Crown Boiler AWI128, TWI095, TWI128, TWI061, TWI162, AWI061, AWI195, AWI162 Start-up and Checkout

Page 23

X Start-up and Checkout

NOTE

SAFE LIGHTING AND OTHER PERFORMANCE CRITERIA WERE MET WITH THE GAS MANIFOLD AND CONTROL ASSEMBLY PROVIDED ON THE BOILER WHEN THE BOILER UNDERWENT THE TESTS SPECIFIED IN Z21.13.

Use the following procedure for initial start-up of the boiler:

1)Make sure that the boiler and system are filled with water.

2)Check all new gas piping for leaks and purge piping sections that are filled with air. See Part 4 of the National Fuel Gas Code for additional information on testing and purging gas lines.

WARNING

NEVER USE A FLAME TO CHECK FOR GAS LEAKS.

MAKE SURE THAT THE AREA AROUND THE BOILER IS CLEAR AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE, AND OTHER FLAMMABLE VAPORS AND LIQUIDS.

3)Verify that vent system is complete and free of obstructions before attempting to fire boiler.

4)Inspect all wiring for loose or uninsulated connections.

5)Make sure the main burners are seated properly in the rear of burner tray and on orifices.

6)Adjust thermostat to the highest setting.

7)Start the boiler using the lighting instructions for boilers with standing pilot (page 24) or operating instructions for boilers with intermittent ignition (page 25).

8)Upon initial start-up, the gas train will be filled with air. Even if the gas line has been completely purged of air, it may take several tries for ignition before a flame is established. Once a flame has been established for the first time, subsequent calls for burner operation should result in a flame on the first try.

9)Observe pilot burner flame:

See Figure 20 for standing pilot. Pilot burner should produce single steady medium blue flame covering around 3/8” to ½” of thermocouple tip.

See Figure 21 for intermittent ignition. Pilot burner produces three flames. The center one should be a steady medium blue flame covering around 3/8” to ½” of spark electrode/flame rod.

10)Make sure vent damper is in open position when main burners are firing.

11)Inspect the main burner flames visible through the observation port in burner access panel. The flame should be stable and mostly blue (see Figure 22 or 23). No yellow tipping should be present; however, intermittent flecks of yellow and orange in the flame are normal.

12)Check entire gas train for leaks using soap and water or other approved leak detection method while boiler is firing. Fix any leaks found immediately.

23

21

Image 23
Contents Crown Inside Front Cover Leave Blank Product Description Table of ContentsII Specifications Bleftpipedconfiguration Specifications IV Locating the Boiler III Before InstallingFor Buildings of Other than Unusually Tight Construction Air for Combustion and VentilationExample ALL AIR from Outdoors Ventilated Crawl Space and Attic For Buildings of Unusually Tight ConstructionVI Venting ALL AIR from OUTDOORS, Using Openings Into Boiler RoomTypicalventsystem Installation and Components 1210 Removing an Existing Boiler from a Common ChimneyGAS Connection to Boiler VII Gas PipingStandardPiping Viii System PipingStandard Boiler Piping Piping for Special SituationsIndirect Water Heater Boiler Bypass Piping Single Zone Wiring IX WiringWiring DIAGRAM, Continuous Ignition Circulator Zonewiring Using HONEYWELLR845As Wiring VariationsSequence of Operation, Standing Pilot AWI/TWI Control System Sequence of OperationSequence of Operation, Intermittent Ignition Start-up and Checkout Page Standing Pilot Burner Flame For Your Safety Read Before Operating For Your Safety Read Before Lighting GAS Valve Detail Standing Pilot XI Service and Maintenance Heat Exchanger Cleaning Procedure XII Troubleshooting AWI/TWI Troubleshooting Chart END Standing Pilot Ignition System Troubleshooting Chart Intermittent Ignition System Troubleshooting Chart Xiii Parts Base-Block-Hood Below 2000 ft Burner Components KEY # Description QTY. or Quantity PER Boiler or Crown P.N Jacket/Components Crown

AWI262, AWI095, TWI095, AWI195, AWI037 specifications

Crown Boiler is a renowned name in the heating industry, providing high-quality, efficient heating solutions that cater to various residential and commercial needs. Among its impressive lineup, the AWI and TWI series stand out for their design, technology, and performance.

The Crown Boiler AWI061 and TWI061 are part of the Hydronic Boiler range, designed to deliver efficient hot water heating. The AWI series features an advanced pressure-jet design that allows it to operate with exceptional fuel efficiency, reducing operating costs for homeowners and businesses alike. Additionally, these models come equipped with an integrated pump system that ensures a consistent supply of hot water, making them ideal for both space heating and domestic hot water applications.

Meanwhile, the AWI162 and AWI128 models are engineered for higher output, addressing larger heating needs without compromising efficiency. These models showcase a robust heat exchanger made of durable cast iron, promoting longevity and effective heat transfer. The AWI series boilers feature a modern control system that allows for precise temperature management, enhancing comfort while minimizing energy consumption.

The Crown Boiler AWI295, on the other hand, steps up with a significant heating capacity suited for commercial applications. This model is designed with advanced safety and efficiency technologies, including an intelligent control module that monitors temperature and pressure, ensuring optimal performance while preventing malfunctions. The large water volume design allows for enhanced thermal stability and consistent heating output.

A notable characteristic across these models is their ease of installation and maintenance. Crown Boiler has engineered the units with user-friendly features, including accessible components and simplified diagnostics that help technicians service the boilers swiftly. Moreover, the durability of cast iron construction ensures that these units can withstand high thermal stress while delivering reliable performance over the years.

In summary, Crown Boiler’s AWI061, TWI061, AWI162, AWI128, and AWI295 models offer a range of solutions equipped with advanced technologies and features designed for efficiency and reliability. These boilers are suitable for diverse heating needs, promising optimal comfort and convenience in both residential and commercial settings. With Crown Boiler's longstanding commitment to quality, customers can be assured of a robust heating solution backed by exceptional service.