications Models BW9Dimensions ClearancesRatings and Capacities Unit Type Btuh Capacity Btuh Afue %Models BS1 and BS2 General DataModels BS1 and BS2 Unit Size Vent DiameterModels BW1 and BW2 Sections Unit Size Vent ConnectionShip Model BW3 GAS Controls Intermittent PilotBW3 Models Unit Type BtuhModels BW4 and BW5 Ratings and Performance