Crown Boiler BWC120, BWC090, BWC070 installation manual

Page 3

2)Maximum Vent and Air Intake Lengths - The maximum length of the vent air intake piping depends upon the vent option selected and the boiler size. See Table 7.1 or 7.9 for the maximum vent length. In horizontal vent systems, the lengths shown in Table 7.1 are in addition to the first standard elbow on top of the boiler. For vertical vent systems, the maximum vertical vent lengths shown in Table 7.9 are in addition to two standard radius elbows. If more elbows are desired, the maximum allowable vent length must be reduced by the amount shown in Table 7.8 for each additional elbow used. Termination fittings are never counted, although the length of the concentric terminal section is counted.

Example:

A 60/100mm concentric vent system is planned for a horizontally vented BWC120 which has the following components:

80/125 x 60/100mm Reducing Elbow (supplied with the boiler) 5ft Straight Pipe

90 elbow

1-1/2ft Straight Pipe 45Elbow

Uncut Terminal Section (supplied with the boiler)

The Vent Option #1 column in Table 7.1 describes a horizontal direct vent system using 60/100mm concentric vent pipe. From this column, we see that a BWC120 may have a vent length of up to 18ft. The 90 degree reducing elbow is not considered. The length of the terminal section (not including the plastic terminal itself) is approximately 22 1/2” (1.9ft) installed. From Table 7.8, we see that the equivalent length of the 60/100mm elbow is 4.5ft and that the equivalent length of the 45 degree elbow is 4ft. The total equivalent length of the planned venting system is therefore:

5ft (Straight ) + 4.5ft (90 Elbow) + 1.5ft (Straight ) + 4 ft (45 Elbow) + 1.9ft (Uncut Terminal Section) = 16.9ft.

Since Table 7.1 shows a maximum allowable vent length of 18ft, the planned vent system length is acceptable.

3)Minimum Vent and Air Intake Lengths - Observe the minimum vent lengths shown in tables 7.1 and 7.9.

4)Permitted Terminals for Horizontal Venting:

Vent Option 1 - The 60/100mm concentric vent terminal is supplied with the boiler as part of the standard vent system.

Vent Option 2 - The exhaust terminal is Crown PN 230511. The air intake fitting is a 90 degree elbow with a rodent screen supplied by the installer. This elbow is made out of the same material as the rest of the air inlet system (either galvanized or PVC) and is installed as shown in Figure 7.3.

Vent Option 3 - Two terminals are permitted:

a)80/125mm Concentric Vent Terminal (Crown PN 230531)

b)80/125mm Snorkel Terminal (Crown PN 230540) . This terminal allows the vent system to exit the building close to grade and go up the exterior wall far enough to provide adequate clearance between the terminal itself and the snow line (Figure 7.7).

5)Horizontal Vent and Air Intake Terminal Location - Observe the following limitations on the vent terminal location (also see Figures 7.6, 7.7). When locating a concentric terminal, observe the limitations outlined below for “vent terminals”.

Vent terminals must be at least 1 foot from any door, window, or gravity inlet into the building.

For twin pipe terminals, maintain the correct clearance and orientation between the vent and air intake terminals. The vent and air intake terminals must be at the same height and their center lines must be between 12 and 36 inches apart. Both terminals must be located on the same wall.

The bottom of all terminals must be at least 12” above the normal snow line. In no case should they be less than 12” above grade level.

The bottom of the vent terminal must be at least 7 feet above a public walkway.

Do not install the vent terminal directly over windows or doors.

The bottom of the vent terminal must be at least 3 feet above any forced air inlet located within 10 feet.

A clearance of at least 4 feet horizontally must be maintained between the vent terminal and gas meters, electric meters, regulators, and relief equipment. Do not install vent terminal over this equipment.

Do not locate the vent terminal under decks or similar structures.

Top of vent terminal must be at least 5 feet below eves, soffits, or overhangs. Maximum depth of overhang is 3 ft.

12

Image 3
Contents Page VII Venting Page Summary of Horizontal Venting Options Horizontal Concentric Venting Vent Option 1,3 Vent Option Manufacturer Vent Size Component Part Number 6c Positioning Vent Terminal Under Overhangs Snorkel Terminal Configuration VENT/ AIR Intake Fitting Equivalent Length 10 Vertical Twin Pipe Vent System Vent Option Removing an Existing Boiler From a Common Chimney Page 21 Dimension L 22 Cutting Outer Pipe 25 Attaching 60/100mm Terminal Section 30a Cuttable Straight Section 31 Cutting Straight Pipe 32a Joining Cuttable Pipe 33a Dimension L, 80/125mm Horizontal Terminal 33c Cutting Inner Pipe of 80/125mm Horizontal Terminal 34 Installation of Snorkel Terminal 35a Dimension H 35b Cutting Vertical Terminal 36 Chimney Chase Installation Assembly of Stainless Steel Venting 47 CORR/GUARD Connection to Vent Collar

BWC120, BWC070, BWC090 specifications

Crown Boiler Company has established itself as a leader in the heating industry, providing reliable and efficient solutions for residential and commercial applications. Among their innovative product line, the BWC series, which includes the BWC120, BWC070, and BWC090 models, showcases advanced technology and design features that cater to the diverse needs of consumers.

The BWC series is designed to deliver exceptional heating performance while being user-friendly and efficient. One of the main features of these models is their compact design, making them suitable for installations in tight spaces, such as basements and utility rooms. This space-saving advantage does not compromise their power or heating capacity, as each model is engineered to handle a variety of heating demands.

A prominent technology in the BWC series is the high-efficiency, modulating condensing design. This allows the boilers to adjust their output based on the heating requirements of the space, leading to significant energy savings. By utilizing a variable-speed blower and an integrated control system, these boilers can operate at lower heating outputs when the demand is lower, ultimately improving overall efficiency and reducing fuel costs.

The BWC120, with an output of 120 MBH, is ideal for larger homes or light commercial applications, providing robust heating capabilities. The BWC090 offers a slightly lower output at 90 MBH, catering to moderately sized homes. Meanwhile, the BWC070 targets smaller residential settings with an output of 70 MBH, ensuring that there is a fitting option for a variety of heating needs.

In addition to their efficiency and compact design, the BWC models are equipped with advanced safety features, including built-in temperature and pressure relief valves. These safety measures give homeowners peace of mind, knowing that their heating system is operating safely and reliably.

Durability is another characteristic that defines the BWC series. Constructed with high-quality materials and designed to withstand the rigors of everyday use, these boilers are built to last. The easy-to-service construction ensures that routine maintenance is straightforward, thereby enhancing longevity and reliability.

In summary, the Crown Boiler BWC120, BWC070, and BWC090 models combine efficiency, advanced technology, and safety features, making them an excellent choice for anyone in the market for dependable heating solutions. Their adaptability to various heating needs, along with their space-saving designs, makes them suitable for a wide range of applications, ensuring comfort and reliability for years to come.